Plan Review Details - Permit 19110539
Plan Review Stops For Permit 19110539
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2020-05-26 Cont ID  
Sent By jwitmer Date 2020-05-26 Time 09:14 Rev Time 0.00
Received By jwitmer Date 2020-05-26 Time 09:04 Sent To  
Notes
2020-05-26 09:08:492017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19110539 (FA?ADE RENOVATIONS & NEW
 COMPONENTS AND CLADDING)
 ADD: 600 NORTHPOINT PARKWAY
 CONT:TBD/ TO BE DETERMINED
 TEL: ?????? CONTACT: ASHLEE CALLAHAN
 E-MAIL:[email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 PERMITS ASSOCIATED WITH THE OVERALL PROJECT.
 19110539 FAADE RENOVATIONS & NEW CLADDING
 ???????? PORTE COCHERE NOT APPLIED FOR
 19120240 INT. REMODEL OF GUEST ROOMS
 19120241 INT. REMODEL OF CORRIDORS & PUBLIC SPACES.
  
 4TH& 5TH REVIEW
 DATE: MAY FRI.15/ 2020,/ MAY TUES26TH/ 2020.
 ACTION: BUILDING PROVSO
  
  
 1) PROVISO: PORT COCHERE TO BE UNDER SEPARATE PERMIT
 AND ASSOCIATED FEES. APPLY SEPARATELY NOT UNDER THIS
 PERMIT.
 2) PROVISO: THE REPLACEMENT PORTE COCHERE IS TO BE
 PROVIDED BY THE OWNER AND INSTALLED BY OTHERS (ANOTHER
 CONTRACTOR
 3-4) PROVISO: THE DESIGNER OF RECORD HAS STATED THAT
 THE PORTE COCHERE WILL BE UNDER SEPARATE PERMIT,
 REVIEWS AND ASSOCIATED FEES. TO DATE NO PERMIT
 APPLICATION HAS BEEN APPLIED FOR.
 5) PROVISO: THE NEW REPLACEMENT PORTICO WILL REQUIRE
 FIRE SPRINKLERS TO BE CONSIDERED PART OF THE MAIN
 BUILDING BEING FIRE SPRINKLERED ALREADY.
 11) PROVISO/ DEFERRED SUBMITTALS, PRODUCT APPROVALS FOR
 COMPONENTS & CLADDING.
  
 JAMES A. WITMER BN, PX, SFP & CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-05-15 Cont ID  
Sent By jwitmer Date 2020-05-15 Time 07:11 Rev Time 0.00
Received By jwitmer Date 2020-05-15 Time 06:30 Sent To  
Notes
2020-05-15 07:10:562017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19110539 (FA?ADE RENOVATIONS & NEW
 COMPONENTS AND CLADDING)
 ADD: 600 NORTHPOINT PARKWAY
 CONT:TBD/ TO BE DETERMINED
 TEL: ?????? CONTACT: ASHLEE CALLAHAN
 E-MAIL:[email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 PERMITS ASSOCIATED WITH THE OVERALL PROJECT.
 19110539 FAADE RENOVATIONS & NEW CLADDING
 ???????? PORTE COCHERE NOT APPLIED FOR
 19120240 INT. REMODEL OF GUEST ROOMS
 19120241 INT. REMODEL OF CORRIDORS & PUBLIC SPACES.
  
 4TH REVIEW
 DATE: MAY FRI.15/ 2020
 ACTION: BUILDING PROVSO
  
  
 1) PROVISO: PORT COCHERE TO BE UNDER SEPARATE PERMIT
 AND ASSOCIATED FEES. APPLY SEPARATELY NOT UNDER THIS
 PERMIT.
 2) PROVISO: THE REPLACEMENT PORTE COCHERE IS TO BE
 PROVIDED BY THE OWNER AND INSTALLED BY OTHERS (ANOTHER
 CONTRACTOR
 3-4) PROVISO: THE DESIGNER OF RECORD HAS STATED THAT
 THE PORTE COCHERE WILL BE UNDER SEPARATE PERMIT,
 REVIEWS AND ASSOCIATED FEES. TO DATE NO PERMIT
 APPLICATION HAS BEEN APPLIED FOR.
 5) PROVISO: THE NEW REPLACEMENT PORTICO WILL REQUIRE
 FIRE SPRINKLERS TO BE CONSIDERED PART OF THE MAIN
 BUILDING BEING FIRE SPRINKLERED ALREADY.
 11) PROVISO/ DEFERRED SUBMITTALS, PRODUCT APPROVALS FOR
 COMPONENTS & CLADDING.
  
 JAMES A. WITMER BN, PX, SFP & CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-05-26 Cont ID  
Sent By jwitmer Date 2020-05-13 Time 08:57 Rev Time 0.00
Received By jwitmer Date 2020-05-11 Time 06:30 Sent To  
Notes
2020-05-13 08:51:492017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19110539 (FA?ADE RENOVATIONS & NEW
 COMPONENTS AND CLADDING)
 ADD: 600 NORTHPOINT PARKWAY
 CONT:TBD/ TO BE DETERMINED
 TEL: ?????? CONTACT: ASHLEE CALLAHAN
 E-MAIL:[email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 PERMITS ASSOCIATED WITH THE OVERALL PROJECT.
 19110539 FA?ADE RENOVATIONS & NEW CLADDING
 ???????? PORTE COCHERE
 19120240 INT. REMODEL OF GUEST ROOMS
 19120241 INT. REMODEL OF CORRIDORS & PUBLIC SPACES.
  
 3RD REVIEW
 DATE: MAY MON. - WED11-13/ 2020
 ACTION: DENIED
  
 **** COMMENT # 6 DENIED. NOTE MONDAY I REACHED OUT TO
 THE ARCHITECT CR ARCHITECTS TO SEE ABOUT RED LINING
 DRAWINGS. I ASKED TO SPEAK TO THE ARCHITECT DAVID
 ARENDS, THEY PUT ME THROUGH TO ERWIND (#2108) AND
 RECEIVED HIS VOICE MAIL. I HAVE CALLED THIS NUMBER
 TWICE AND RECEIVED NO RETURN TELEPHONE CALLS, I AM
 WORKING FROM HOME AND EVEN LEFT MY CELL PHONE NUMBER
 561-718-9724 TO GET BACK IN TOUCH WITH ME.
  
 1) PROVISO: PORT COCHERE TO BE UNDER SEPARATE PERMIT
 AND ASSOCIATED FEES. APPLY SEPARATELY NOT UNDER THIS
 PERMIT.
  
 2) PROVISO: THE REPLACEMENT PORTE COCHERE IS TO BE
 PROVIDED BY THE OWNER AND INSTALLED BY OTHERS (ANOTHER
 CONTRACTOR
  
 3-4) PROVISO: THE DESIGNER OF RECORD HAS STATED THAT
 THE PORTE COCHERE WILL BE UNDER SEPARATE PERMIT,
 REVIEWS AND ASSOCIATED FEES. TO DATE NO PERMIT HAS BEEN
 APPLIED FOR.
  
 5) PROVISO: THE NEW REPLACEMENT PORTICO WILL REQUIRE
 FIRE SPRINKLERS TO BE CONSIDERED PART OF THE MAIN
 BUILDING BEING FIRE SPRINKLERED ALREADY.
  
  
 6) 3RD REQUEST, SEMI-COMPLIED. SHEET G-100. THE
 STANDARD PARKING DETAIL AS SHOWN SHOWS AN OVERALL WIDTH
 OF 16 INCHES WIDE WITH 2 4 INCH STRIPES AND A 8 INCHES
 BETWEEN THE STRIPES. THE CITY STANDARD IN THE MUNI CODE
 IS 2 4 INCH STRIPES WITH 12 INCHES BETWEEN THE STRIPES.
 PLEASE NOTE THE STATE ALLOWS THE JURISDICTION TO DECIDE
 SINGLE STRIPE OR DOUBLE STRIPE AND THE DIMENSIONS
 BETWEEN THE STRIPES. 2017 FBC-ACCESSIBILITY CODE
 ADVISORY 502.3.3 MARKINGS. THE METHOD AND COLOR OF
 MARKINGS ARE NOT SPECIFIED BY THIS REQUIREMENT BUT MAY
 BE ADDRESSED BY STATE OR LOCAL LAWS AND REGULATIONS.
 THE CITY OF WES PALM BEACH MUNI CODE ARTICLE XV 94-485
 PARKING PROVIDE A DOUBLE LINED DIMENSIONED PARKING
 STALL DETAIL.
  
 7-10) COMPLIED.
  
  
 11) PROVISO/ DEFERRED SUBMITTALS PRODUCT APPROVALS FOR
 COMPONENTS & CLADDING.
  
 12) PROVISO / PORT COCHERE UNDER SEPARATE PERMIT,
 REVIEW AND ASSOCIATED FEES.
  
 13-16) COMPLIED.2ND REVIEW. THE RESPONSE INDICATES LIST
 OF DEFERRED SUBMITTALS IS FOUND ON SHEET A601. THIS
 SHEET HAS NEVER BEEN REVISED. W.P. B. AMENDMENT
 107.3.4.2 DEFERRED SUBMITTALS. COMPONENTS AND CLADDING
 WERE SUBMITTED AS EXHIBITS A-E. PLEASE NOTE SINCE THE
 SUBMITTED PRODUCT APPROVALS ARE GOING THROUGH REVIEW
 ANY PRODUCT APPROVAL BEING SUBMITTED EACH PRODUCT
 APPROVAL WOULD THEN BE CONSIDERED SINCE THE CITY HAS
 PUT IN PLAN REVIEW TIME ON THE DOCUMENTS SUBMITTED AT
 TIME OF APPLICATION.
  
 17) PROVISO; NOT APPLICABLE EXTERIOR WORK ONLY WILL
 RELATE TO PERMIT # 19120241 INT. REMODELING OF THE
 CORRIDORS AND PUBLIC SPACES.
  
 18) PROVISO: NOT APPLICABLE EXTERIOR WORK ONLY WILL
 RELATE TO PERMIT # 19120241 INT. REMODELING OF THE
 CORRIDORS AND PUBLIC SPACES.
  
 JAMES A. WITMER BN, PX, SFP & CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-03-31 Cont ID  
Sent By jwitmer Date 2020-03-31 Time 13:37 Rev Time 0.00
Received By rmcphers Date 2020-03-30 Time 15:47 Sent To  
Notes
2020-03-31 13:37:352017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19110539 (FA?ADE RENOVATIONS & NEW
 COMPONENTS AND CLADDING)
 ADD: 600 NORTHPOINT PARKWAY
 CONT:TBD/ TO BE DETERMINED
 TEL: ?????? CONTACT: ASHLEE CALLAHAN
 E-MAIL:[email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 PERMITS ASSOCIATED WITH THE OVERALL PROJECT.
 19110539 FA?ADE RENOVATIONS & NEW CLADDING
 ???????? PORTE COCHERE
 19120240 INT. REMODEL OF GUEST ROOMS
 19120241 INT. REMODEL OF CORRIDORS & PUBLIC SPACES.
  
 1ST REVIEW
 DATE: 2ND REVIEW
 ACTION: DENIED
  
 1) SEMI-COMPLIED, VALUE FOR THIS PROJECT WAS INCREASED
 TO $825,000.00 DOLLARS IN VALUE IN THE NEW PERMIT
 APPLICATION. THE RESPONSE LETTER FROM THE DESIGN
 PROFESSIONAL STATES THE CORRECT VALUE OF THE PROJECT IS
 $750,000.00 DOLLARS IN VALUE. PLEASE NOTE THERE SEEMS
 TO BE A DISCREPANCY OF OPINION.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) 2ND REVIEW/ SEMI-COMPLIED. THE QUESTION WAS ASKED
 SHEET G100 STATES THE NEW PORTE CACHERE IS TO BE
 PROVIDED BY THE OWNER AND INSTALLED BY OTHERS (ANOTHER
 CONTRACTOR). THE RESPONSE WAS NOT PART OF THIS PERMIT,
 IT IS TO BE SUBMITTED UNDER SEPARATE PERMIT, REVIEW AND
 ASSOCIATED FEES. THERE SEEMS TO BE A DISCONNECT ON THE
 SUBMITTAL SIDE AND THE DESIGNER OF RECORD. IN THE
 RESPONSE TO COMMENTS 2, 3 & 4 THE DESIGNER OF RECORD
 REPEATEDLY STATED THAT THE PORTE COCHERE WOULD BE UNDER
 SEPARATE PERMIT. UNDER THE 2ND REVIEW A NEW PERMIT
 APPLICATION WAS ADDED UNDER THE DESCRIPTION OF WORK
 ADDITIONAL WORDING WAS ADDED ( + PORTE COCHERE). THE
 VALUE OF THE PERMIT WAS INCREASE TO THE DOLLAR AMOUNT
 OF $825,000.00 IN VALUE. DISCREPANCY IN WHAT IS TO BE
 COVERED UNDER THE SCOPE OF THIS PERMIT. FOR THIS REVIEW
 I?M GOING TO TAKE THE ARCHITECT AS THE DESIGNER OF
 RECORD AS MAKING ALL THE CALLS ON THIS PROJECT, AND ALL
 INFORMATION SHOULD BE REVIEWED BY THE DESIGNER OF
 RECORD FOR ACCURACY AS IT PERTAINS TO THE PROJECT.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) SEMI-COMPLIED. THE DESIGNER OF RECORD HAS STATED
 THAT THE PORTE COCHERE WILL BE UNDER SEPARATE PERMIT,
 REVIEWS AND ASSOCIATED FEES. TO DATE NO PERMIT HAS BEEN
 APPLIED FOR, DISCREPANCY SEE COMMENT # 2.
  
 4) SEMI-COMPLIED. THE DESIGNER OF RECORD HAS STATED
 THAT THE PORTE COCHERE WILL BE UNDER SEPARATE PERMIT,
 REVIEWS AND ASSOCIATED FEES. TO DATE NO PERMIT HAS BEEN
 APPLIED FOR, DISCREPANCY SEE COMMENT # 2.
  
 5) 2ND REVIEW. NOT ADDRESSED. THE RESPONSE QUOTES
 REGULATIONS UNDER THE ZONING DIVISION, NOT REQUIREMENTS
 BY THE 2017 FBC-B. THE PORTE COCHERE TO BE CONSIDERED
 PART OF THE 3 STORY BUILDING IT WILL REQUIRE FIRE
 SPRINKLERS FOR A TYPE 5A BUILDING, OTHERWISE YOU ARE
 LOOKING AT 2 SEPARATE BUILDINGS ON THE SAME LOT. SEE
 503.1.2 BUILDINGS ON THE SAME LOT WITH ASSUMED PROPERTY
 LINE. ALSO REVIEW BUILDING HEIGHT AND AREA LIMITATIONS
 SECTIONS 504 AND 506 FOR BUILDINGS TO COMPLY WITH THE
 PROVISIONS OF THIS CODE APPLICABLE TO THE AGGREGATE
 BUILDING FOR AREA AND HEIGHT.
  
 6) 2ND REQUEST. SHEET G100 STATES THAT 5 OF THE 5
 ACCESSIBLE PARKING SPACES ARE TO BE REGRADED AND
 RESTRIPED. THE REVISION STATES NOTE 3 THAT ALL WORK
 WILL BE IN THE ACCORDANCE WITH THE 2017
 FBC-ACCESSIBILITY CODE.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1. W.P.B.
 ADMINISTRATIVE CODE/2017 DRAWINGS & SPECIFICATIONS
 SHALL CONTAIN INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC TO THE
 TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR IN
 PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED AS
 A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
 PLEASE NOTE THE STATE ALLOWS THE JURISDICTION TO DECIDE
 SINGLE STRIPE OR DOUBLE STRIPE AND THE DIMENSIONS
 BETWEEN THE STRIPES. 2017 FBC-ACCESSIBILITY CODE
 ADVISORY 502.3.3 MARKINGS. THE METHOD AND COLOR OF
 MARKINGS ARE NOT SPECIFIED BY THIS REQUIREMENT BUT MAY
 BE ADDRESSED BY STATE OR LOCAL LAWS AND REGULATIONS.
 THE CITY OF WES PALM BEACH MUNI CODE ARTICLE XV 94-485
 PARKING PROVIDE A DOUBLE LINED DIMENSIONED PARKING
 STALL DETAIL.
  
 7) 2ND REQUEST. DEALS WITH SHEET G100ANDNOTE NUMBER 9TO
 PROVIDE NEW CURB WITH FLUSH TRANSITION AND 5 FOOT WIDE
 SIDEWALK TO THE NEW ACCESSIBLE PARKING SPACE. WITH
 REGARDS TO THE OTHER EXISTING ACCESSIBLE PARKING SPACES
 AND ACCESS AISLES TO THE EXISTING SIDEWALKS? ARE THE
 OTHER EXISTING ACCESSIBLE PARKING SPACES AND ACCESS
 AISLES WITH DROPPED CURBS WITH CURB RAMPS IN COMPLIANCE
 WITH THE 2017 FBC-ACCESSIBILITY CODE406 CURB RAMPS? THE
 RESPONSE INDICATES THAT COMPLIANCE WITH THE 2017
 FBC-ACCESSIBILITY CODE WILL BE IN ACCORDANCE WITH THE
 2017 FBC-ACCESSIBILITY CODE.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1. W.P.B.
 ADMINISTRATIVE CODE/2017 DRAWINGS & SPECIFICATIONS
 SHALL CONTAIN INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC TO THE
 TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR IN
 PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED AS
 A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 8) 2ND REQUEST. SHEET G100 INDICATES THE RE-USE OF THE
 EXISTING POOL GATE. I ASKED TO SHOW COMPLIANCE WITH
 SECTION 454.1.3.1.9 OF THE 2017 FBC-B REQUIREMENTS FOR
 THE GATE AND LATCHING REQUIRMENTS. SUBMITTED WAS
 EXHIBIT G. STANDARDS THE GATE AND LATCH HAS TO MEET.
 THERE WERE NO DOCUMENTS FOR THE GATE. 2017 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION 107.2.1. W.P.B. ADMINISTRATIVE
 CODE/2017 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 9 &10) COMPLIED.
  
 11) 2ND REVIEW. COMPONENTS AND CLADDING WERE SUBMITTED
 AS EXHIBITS A-E. PLEASE NOTE SINCE THE SUBMITTED
 PRODUCT APPROVALS ARE GOING THROUGH REVIEW ANY PRODUCT
 APPROVAL BEING SUBMITTED EACH PRODUCT APPROVAL WOULD
 THEN BE CONSIDERED SINCE THE CITY HAS PUT IN PLAN
 REVIEW TIME ON THE DOCUMENTS SUBMITTED AT TIME OF
 APPLICATION.
  
  
 11) EXHIBIT A: TPO SINGLE PLY ROOF SYSTEM, ROOF NOA
 15-0729.18 PAGES 16 & 17. FASTENER # 2.
 LIMITATION # 7. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 11) EXHIBIT B: DRYVIT SYSTEMS OVER PLYWOOD, NOA
 17-0807.19 +/- 100 PSF. GOOD.
  
 11) EXHIBIT C: STOREFRONT. W.W. SCHAEFER ENG. KANEER
 ENG. EVALUATION 1-D, QUALITY ASSURANCE: ARCHITECTURAL
 TESTING INC. GOOD.
  
 11) EXHIBIT D: ROOF TILE NOA 16-0314.06 TABLE 4
 ATTACHMENT METHOD AND UPLIFT NOT IDENTIFIED/ CIRCLED.
  
 11E) NICHIHA USA FIBER CEMENT WALL PANELS NOA:
 16-0404.18 PRESSURES +45/ -55. GOOD.
  
 12A) 2ND REQUEST. RESPONSE INDICATES CODE COMPLIANCE TO
 BE FOUND ON SHEET S002 UNDER SECTION E, FASTENERS.
 COMPLIANCE FOR WELDED AND BOLTED CONNECTIONS WAS NOT
 FOUND.
  
 WELDED OR BOLTED CONNECTIONS
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE
 AMERICAN WELDING SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
 IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS
 FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING
 INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU.
  
 12B1) COMPLIED FIRE RESISTANCE OF EXISTING & NEW
 ELEMENTS ON THE 3 STORY BUILDING.
  
 1B2) 2ND REQUEST. THE RESPONSE INDICATES NOTES WERE
 ADDED ON SHEET A-103 FOR THE RATING OF THE STEEL PORTE
 COCHERE WITH SHERWIN WILLIAMS FIRETEX INTUMESCENT
 PAINT. SHEET A-103 HAS NOT BEEN REVISED TO A VERSION 2.
 PLEASE PROVIDE THE INFORMATION SHEET FOR SHERWIN
 WILLIAMS FIRETEX INTUMESCENT PAINT.
 13) 2ND REVIEW. THE RESPONSE INDICATES LIST OF DEFERRED
 SUBMITTALS IS FOUND ON SHEET A601. THIS SHEET HAS NEVER
 BEEN REVISED. W.P. B. AMENDMENT 107.3.4.2 DEFERRED
 SUBMITTALS. COMPONENTS AND CLADDING WERE SUBMITTED AS
 EXHIBITS A-E. PLEASE NOTE SINCE THE SUBMITTED PRODUCT
 APPROVALS ARE GOING THROUGH REVIEW ANY PRODUCT APPROVAL
 BEING SUBMITTED EACH PRODUCT APPROVAL WOULD THEN BE
 CONSIDERED SINCE THE CITY HAS PUT IN PLAN REVIEW TIME
 ON THE DOCUMENTS SUBMITTED AT TIME OF APPLICATION.
  
 14-16) COMPLIED.
  
 17) NOT APPLICABLE EXTERIOR WORK ONLY WILL RELATE TO
 PERMIT # 19120241 INT. REMODELING OF THE CORRIDORS AND
 PUBLIC SPACES.
  
 18) NOT APPLICABLE EXTERIOR WORK ONLY WILL RELATE TO
 PERMIT # 19120241 INT. REMODELING OF THE CORRIDORS AND
 PUBLIC SPACES.
  
 19) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP & CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-01-27 Cont ID  
Sent By jwitmer Date 2020-01-27 Time 14:14 Rev Time 0.00
Received By jwitmer Date 2020-01-27 Time 06:33 Sent To  
Notes
2020-01-27 14:14:27 
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19110539
 ADD: 600 NORTHPOINT PARKWAY
 CONT: TBD/ TO BE DETERMINED
 TEL: ????????????????????
 E-MAIL: [email protected] CONTACT: ASHLEE
 CALLAHAN
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JAN. 27TH/ 2020
 ACTION: DENIED
  
 1) ON THE PERMIT APPLICATION THERE ARE 2 VALUES FOR THE
 PROJECT, $750,000 AND $75,000 DOLLARS OF VALUE. THE
 APPLICATION UNDER THE HEADING WORK DESCRIPTION STATES:
 FA?ADE RENOVATION/ IMPROVEMENTS WITH NEW CLADDING AND
 ARCHITECTURAL FEATURES IN LIMITED SELECT AREAS + PORTE
 COCHERE REPLACEMENT. PLEASE EXPLAIN WHY THE COST BREAK
 OUT?
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) SHEET G100 THE EXISTING SITE DIAGRAM STATES THE NEW
 PORTE COCHERE PROVIDED BY THE OWNER, INSTALLED BY
 OTHERS. IF THE PORTE COCHERE IS BEING PROVIDED BY THE
 OWNER, DOES THE COST OF THE PORTE COCHERE (MATERIALS,
 LABOR, ENGINEERING, OVERHEAD & PROFIT FOR THE
 CONTRACTOR FIGURED INTO ONE OF THE DOLLAR AMOUNTS
 LISTED ABOVE? IT WOULD APPEAR THAT A 2ND PERMIT WILL
 NEED TO BE APPLIED FOR AS WELL AS CONTRACTOR FOR THIS
 PORTION OF THE JOB?
 108.3* BUILDING PERMIT VALUATION. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE UNDER
 ESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL,
 PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD
 AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION
 REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 3) THE SHEET G100 STATES THE NEW PORTE COCHERE PROVIDED
 BY THE OWNER, INSTALLED BY OTHERS. IS THE ARCHITECT OF
 RECORD TO BE OVER BOTH OF THE STRUCTURAL ENGINEERS? OR
 IS THE STRUCTURAL ENGINEER FOR THE BUILDING THE
 STRUCTURAL ENGINEER OF RECORD AND THE PORT COCHERE
 ENGINEER A DELEGATE ENGINEER TO THE STRUCTURAL
 ENGINEER? FLORIDA ADMINISTRATIVE CODE 61G15-31.001.
  
 4) THE ISSUE WITH 2 GENERAL CONTRACTORS ON THE SAME
 SITE AND ONE SET OF PLANS. PLEASE BREAK OUT THE PLAN
 INFORMATION FOR THE PORTE COCHERE INTO A SEPARATE
 PERMIT AND PLANS. THERE NEEDS TO BE A DEFINITE
 DISTINCTION AS WHAT WORK BELONGS TO WHICH CONTRACTOR.
 FOR EXAMPLE ELECTRICAL, ROOFING AND FIRE SPRINKLERS.
 107.2.1.2. ADDITIONAL INFORMATION REQUIRED.
  
 5) THE PORTE COCHERE TO BE CONSIDERED PART OF THE 3
 STORY BUILDING WOULD REQUIRE SPRINKLERS, FOR A BUILDING
 TYPE 5A, OTHERWISE YOU ARE LOOKING AT 2 SEPARATE
 BUILDINGS ON THE SAME LOT AND AN ASSUMED PROPERTY LINE.
 YOU NOW HAVE 2 SEPARATE BUILDINGS ON THE SAME LOT.
 503.1.2 BUILDINGS ON SAME LOT. TWO OR MORE BUILDINGS ON
 THE SAME LOT SHALL BE REGULATED AS SEPARATE BUILDINGS
 OR SHALL BE CONSIDERED AS PORTIONS OF ONE BUILDING
 WHERE THE BUILDING HEIGHT, NUMBER OF STORIES OF EACH
 BUILDING AND THE AGGREGATE BUILDING AREA OF THE
 BUILDINGS ARE WITHIN THE LIMITATIONS SPECIFIED IN
 SECTIONS 504 AND 506. THE PROVISIONS OF THIS CODE
 APPLICABLE TO THE AGGREGATE BUILDING SHALL BE
 APPLICABLE TO EACH BUILDING.
  
 6) SHEET G100 THE EXISTING SITE DIAGRAM INDICATES AN
 EXISTING PARKING OF 215 SPACES, OF THESE 7 PARKING
 SPACES ARE SET UP TO BE ACCESSIBLE PARKING SPACES. NOTE
 5 STATES THE ACCESSIBLE PARKING SPACES ARE TO BE
 RE-GRADED AND RE-STRIPED. THE NOTE STATES THE RE-STRIPE
 OF THE PARKING SPACES TO MINIMUM DIMENSIONS SHOWN PER
 THE 2012 FLORIDA ACCESSIBILITY CODE REQUIREMENTS.
 PLEASE REFER TO THE 2017 FBC-ACCESSIBILITY CODE AND
 WEST PALM BEACH CITY ACCESSIBLE PARKING STANDARD. AN
 ACCESSIBLE PARKING SPACE AND ACCESS AISLE, PLEASE SEE
 THE 2017 FBC-ACCESSIBILITY CODE 502.3.3 MARKING. ACCESS
 AISLES SHALL BE MARKED SO AS TO DISCOURAGE PARKING IN
 THEM. THE ACCESS AISLE MUST BE STRIPED DIAGONALLY TO
 DESIGNATE IT AS A NO-PARKING ZONE.
 ADVISORY 502.3.3 MARKING. THE METHOD AND COLOR OF
 MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT MAY
 BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS.
 BECAUSE THESE REQUIREMENTS PERMIT THE VAN ACCESS AISLE
 TO BE AS WIDE AS A PARKING SPACE, IT IS IMPORTANT THAT
 THE AISLE BE CLEARLY MARKED. FLORIDA LAW,
 S.553.5041(5)(C)1., REQUIRES DIAGONAL STRIPING OF
 ACCESS AISLES. THE CITY OF W. P. B. MUNI CODE ARTICLE
 XV 94-485 PARKING PROVIDES A DOUBLE LINED DIMENSIONED
 PARKING STALL DETAIL.
  
 7) SHEET G100 THE EXISTING SITE DIAGRAM INDICATES WITH
 NOTE NUMBER 9 TO PROVIDE A NEW CURB WITH FLUSH
 TRANSITION AND 5 FOOT WIDE SIDEWALK TO THE NEW
 ACCESSIBLE PARKING SPACE. WITH THE REGRADING OF THE
 OTHER ACCESSIBLE PARKING SPACES WILL THERE POSSIBLY BE
 ADDITIONAL WORK TO MAKE THE TRANSITION FROM THE ACCESS
 AISLE TO THE SIDEWALK? ARE THE OTHER DROPPED AT THE
 ACCESS AISLE AND IN COMPLIANCE WITH 406 CURB RAMPS OF
 THE 2017 ACCESSIBILITY CODE, FBC.
  
 8) SHEET G100 THE EXISTING SITE DIAGRAM ALSO INDICATES
 THE RE-USE OF THE EXISTING GATES TO THE POOL. THERE ARE
 ABBREVIATIONS RFID LATCH ASSEMBLY, AND RFID EXIT
 DEVICE, THIS ABBREVIATION IS NOT LISTED ON THE
 COVERSHEET. 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED. PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-B
 SECTION 454.1.3.1.9. LATCHING REQUIREMENTS.
  
 9) SHEET S001 NOTE 2. WIND LOAD PER ASCE 7 IS LISTED AS
 A B EXPOSURE. IN THE ASCE 7-10 26.7.3 EXPOSURE
 CATEGORIES. THE EXPOSURE B PREVAILS IN THE UPWIND
 DIRECTION FOR A DISTANCE GREATER THAN 2,600 FT. OR 20
 TIMES THE HEIGHT OF THE BUILDING, WHICHEVER IS GREATER.
 YOU CAN SHOOT A VECTOR TO THE SOUTHEAST OF THE SITE
 DOWN THE I-95 CORRIDOR FOR OVER 3,000 FT. BEFORE ANY
 OBJECTS OCCUR. FOR SITES LOCATED IN TRANSITION ZONES
 BETWEEN EXPOSURE CATEGORIES, THE CATEGORY RESULTING IN
 THE LARGEST WIND FORCE SHALL BE USED. ASCE 7-10 SECTION
 26.7.1 WIND DIRECTION AND SECTORS DOES NOT REQUIRE THE
 MORE STRINGENT WIND EXPOSURE FROM ALL SECTORS AS STATED
 ON THE PLAN SHEET.
  
 10) NEITHER THE ARCHITECTURAL SHEETS NOR THE STRUCTURAL
 SHEETS PROVIDE THE PRESSURES FOR COMPONENTS AND
 CLADDING. WE WILL NEED PRESSURES IN VASD FOR FLAT ROOFS
 AS WELL AS FOR SLOPED ROOFS FOR ROOF ZONES 1,2 & 3 AS
 WELL AS WALL ZONES 4 & 5. ASCE 7-10 FIGURE 30.5-1.
  
 11) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS, NICHIHA PANELS
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
  
 12A) SHEET S201 SHOWS NEW STEEL MEMBERS WITH BOLTED AND
 WELDED CONNECTIONS, PLEASE PROVIDE COMPLIANCE WITH:
 WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION. IN ACCORDANCE WITH THE AMERICAN WELDING
 SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING. SPEAK WITH THE CHIEF
 BUILDING INSPECTOR ABOUT 3RD PARTY CERTIFICATION OF
 BOLTED ASSEMBLIES. IF THERE IS ANY QUESTIONS ABOUT THE
 CODE REQUIREMENTS FOR THIS SECTION, PLEASE CONTACT THE
 CHIEF BUILDING INSPECTOR KEN CONRAD AT 561-805-6666.
 THANK YOU.
  
 12B) THE COVERSHEET LIST THE BUILDING TYPE AS
 CONSTRUCTION TYPE 5A. WITH ALL OF THE STEEL COLUMNS,
 BEAMS THE PLANS DOES NOT INDICATE HOW COMPLIANCE WITH
 TABLE 601 OF THE 2017 FBC-BUILDING A 1 HOUR FIRE RATING
 WILL BE ACHIEVED. THE SAME 1 HOUR RATING WILL ALSO NEED
 TO BE PROVIDED ON THE STRUCTURAL MEMBERS OF THE
 PROPOSED PAVILION.
  
 13) PLEASE PROVIDE IN A WRITTEN STATEMENT IF THE
 PRODUCT APPROVALS ARE TO BE SUBMITTED AFTER PERMIT
 ISSUANCE. 107.3.4.2 DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 14) IDENTIFY GLAZING/ MULLIONS. THE SUBMITTED PRODUCT
 APPROVALS THE ELEMENTS LISTED BELOW ARE NOT IDENTIFIED.
 PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED
 OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 15) EFIS SYSTEMS: PLEASE PROVIDE THE PRODUCT APPROVAL
 FOR THE SYSTEM TO BE INSTALLED. PLEASE ALSO PROVIDE THE
 MANUFACTURERS INSTALLATION BROCHURE PROVIDING
 COMPLIANCE WITH 2017 FBC-B SECTIONS;
 1408.2 PERFORMANCE CHARACTERISTICS.
 1408.2 PERFORMANCE CHARACTERISTICS.
 1408.3 STRUCTURAL DESIGN.
 1408.4 WEATHER RESISTANCE.
 1408.4.1 EIFS WITH DRAINAGE.
 408.4.1.1 WATER-RESISTIVE BARRIER.
 1408.5 INSTALLATION.
  
 16) FOR THE NICHIHA PRODUCT APPROVAL REPORT IDENTIFY,
 CIRCLE THE MODEL, NUMBER OR NAME OF THE SYSTEM TO BE
 INSTALLED. UNDER THE INSTALLATION INSTRUCTIONS CIRCLE
 THE TYPE OF SIDING, FASTENER, SPACING, TYPE OF WALL
 FRAMING THE ALLOWABLE DESIGN PRESSURE VASD AND VULT
 PRESSURES FOR VULT. THANK YOU.
  
 17) THERE IS NO LIFE SAFETY PLAN OF THE RE-CONFIGURED
 LOBBY, MISSING THE OCCUPANT LOAD, THE FLOOR PLAN SHOWS
 ONLY ONE MEANS OF EGRESS, COMMON PATH OF TRAVEL IS NOT
 PROVIDED AND THE WIDTH OF THE ENTRY DOORS.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 EMERGENCY LIGHTING AND EXIT SIGNS
  
 18) SHEET A-341 THE MAIN ENTRY SHOWS THE S-BAR AND
 COMMUNAL TABLE BUT NO DETAILS FOR ACCESSIBILITY. THE
 LIFE SAFETY SHEET DOES NOT SHOW COMPLIANCE WITH THE
 2017 FBC-ACCESSIBILITY CODE;
 18A) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
  
 18B) 226.2 DISPERSION. DINING SURFACES AND WORK
 SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 18C) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN
 RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL
 BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR
 SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS.
  
 18D) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK
 SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS,
 STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER
 TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON
 COUNTERS, AND WHERE COVERED BY THE ADA SCOPING
 PROVISIONS, EMPLOYEE WORK STATIONS.
  
 18E)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR
 FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 18E)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 19)A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-03-27 Cont ID  
Sent By jleahy Date 2020-03-27 Time 11:27 Rev Time 0.00
Received By jleahy Date 2020-03-27 Time 11:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-01-13 Cont ID  
Sent By jpearson Date 2020-01-13 Time 13:13 Rev Time 0.00
Received By jpearson Date 2020-01-13 Time 13:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-03-27 Cont ID  
Sent By pleduc Date 2020-03-27 Time   Rev Time 0.00
Received By pleduc Date 2020-03-26 Time 09:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-01-06 Cont ID  
Sent By pleduc Date 2020-01-06 Time   Rev Time 0.00
Received By pleduc Date 2020-01-06 Time 14:11 Sent To  
Notes
2020-01-06 14:38:41THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET G 000 - UNDER THE CODE INFORMATION: FIRE
 PREVENTION, THERE IS AN INDICATION OF FLORIDA BUILDING
 CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 FLORIDA FIRE PREVENTION CODE; 6TH EDITION.
  
 PLEASE ENSURE COMPLIANCE AND CORRECT.
  
  
  
 2) SHEET G 101 - THERE IS AN INDICATION OF A FIRE PIT -
 HOW WILL PROTECTION BE PROVIDED TO PREVENT THE
 POSSIBLITIY OF ACCIDENTAL TOUCHING AND CONTACT WITH THE
 FLAME?
  
 PER NFPA 1
 10.10.8 INCINERATORS AND FIREPLACES.
 10.10.8.1 INCINERATORS, OUTDOOR FIREPLACES, PERMANENT
 BARBECUES,
 AND GRILLS SHALL NOT BE BUILT, INSTALLED, OR MAINTAINED
 WITHOUT PRIOR
 APPROVAL OF THE AHJ.
 10.10.8.2 INCINERATORS, OUTDOOR FIREPLACES, PERMANENT
 BARBECUES,
 AND GRILLS SHALL BE MAINTAINED IN GOOD REPAIR AND IN A
 SAFE
 CONDITION AT ALL TIMES.
 10.10.8.3 OPENINGS IN INCINERATORS, OUTDOOR FIREPLACES,
 PERMANENT
 BARBECUES, AND GRILLS SHALL BE PROVIDED WITH AN
 APPROVED SPARK
 ARRESTER, SCREEN, OR DOOR.
  
 PLEASE PROVIDE DETAILS.
  
  
  
 3) SHEET G 101 - THERE IS AN INDICATION OF A FIRE PIT
 EMERGENCY SHUTOFF. - THE EMERGENCY SHUT OFF SHALL BE
 REMOTE FORM THE FIRE PIT ITSELF.
  
 PLEASE PROVIDE AN ALTERNATE SHUTOFF THAT IS NOT LOCATED
 AT THE ACTUAL FIRE PIT LOCATION.
  
  
  
 4) NO LIFE SAFETY SHEET - THERE ARE INDICATIONS OF WORK
 IN AND AROUND THE REQUIRED MEAND OF EGRESS AND EXITING.
  
 HOW WILL THE REQUIRED EXIT EGRESS AND EXIT DISCHARGES
 BE MAINTAINED THROUGHOUT CONSTRUCTION.
  
 PER NFPA 101 CH. 7, MEANS OF EGRESS
  
 7.5 ARRANGEMENT OF MEANS OF EGRESS.
 7.5.1 GENERAL.
 7.5.1.1 EXITS SHALL BE LOCATED, AND EXIT ACCESS SHALL
 BE ARRANGED, SO
 THAT EXITS ARE READILY ACCESSIBLE AT ALL TIMES.
 7.5.1.1.1* WHERE EXITS ARE NOT IMMEDIATELY ACCESSIBLE
 FROM AN
 OPEN FLOOR AREA, CONTINUOUS PASSAGEWAYS, AISLES, OR
 CORRIDORS
 LEADING DIRECTLY TO EVERY EXIT SHALL BE MAINTAINED AND
 SHALL BE
 ARRANGED TO PROVIDE ACCESS FOR EACH OCCUPANT TO NOT
 LESS THAN TWO
 EXITS BY SEPARATE WAYS OF TRAVEL, UNLESS OTHERWISE
 PROVIDED IN
 7.5.1.1.3 AND 7.5.1.1.4.
  
 7.5.2.2* EXIT ACCESS AND EXIT DOORS SHALL BE DESIGNED
 AND ARRANGED
 TO BE CLEARLY RECOGNIZABLE.
  
  
 PLEASE REVIEW AND PROVIDE A LIFE SAFETY PLAN.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2020-06-10 Cont ID  
Sent By ccole Date 2020-06-10 Time 11:16 Rev Time 0.00
Received By ccole Date 2020-06-10 Time 08:24 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2020-05-28 Cont ID  
Sent By ccole Date 2020-05-28 Time 12:26 Rev Time 0.00
Received By ccole Date 2020-05-28 Time 11:03 Sent To  
Notes
2020-05-28 12:28:583RD REVIEW FBC-2017 FUEL GAS
 PERMIT 19110539
 5/28/20
  
 CODES IN EFFECT:
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENTS FROM THE 2ND REVIEW WERE NOT COMPLETED
 ADDRESSED.
  
 1) SHEET P200- GAS PIPING LAYOUT AND RISER DRAWINGS:
 A) TOTAL LENGTH OF THE RUN, AND THE TYPE OF 1-1/4"
 PIPING TO THE NEW FIRE PIT NOT SHOWN- SECTIONS 402.4.1,
 402.4.2 FBC FG.
  
 2) THE REQUESTED MANUFACTURER'S SPECIFICATIONS FOR THE
 FIRE PIT WERE NOT SUBMITTED- SECTIONS 601.1 AND 636.1
 FBC FG.
  
 3) P200: AS NOTED ABOVE THE TYPE OF UNDERSLAB PIPING
 FROM THE BUILDING TO THE FIRE PIT NEEDS TO BE
 IDENTIFIED AND THE BURIAL DEPTH BELOW GRADE INDICATED-
 SECTION 404.12 AND 404.12.1 FBC FG. IF METALLIC PIPING
 IS TO BE USED IN MUST BE PROTECTED AGAINST CORROSION IN
 ACCORDANCE WITH SECTION 404.11. PLEASE NOTE THAT PE
 PIPE MAY BE USED UNDERSLAB PER SECTION 404.17.3 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-05-14 Cont ID  
Sent By ccole Date 2020-05-14 Time 08:37 Rev Time 0.00
Received By ccole Date 2020-05-13 Time 14:30 Sent To  
Notes
2020-05-14 08:41:502ND REVIEW FBC-2017 FUEL GAS
 PERMIT 19110539
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENT #1 FROM THE 1ST REVIEW LISTED BELOW WAS NOT
 ADDRESSED ON THE RESUBMITTED PLANS, AND THERE WAS NO
 NARRATIVE RESPONSE PROVIDED. PLEASE COMPLY WITH THE
 COMMENTS.
  
 GAS COMMENTS:
 1. 2017 FLORIDA FUEL GAS CODE AND 2017 FBC 2017-107.2.1
 AND NFPA 1. ALL THAT IS SHOWN ON THESE DRAWINGS IS A
 CONNECTION OF A NEW GAS LINE TO AN EXISTING GAS LINE
 FOR AN OUTDOOR FIRE PIT. THERE HAS BEEN NO SUBMITTAL OF
 THE FIRE PIT AS PART OF THE DOCUMENTS. THERE IS NO GAS
 RISER DIAGRAM SHOWING THE LONGEST LENGTH METHOD OF PIPE
 SIZING, ANY EXISTING APPLIANCES AND THE BTUH VALUES,
 VALVING, DIRT LEGS, ETC. PLEASE ALSO TO THE CITY OF
 WEST PALM BEACH GAS PERMIT APPLICATION REQUIREMENTS FOR
 OTHER INFORMATION THAT MAY BE REQUIRED ON THE
 DOCUMENTS.
  
 2) NEW COMMENT- GAS ISOMETRIC DRAWING REQUIREMENTS:
  
 A) PLEASE NOTE WHEN PREPARING THE ISOMETRIC DRAWING
 THAT THE TOTAL LOAD OF THE NEW FIRE PIT SYSTEM MUST BE
 ADDED TO THE TOTAL LOAD OF THE EXISITNG SYSTEM TO
 ENSURE THE EXISTING SYSTEM AND MAIN GAS LINE ARE
 PROPERLY SIZED- SECTION 107.2.1 WPB
  
 B) SHOW THE PIPING RUN FROM THE METER TO THE MOST
 REMOTE OUTLET, INDICATE THE TOTAL LENGTH OF THE RUN,
 AND THE LENGTHS OF EACH BRANCH LINE SUPPLY A GAS
 APPLIANCE- SECTIONS 402.4.1, 402.4.2 FBC FG .INDICATE
 THE TYPES AND SIZES OF ALL PIPING IN THE SYSTEM.
  
 C) SHOW THE TOTAL BTUH LOAD OF THE SYSTEM AND THE BTUH
 LOAD OF EACH INDIVIDUAL APPLIANCE- SECTIONS 401.8 AND
 402.2 FBC FG.
  
 D) INDICATE THE DELIVERY PRESSURE AT THE METER, AND THE
 REDUCED PRESSURES AT ALL MP REGULATORS OR IN-LINE
 APPLIANCE REGULATORS- SECTIONS 402.1, 402.4.3 THRU
 402.6 FBC FG.
  
 E) INDICATE THE PIPE SIZING TABLES USED- TABLES
 402.4(1) THRU 402.4(37) FBC FG.
  
 F) REFER TO SECTIONS 601.1 AND 636.1 FBC FG, AND SUBMIT
 MANUFACTURER'S SPECIFICTIONS FOR THE FIRE PIT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  
  
 .
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-03-27 Cont ID  
Sent By shill Date 2020-03-27 Time 13:55 Rev Time 0.00
Received By shill Date 2020-03-27 Time 13:55 Sent To  
Notes
2020-03-27 13:56:02FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC P = FBC PLUMBING
  
 FAILED
  
 PLEASE NOTE THAT THE RESPONSES TO THE PREVIOUS PLUMBING
 COMMENTS ARE ACCEPTABLE, HOWEVER WE HAVE TO ADD
 COMMENTS FOR THE GAS OUTDOOR FIRE PIT.
  
 GAS COMMENTS:
 1. 2017 FLORIDA FUEL GAS CODE AND 2017 FBC
 2017-107.2.1 AND NFPA 1. ALL THAT IS SHOWN ON THESE
 DRAWINGS IS A CONNECTION OF A NEW GAS LINE TO AN
 EXISTING GAS LINE FOR AN OUTDOOR FIRE PIT. THERE HAS
 BEEN NO SUBMITTAL OF THE FIRE PIT AS PART OF THE
 DOCUMENTS. THERE IS NO GAS RISER DIAGRAM SHOWING THE
 LONGEST LENGTH METHOD OF PIPE SIZING, ANY EXISTING
 APPLIANCES AND THE BTUH VALUES, VALVING, DIRT LEGS,
 ETC. PLEASE ALSO TO THE CITY OF WEST PALM BEACH GAS
 PERMIT APPLICATION REQUIREMENTS FOR OTHER INFORMATION
 THAT MAY BE REQUIRED ON THE DOCUMENTS.
  
  
 REVIEWED REMOTELY BY JAMES BAKER, PE
 PX3997, PE77268
 561-805-6724
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date   Cont ID  
Sent By   Date 2020-06-10 Time   Rev Time 0.00
Received By cpuell Date 2020-06-05 Time 16:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2020-05-28 Time   Rev Time 0.00
Received By lmarchan Date 2020-05-22 Time 13:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2020-05-14 Time   Rev Time 0.00
Received By lmarchan Date 2020-05-07 Time 08:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-03-31 Cont ID  
Sent By rmcphers Date 2020-03-31 Time 13:38 Rev Time 0.00
Received By rmcphers Date 2020-03-24 Time 10:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-01-29 Cont ID  
Sent By lmarchan Date 2020-01-29 Time 09:34 Rev Time 0.00
Received By lmarchan Date 2019-12-30 Time 10:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status P Date 2020-06-10 Cont ID  
Sent By ccole Date 2020-06-10 Time 11:58 Rev Time 0.00
Received By ccole Date 2020-06-10 Time 08:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2020-05-28 Cont ID  
Sent By ccole Date 2020-05-28 Time 12:24 Rev Time 0.00
Received By ccole Date 2020-05-28 Time 11:03 Sent To  
Notes
2020-05-28 12:26:503RD REVIEW FBC-2017 PLUMBING
 PERMIT 19110539
 5/28/20
  
 CODES IN EFFECT:
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 THIS IS THE 3RD REVIEW AND THE 1ST REVIEW COMMENTS
 LISTED BELOW HAVE STILL NOT BEEN ADDRESSED AND AGAIN NO
 NARRATIVE RESPONSE WAS PROVIDED.
 THE ENGINEER OF RECORD SHALL PROVIDE A WRITTEN RESPONSE
 TO THE COMMENTS, AND PROVIDE A SCOPE OF WORK OULTINE
 FOR PLUMBING AND ROOF DRAINAGE UNDER THIS PERMIT. THE
 SCOPE AND LIMITATIONS OF THE WORK SHALL BE CLEARLY
 NOTED ON THE PLAN AND CORRESPONDING DRAWINGS AND
 DETAILS SHALL BE PROVIDED- SECTION 107.2.1 WPB.
  
 1. SHEET P200: ON ROOFS WHERE PONDING COULD OCCUR IF
 THE PRIMARY DRAIN IS CLOGGED A EMERGENCY OVERFLOW ROOF
 DRAIN IS REQUIRED. PER FBC PL 1108.1.
  
 2.P200: PROVIDE SIZING CALCULATION FOR ALL NEW ROOF
 DRAINS . PER FBC PL 1106.2.
  
 5. P200: SHOW STORM PIPING FOR STAIR WELLS. PER WPB
 AMEND TO FBC 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2020-05-14 Cont ID  
Sent By ccole Date 2020-05-14 Time 08:28 Rev Time 0.00
Received By ccole Date 2020-05-13 Time 14:30 Sent To  
Notes
2020-05-14 08:36:572ND REVIEW FBC-2017 PLUMBING
 PERMIT 19110539
 5/14/20
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 THE 1ST REVIEW COMMENTS LISTED BELOW WERE NOT ADDRESSED
 ON THE RESUMBITTED PLANS, AND THERE WAS NO NARRATIVE
 RESPONSE PROVIDED. PLEASE COMPLY WITH THE COMMENTS.
 PLEASE NOTE IF THE ROOF DRAINAGE FOR THE PORTE COCHERE
 IS NOT TO BE INCLUDED IN THE THIS PERMIT SUBMITTAL,
 PROVIDE NOTES ON THE PLAN TO INDICATE THE LIMITATIONS
 OF THE PLUMBING AND ROOF DRAINAGE WORK UNDER THIS
 PERMIT.
  
 1. SHEET P200: ON ROOFS WHERE PONDING COULD OCCUR IF
 THE PRIMARY DRAIN IS CLOGGED A EMERGENCY OVERFLOW ROOF
 DRAIN IS REQUIRED. PER FBC PL 1108.1
  
 2.P200: PROVIDE SIZING CALCULATION FOR ALL NEW ROOF
 DRAINS . PER FBC PL 1106.2
  
 5. P200: SHOW STORM PIPING FOR STAIR WELLS. PER WPB
 AMEND TO FBC 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-03-27 Cont ID  
Sent By jbaker Date 2020-03-27 Time 13:54 Rev Time 0.00
Received By shill Date 2020-03-27 Time 09:36 Sent To  
Notes
2020-03-27 13:55:21REVIEWED REMOTELY BY JAMES BAKER, PE
 PX3997, PE77268
 561-805-6724
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-01-13 Cont ID  
Sent By gjohnson Date 2020-01-13 Time 11:41 Rev Time 0.00
Received By gjohnson Date 2020-01-10 Time 09:13 Sent To  
Notes
2020-01-13 11:42:031ST REVIEW: 19110539
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. ON ROOFS WHERE PONDING COULD OCCUR IF THE PRIMARY
 DRAIN IS CLOGGED A EMERGENCY OVERFLOW ROOF DRAIN IS
 REQUIRED. PER FBC PL 1108.1
  
 2. PROVIDE SIZING CALCULATION FOR ALL NEW ROOF DRAINS .
 PER FBC PL 1106.2
  
 3.SHT. P200 GENERAL NOTE 1(E) PLUMBING CONTRACTOR SHALL
 BE LICENSED BY STATE OF FLORIDA. PER FAC 589
  
 4. SHT. P200 GENERAL NOTE # 14 (A) STORM PIPING NOT
 PERMITTED TO DISCHARGE TO SANITARY SEWER. PER WPB
 ORDINANCE
  
 5. SHT. P200 SHOW STORM PIPING FOR STAIR WELLS. PER WPB
 AMEND TO FBC 107.2.1
  
 END OF COMMENTS
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status N Date 2020-05-13 Cont ID  
Sent By jwitmer Date 2020-05-13 Time 08:42 Rev Time 0.00
Received By jwitmer Date 2020-05-11 Time 06:30 Sent To  
Notes
2020-05-13 08:41:40THE DESIGNER OF RECORD HAS REQUESTED DEFERRED SUBMITTAL
 FOR ROOFING PRODUCT APPROVALS. THE ROOFING CONTRACTOR
 TO PROVIDE THE ROOFING PRODUCT APPROVAL. BEFORE THE
 ROOFING PRODUCT APPROVAL CAN BE SUBMITTED TO
 THEBUILDING DEPARTMENT, THE DESIGNER OF RECORD IS TO
 REVIEW AND APPLY THEIR SHOP DRAWING STAMP OF APPROVAL.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2020-03-31 Cont ID  
Sent By jwitmer Date 2020-03-31 Time 13:44 Rev Time 0.00
Received By rmcphers Date 2020-03-31 Time 13:39 Sent To  
Notes
2020-03-31 13:40:20SEE BUILDING REVIEW BY JWITMER

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2020-01-27 Cont ID  
Sent By jwitmer Date 2020-01-27 Time 14:15 Rev Time 0.00
Received By jwitmer Date 2020-01-27 Time 06:33 Sent To  
Notes
2020-01-27 14:15:51PLEASE REFER BACK TO THE BUILDING REVIEW AT THIS TIME,
 NO WIND DESIGN PRESSURES WERE GIVEN NOR PRODUCT
 APPROVALS.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2020-06-10 Cont ID  
Sent By dbattles Date 2020-06-10 Time 15:51 Rev Time 0.00
Received By dbattles Date 2020-06-10 Time 15:51 Sent To  
Notes
2020-06-10 15:52:27PAGES SELF CERTIFIED AND THE ENGINEER IS NOTIFIED FOR
 FUTURE DIGITAL SIGNATURES 3RD PERTY VERIFICATION IS
 REQUIRED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2020-06-10 Cont ID  
Sent By ccole Date 2020-06-10 Time 12:03 Rev Time 0.00
Received By ccole Date 2020-06-10 Time 11:59 Sent To  
Notes
2020-06-10 12:07:09NEW SHEETS P100 AND P200 ARE NOT ELECTRONICALLY SIGNED
 AND SEALED BY THE ENGINEER- FL. STATUTE 471.025 &
 SECTION 61G15-23.005 FAC.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-05-27 Cont ID  
Sent By dbattles Date 2020-05-27 Time 12:43 Rev Time 0.00
Received By dbattles Date 2020-05-27 Time 12:43 Sent To  
Notes
2020-05-27 12:44:07ANY ADDITIONAL DRAWINGS SUBMITTED TO BE DIGITALLY
 SIGNED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-05-13 Cont ID  
Sent By dbattles Date 2020-05-13 Time 10:33 Rev Time 0.00
Received By dbattles Date 2020-05-13 Time 10:28 Sent To  
Notes
2020-05-13 10:34:45017_A321 MID-ENTRY DEMO-NEW CONSTRUCTION DIAGRAMS -
 PLEASE RELOAD WITH DIGITAL SIGNATURE.
  
 ANY NEW SHEETS FOR COMMENT RESPONSE NEED TO BE
 DIGITALLY SIGNED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-04-07 Cont ID  
Sent By shill Date 2020-04-07 Time 16:19 Rev Time 0.00
Received By shill Date 2020-04-07 Time 16:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-01-13 Cont ID  
Sent By jpearson Date 2020-01-13 Time 13:06 Rev Time 0.00
Received By jpearson Date 2020-01-13 Time 13:06 Sent To  
Notes
2020-01-13 13:06:51STRUCTURAL, ELECTRICAL AND PLUMBING SHEETS: PER THE WPB
 AMENDMENTS TO THE FBC, EACH SHEET OF PLAN IS REQUIRED
 TO BE SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR
 THE DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION.
 SELF-CERTIFICATION IS NOT ACCEPTABLE FOR ENGINEERS.
 PROVIDE CORRECTION. WPB FBC 107.1; FS 471/481

Review Stop Z ZONING
Rev No 2 Status P Date 2020-04-07 Cont ID  
Sent By rfalcone Date 2020-04-07 Time 10:10 Rev Time 0.00
Received By rfalcone Date 2020-04-07 Time 10:10 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-01-29 Cont ID  
Sent By Rfalcone Date 2020-01-29 Time 09:19 Rev Time 0.00
Received By rfalcone Date 2020-01-29 Time 09:19 Sent To I
Notes
2020-01-29 09:20:221/29/2020 FAILED.
  
 PLEASE PROVIDE A SURVEY OF THE SUBJECT SITE WITH THE
 PROPOSED PORTE COCHERE ADDITION AND ITS SETBACKS FROM
 THE PROPERTY LINES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 RACHEL FALCONE, ASSOCIATE PLANNER
 DEVELOPMENT SERVICES DEPARTMENT
 E-MAIL: [email protected]
 TEL: (561) 822-1442
  