| 2019-11-16 06:42:05 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19110420 |
| | ADD: 251 BANYAN BLVD. |
| | CONT: TYCON MANAGEMENT LLC |
| | TEL: 561-860-1663 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SAT. NOV. 16/ 2019 |
| | ACTION: DENIED |
| | |
| | 1) ASBESTOS COMMERCIAL. PLEASE PROVIDE A SIGNED |
| | ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD, |
| | STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF |
| | ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF |
| | HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT |
| | NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL |
| | INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE |
| | FOUND ON THEIR WEBSITE: |
| | |
| | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE |
| | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- |
| | RENOVATION.HTML |
| | |
| | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO |
| | [email protected]. THE INFORMATION SHOULD BE IN PDF |
| | FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE |
| | THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE. |
| | |
| | 2) SHEET A2.1.1.: |
| | |
| | 2A) RESTROOM DETAILS 8 & 9 BOTH SHOW THE WATER CLOSET |
| | GRAB RAILS BEING MEASURED 36 INCHES FROM THE CENTERLINE |
| | OF THE GRAB BAR ABOVE THE FLOOR LEVEL. PLEASE NOTE IN |
| | THE 2017 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION |
| | OF GRAB BARS. GRAB BARS SHALL BE INSTALLED IN A |
| | HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF |
| | THE GRIPPING SURFACE, NOT CENTERLINE. |
| | A 36 INCH MEASUREMENT MEASURED FROM THE CENTERLINE ON A |
| | 1 ? GRAB BAR WOULD PUT THE GRAB BAR 36 ? INCHES ABOVE |
| | THE FINISH FLOOR BECAUSE OF THE MEASURING FROM CENTER |
| | LINE AND NOT THE TOP OF THE GRIPPING SURFACE. |
| | |
| | 2B) DETAIL 9 OF THE SAME PAGE, IT APPEARS EITHER THE |
| | DETAIL WAS PARTIALLY DELETED OR THE PRINTER RAN OUT OF |
| | INK IN THE SAME AREA ON BOTH SETS OF PLANS? 107.2.1.2 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 2C) DISCREPANCY IN PLANS. PLEASE REVIEW DETAILS B |
| | RESTROOM 113 AND DETAIL 8. IN DETAIL B THE WATER CLOSET |
| | IS DIMENSIONED (BACKWALL) 1 FOOT 6 INCHES AWAY FROM THE |
| | NEAREST CORNER WHEREAS IN THE DETAIL 8 THE WATER CLOSET |
| | IS DIMENSIONED AT 1 FOOT 5 INCHES, A DISCREPANCY OF 1 |
| | INCH. THE CODE DOES ALLOW THE ACCESSIBLE WATER CLOSET |
| | TO BE BETWEEN 16-18 INCHES AWAY FROM THE CORNER WALL |
| | (2017 ACCESSIBILITY CODE SECTION 604.2 LOCATION). |
| | PLEASE CORRECT THE DISCREPANCY IN THE PLANS. 107.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, DISCREPANCY. |
| | |
| | 2D) DETAIL A BREAK ROOM CABINETRY. THE FLOOR PLAN DOES |
| | NOT SHOW WHICH APPROACH WILL BE USED TO GAIN ENTRY TO |
| | THE BREAK ROOM SINK. THE LOCATION OF THE REQUIRED |
| | ACCESSIBLE SINK GIVEN ON THIS PLAN APPEARS TO |
| | CENTERLINE 18 INCHES FROM THE CORNER WALL. SHEET |
| | A4.1.1. DETAIL 9 A SECTION OF THE SAME CABINETRY SHOWS |
| | A TOE KICK AND BOTTOM IN THE CABINETRY AND THE PIPES |
| | NOT COVERED WITH INSULATION. IT APPEARS AS DRAWN |
| | NEITHER A SIDE APPROACH NOR FRONT APPROACH WILL WORK. |
| | PLEASE PROVIDE COMPLIANCE WITH THE 2017 |
| | FBC-ACCESSIBILITY CODE SECTIONS: |
| | |
| | 602.2 CLEAR FLOOR SPACE. UNITS SHALL HAVE A CLEAR FLOOR |
| | OR GROUND SPACE COMPLYING WITH 305 POSITIONED FOR A |
| | FORWARD APPROACH AND CENTERED ON THE UNIT. KNEE AND TOE |
| | CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED. |
| | |
| | 2017 FBC-ACCESSIBILITY CODE 606.5 EXPOSED PIPES AND |
| | SURFACES. WATER SUPPLY AND DRAIN PIPES UNDER LAVATORIES |
| | AND SINKS SHALL BE INSULATED OR OTHERWISE CONFIGURED TO |
| | PROTECT AGAINST CONTACT. THERE SHALL BE NO SHARP OR |
| | ABRASIVE SURFACES UNDER LAVATORIES AND SINKS. |
| | |
| | MUST ALSO COMPLY WITH 306.2 TOE CLEARANCE AND 306.3 |
| | KNEE CLEARANCE FOR FORWARD APPROACH. 2017 |
| | FBC-ACCESSIBILITY CODE. |
| | |
| | IN THE PRESENT LOCATION A SIDE APPROACH WILL NOT WORK, |
| | THE CENTERLINE OF THE SINK WOULD BE REQUIRED TO BE 2 |
| | FEET FROM THE CORNER WALL FOR THE SIDE APPROACH TO |
| | WORK. |
| | |
| | |
| | 3) SHEET A1.1.1.WINDOW TYPES A & B BOTH QUALIFY AS |
| | GLAZING IN HAZARDOUS LOCATIONS SEE 2406.4.3 OF THE 2017 |
| | FBC-B. PLEASE IDENTIFY WINDOWS AS SUCH AND THE TYPE OF |
| | TREATMENT TO BE USED ON THESE WINDOWS. |
| | |
| | 4) SHEET A1.1.1. PLEASE PROVIDE WHERE THE PROPERTY LINE |
| | IS LOCATED SINCE THE ENTRY DOORS ARE A OUTSWING DOOR |
| | AND MAY SWING OUT OVER THE PROPERTY LINE? SHOW |
| | COMPLIANCE WITH THE 2017 FBC-B SECTION: |
| | |
| | 3202.2 ENCROACHMENTS ABOVE GRADE AND BELOW 8 FEET IN |
| | HEIGHT. ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY |
| | ABOVE GRADE AND BELOW 8 FEET (2438 MM) IN HEIGHT SHALL |
| | BE PROHIBITED EXCEPT AS PROVIDED FOR IN SECTIONS |
| | 3202.2.1 THROUGH 3202.2.3. DOORS AND WINDOWS SHALL NOT |
| | OPEN OR PROJECT INTO THE PUBLIC RIGHT-OF-WAY. |
| | |
| | 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |