Plan Review Details - Permit 19110489
Plan Review Stops For Permit 19110489
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-11-18 Cont ID  
Sent By jgomez Date 2019-11-18 Time 09:59 Rev Time 0.00
Received By jgomez Date 2019-11-18 Time 09:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-11-14 Cont ID  
Sent By jgomez Date 2019-11-14 Time 07:53 Rev Time 0.00
Received By jgomez Date 2019-11-13 Time 18:58 Sent To  
Notes
2019-11-14 09:02:59RESIDENTIAL (R2) BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 1)FLOORING SOUND INSULATION:
 A) PROVIDE 2 COPIES OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 6TH EDITION
 (2017).
  
 B)SOUND TRANSMISSION CLASS (STC) TEST PROVIDED IS FOR
 AN 8 INCH CONCRETE SLAB WITH A GYPSUM BOARD SUSPENDED
 ACOUSTICAL CEILING ASSEMBLY. THIS IS WHY THE THE SOUND
 TRANSMISSION RESULTS ARE SO HIGH. TYPICALLY, SUSPENDED
 ACOUSTICAL CEILING ASSEMBLIES ARE NOT FOUND IN
 BUILDINGS IN THIS AREA. PROVIDE PROOF THAT EXISTING
 BUILDING HAS AN ACOUSTICAL CEILING ASSEMBLY OR PROVIDE
 COPY OF TEST WITHOUT THE ACOUSTICAL CEILING ASSEMBLY.
 ALSO, PROVIDE TWO COPIES. ONLY ONE WAS SUBMITTED.
 NOTE: TEST SAMPLE TO MATCH BUILDING CONSTRUCTION.
 SEC. 1207.2 OF FBC 6TH EDITION (2017).
  
 C) IMPACT INSULATION CLASS (IIC) TEST PROVIDED IS FOR
 AN 8 INCH CONCRETE SLAB WITH A GYPSUM BOARD SUSPENDED
 ACOUSTICAL CEILING ASSEMBLY. THIS IS WHY THE THE SOUND
 TRANSMISSION RESULTS ARE SO HIGH. TYPICALLY, SUSPENDED
 ACOUSTICAL CEILING ASSEMBLIES ARE NOT FOUND IN
 BUILDINGS IN THIS AREA. PROVIDE PROOF THAT EXISTING
 BUILDING HAS AN ACOUSTICAL CEILING ASSEMBLY OR PROVIDE
 COPY OF TEST WITHOUT THE ACOUSTICAL CEILING ASSEMBLY.
 ALSO, PROVIDE TWO COPIES. ONLY ONE WAS SUBMITTED.
 NOTE: TEST SAMPLE TO MATCH BUILDING CONSTRUCTION.
 SEC. 1207.3 OF FBC 6TH EDITION (2017).
  
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-11-18 Cont ID  
Sent By jgomez Date 2019-11-18 Time 10:07 Rev Time 0.00
Received By jgomez Date 2019-11-18 Time 09:04 Sent To  
Notes
2019-11-18 09:04:57CONTRACTOR E-MAILED NEW FLOORING UNDERLAYMENT.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-11-14 Cont ID  
Sent By jgomez Date 2019-11-14 Time 09:03 Rev Time 0.00
Received By jgomez Date 2019-11-12 Time 16:39 Sent To I
Notes
2019-11-13 16:39:55SUBMITTAL ROUTED TO JGOMEZ


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved