Plan Review Details - Permit 19110409
Plan Review Stops For Permit 19110409
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-11-19 Cont ID  
Sent By jbrooks Date 2019-11-19 Time 09:07 Rev Time 0.00
Received By jbrooks Date 2019-11-19 Time 09:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-11-12 Cont ID  
Sent By jbrooks Date 2019-11-12 Time 09:59 Rev Time 0.00
Received By jbrooks Date 2019-11-12 Time 09:58 Sent To  
Notes
2019-11-12 09:59:08JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561)
 805-6724
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC B 107.2.1. PLEASE PROVIDE THE FOLLOWING TEST
 REPORTS FOR QUIETCORK SOUND PROOF UNDERLAYMENT.
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE.
 1. FBC B 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
 2. FBC B 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
 3. FBC B 603.1, ALLOWABLE MATERIALS IN NON-COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-11-19 Cont ID  
Sent By jbrooks Date 2019-11-19 Time 09:07 Rev Time 0.00
Received By jbrooks Date 2019-11-14 Time 15:53 Sent To  
Notes
2019-11-18 15:54:09TO JB DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-11-12 Cont ID  
Sent By jbrooks Date 2019-11-12 Time 09:59 Rev Time 0.00
Received By jbrooks Date 2019-11-07 Time 10:29 Sent To B
Notes
***NONE***