Plan Review Details - Permit 19110540
Plan Review Stops For Permit 19110540
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-01-27 Cont ID  
Sent By dbattles Date 2020-01-27 Time 13:44 Rev Time 0.00
Received By dbattles Date 2020-01-27 Time 11:15 Sent To  
Notes
2020-01-27 14:16:42PROVISOS:
 HANDRAIL/GUARDRAIL ENGINEERING
 ROOFING PRODUCT APPROVALS WITH SUB PERMIT APPLICATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-12-11 Cont ID  
Sent By dbattles Date 2019-12-11 Time 10:34 Rev Time 0.00
Received By dbattles Date 2019-12-10 Time 15:56 Sent To  
Notes
2019-12-11 10:34:46BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19110540
 REVIEWED: DECEMBER 10, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1) 107.3.5 FBC[AMENDED]THE COVER SHEET SHOWS EXISTING
 AND PROPOSED SQ. FOOTAGE FOR BOTH MAIN HOUSE AND
 GARAGE. THIS WILL BE GOING PBC IMPACT REVIEW AND IT
 APPEARS AS IF WORK IS BEING DONE ON BOTH STRUCTURES.
 THE NEXT SHEET A0.02 SAYS HATCH AREA DENOTES AREA OF
 WORK AND THE REMAINING PLANS INDICATE THAT THE GARAGE
 (HATCHED AREA) IS THE ONLY AREA OF WORK.
 PLEASE ADJUST DATA ON COVER TO CLARIFY AREA OF WORK
 EXISTING AND NEW AREA ADDED.
 SHEET A.0.02 MENTIONS ADDITIONS. IS THE ONLY WORK BEING
 DONE ON THE SITE THE 2 STORY BUILDING THAT IS HATCHED?
  
 2) 501 FBC[EXISTING]PLEASE PUT CLASSIFICATION OF WORK
 ON PLANS FOR ANY AREA OF WORK TO BE PERFORMED.
  
 3) 107.3.5 FBC[AMENDED]PROVIDE PRODUCT APPROVALS FOR
 NEW COVERED ROOF AREA AT STAIR LANDING, OR INDICATE
 THAT IT WILL BE DEFERRED UNTIL ROOFING SUB PERMIT
 APPLICATION.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-11-21 Cont ID  
Sent By jpearson Date 2019-11-21 Time 07:27 Rev Time 0.00
Received By jpearson Date 2019-11-21 Time 06:36 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-01-25 Cont ID  
Sent By gjohnson Date 2020-01-25 Time 09:53 Rev Time 0.00
Received By gjohnson Date 2020-01-25 Time 09:53 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-11-21 Cont ID  
Sent By gjohnson Date 2019-11-21 Time 15:52 Rev Time 0.00
Received By gjohnson Date 2019-11-21 Time 15:52 Sent To  
Notes
2019-11-21 15:52:401ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE PLUMBING SHEETS ARE SEALED BY AN ENGINEER BUT
 THEY ARE NOT SIGNED AND DATED THEY SHALL COMPLY WITH
 FAC 61G15-23.003 PROCEDURES FOR PHYSICALLY SIGNING AND
 SEALING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS.
 ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN
 ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025,
 F.S., AND RULE 61G15-23.001, F.A.C. MAY BE PHYSICALLY
 SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT BE
 USED.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2019-11-26 Cont ID  
Sent By fmittner Date 2019-11-26 Time 16:47 Rev Time 0.00
Received By fmittner Date 2019-11-26 Time 16:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-01-29 Cont ID  
Sent By dbattles Date 2020-01-29 Time 10:12 Rev Time 0.00
Received By dbattles Date 2020-01-14 Time 13:59 Sent To  
Notes
2020-01-15 13:59:51R03

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-12-13 Cont ID  
Sent By cmontell Date 2019-12-13 Time 12:19 Rev Time 0.00
Received By cmontell Date 2019-12-13 Time 12:19 Sent To  
Notes
2019-12-13 08:06:52TO CM DESK
2019-11-14 13:34:41R02

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2020-01-27 Cont ID  
Sent By dbattles Date 2020-01-27 Time 13:41 Rev Time 0.00
Received By dbattles Date 2020-01-27 Time 11:16 Sent To  
Notes
2020-01-27 13:44:46OK-PLANS STAMPED
 NO MU # SINCE NO FEES ACCESSED.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-12-10 Cont ID  
Sent By dbattles Date 2019-12-10 Time 16:02 Rev Time 0.00
Received By dbattles Date 2019-12-10 Time 16:02 Sent To  
Notes
2019-12-10 16:02:41109 FBC[AMENDED] PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. ?CALL (561) 233-5025. ?UPON APPROVAL, YOU
 MAY CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. ?PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-01-29 Cont ID  
Sent By hmoser Date 2020-01-29 Time 09:23 Rev Time 0.00
Received By hmoser Date 2020-01-29 Time 09:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-12-13 Cont ID  
Sent By cmontell Date 2019-12-13 Time 12:19 Rev Time 0.00
Received By cmontell Date 2019-12-13 Time 12:17 Sent To I
Notes
2019-12-13 12:19:02MECHANICAL PLAN REVIEW FAIL
  
 1. THE PLANS ARE SEALED BY AN ENGINEER BUT THEY ARE NOT
 SIGNED AND DATED THEY SHALL COMPLY WITH FAC
 61G15-23.003 PROCEDURES FOR PHYSICALLY SIGNING AND
 SEALING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS.
 ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN
 ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025,
 F.S., AND RULE 61G15-23.001, F.A.C. MAY BE PHYSICALLY
 SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT BE
 USED.
  
 CHRIS MONTELLO
 561-805-6733

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-01-25 Cont ID  
Sent By gjohnson Date 2020-01-25 Time 09:54 Rev Time 0.00
Received By gjohnson Date 2020-01-25 Time 09:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-11-21 Cont ID  
Sent By gjohnson Date 2019-11-21 Time 15:42 Rev Time 0.00
Received By gjohnson Date 2019-11-21 Time 15:42 Sent To  
Notes
2019-11-21 15:51:441ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE PLUMBING SHEETS ARE SEALED BY AN ENGINEER BUT
 THEY ARE NOT SIGNED AND DATED THEY SHALL COMPLY WITH
 FAC 61G15-23.003 PROCEDURES FOR PHYSICALLY SIGNING AND
 SEALING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS.
 ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN
 ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025,
 F.S., AND RULE 61G15-23.001, F.A.C. MAY BE PHYSICALLY
 SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT BE
 USED.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 3 Status P Date 2020-01-30 Cont ID  
Sent By dbattles Date 2020-01-30 Time 14:12 Rev Time 0.00
Received By dbattles Date 2020-01-30 Time 14:12 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 2 Status F Date 2020-01-29 Cont ID  
Sent By dbattles Date 2020-01-27 Time 13:39 Rev Time 0.00
Received By dbattles Date 2020-01-27 Time 13:38 Sent To  
Notes
2020-01-27 13:41:42OK-NOTIFICATION TO BUILDING OFFICIAL PROVIDED
  
 COMPLIANCE AFFIDAVIT:
 PLEASE UPDATE THE AFFIDAVIT TO BREAKDOWN WHAT SHEETS
 WERE REVIEWED AND BY WHICH PLANS EXAMINER.
 ALSO, MAKE SURE THE REVIEWERS LISTED MATCHES THE STAMPS
 ON THE DRAWINGS.
  
 DYLAN BATTLES
 561-805-6718
 [email protected]
  
 THE CITY OF WEST PALM BEACH
 BUILDING PLANS EXAMINER PX4191
  
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status F Date 2019-11-21 Cont ID  
Sent By shill Date 2019-11-21 Time 17:33 Rev Time 0.00
Received By shill Date 2019-11-21 Time 17:33 Sent To  
Notes
2019-11-21 17:38:26****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 FLORIDA 553.791, SOMEONE INFORMED THE FRONT COUNTER
 THAT THIS PROJECT IS PRIVATE PROVIDER. THE PRIVATE
 PROVIDER AFFIDAVIT AND THE NOTICE TO BUILDING OFFICIAL
 WERE NOT SUBMITTED, PLANS ARE STAMPED, INTENT IS NOT
 CLEAR. IF THIS IS PRIVATE PROVIDER, PROVIDE THE
 DOCUMENTS REQUIRED VIA EMAIL, ORIGINALS TO BE PROVIDED
 AT TIME OF PICKUP OR RESUBMITTAL.
  
 PLEASE SUBMIT REQUIRED DOCUMENTS TO [email protected].
  
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2020-01-27 Cont ID  
Sent By dbattles Date 2020-01-27 Time 13:35 Rev Time 0.00
Received By dbattles Date 2020-01-27 Time 11:16 Sent To  
Notes
2020-01-27 13:38:48PROVIDE ROFFING PRODUCT APPROVALS WITH SUB PERMIT
 APPLICATION.
 ADD HISTORICAL STOP FOR SUB PERMIT REVIEW OF MATERIAL.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-12-11 Cont ID  
Sent By dbattles Date 2019-12-11 Time 10:42 Rev Time 0.00
Received By dbattles Date 2019-12-10 Time 16:05 Sent To  
Notes
2019-12-11 10:43:02SEE BUILDING COMMENTS

Review Stop Z ZONING
Rev No 1 Status P Date 2019-11-26 Cont ID  
Sent By fmittner Date 2019-11-26 Time 16:47 Rev Time 0.00
Received By fmittner Date 2019-11-26 Time 16:47 Sent To  
Notes
***NONE***