Plan Review Details - Permit 19110402
Plan Review Stops For Permit 19110402
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-06-19 Cont ID  
Sent By rmcdouga Date 2020-06-19 Time 10:43 Rev Time 0.00
Received By rmcdouga Date 2020-06-19 Time 10:43 Sent To  
Notes
2020-06-19 10:46:12SEE SIGNATURE COMMENT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-05-15 Cont ID  
Sent By rmcdouga Date 2020-05-15 Time 14:33 Rev Time 0.00
Received By rmcdouga Date 2020-05-15 Time 14:19 Sent To  
Notes
2020-05-15 14:43:17PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD AND ANCHORING PLANS ARE REQUIRED
 TO HAVE THE ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE.
 ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN
 ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025,
 F.S., AND RULE 61G15-23.001, F.A.C. MUST BE PHYSICALLY
 SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE
 USED.
  
 2) THE GENERATOR PAD ENGINEERING THAT WAS SUBMITTED IS
 NOT FOR THE GENERAC 16KW GENERATOR SPECS. THAT WERE
 SUBMITTED. THE GENERATOR IN THE SPECIFICATIONS IS 409
 LBS AND DOES NOT MEET THE WEIGHT REQUIRED BY THE PAD
 ENGINEERING. THE SIZE AND WEIGHT OF THE GENERATOR HAS
 TO MATCH THE REQUIREMENTS OF THE PAD ENGINEERING. FBC
 107.2.1
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-01-02 Cont ID  
Sent By rmcdouga Date 2020-01-02 Time 11:01 Rev Time 0.00
Received By rmcdouga Date 2020-01-02 Time 11:01 Sent To  
Notes
2020-01-02 11:04:37PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING - COMMENT FROM FIRST REVIEW WAS NOT
 ADDRESSED.
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD AND ANCHORING PLANS FROM AN
 ENGINEER ARE REQUIRED TO HAVE THE ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATIRE. ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS WHICH MUST
 BE SIGNED, DATED AND SEALED IN ACCORDANCE WITH THE
 PROVISIONS OF SECTION 471.025, F.S., AND RULE
 61G15-23.001, F.A.C. MUST BE PHYSICALLY SIGNED, DATED
 AND SEALED AS PROVIDED HEREIN BY THE PROFESSIONAL
 ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE
 USED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-11-14 Cont ID  
Sent By rmcdouga Date 2019-11-14 Time 18:23 Rev Time 0.00
Received By rmcdouga Date 2019-11-14 Time 18:23 Sent To  
Notes
2019-11-14 18:27:53PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD AND ANCHORING PLANS ARE REQUIRED
 TO HAVE THE ENGINEER'S ORIGINAL HANDWRITTEN SIGNATIRE.
 ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN
 ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025,
 F.S., AND RULE 61G15-23.001, F.A.C. MUST BE PHYSICALLY
 SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE
 USED.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-06-22 Cont ID  
Sent By cthroop Date 2020-06-22 Time 11:25 Rev Time 0.00
Received By cthroop Date 2020-06-22 Time 11:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-11-15 Cont ID  
Sent By jleahy Date 2019-11-15 Time 16:55 Rev Time 0.00
Received By jleahy Date 2019-11-15 Time 16:55 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2020-07-23 Cont ID  
Sent By medwards Date 2020-06-22 Time 12:16 Rev Time 0.00
Received By medwards Date 2020-07-23 Time 14:41 Sent To  
Notes
2020-06-22 12:16:414TH REVIEW FBC-2017 MECHANICAL
 PERMIT-19110402
  
 CODES IN EFFECT:
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE GAS PRESSURE DELIVERED TO THE
 METER. IF THIS IS A 2PSI SYSTEM PLEASE SHOW THE
 REGULATOR LOCATION THAT STEPS THE PRESSURE DOWN.
 PROVIDE THE SPECS ON ALL REGULATORS USED IN THIS
 INSTALLATION. FBC FS 107.2.1
  
 2) PLEASE PROVIDE THE BTU?S ON THE DRAWING FOR THE NEW
 GENERATOR. FBC FS 107.2.1
  
 3) PLEASE SHOW A DETAIL OF THE NEW PIPING CONNECTING TO
 THE EXISTING PIPING SYSTEM. FBC FS 107.2.1
  
 4) THE ?? GALV. PIPE FROM THE METER TO THE ?T?
 CONNECTION FOR THE NEW PIPING TO THE GENERATOR MUST BE
 ABLE TO CARRY THE ENTIRE PIPING SYSTEM BTU?S AT THE NOW
 LONGER ? LONGEST LENGTH METHOD?. FBC FS 107.2.1
  
 5) PROVIDE THE NUMBERS OF THE GAS TABLES USED TO SIZE
 THIS SYSTEM. FBC FS 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2020-06-04 Cont ID  
Sent By medwards Date 2020-06-04 Time 09:43 Rev Time 0.00
Received By medwards Date 2020-06-04 Time 09:43 Sent To  
Notes
2020-06-04 09:44:243RD REVIEW FBC-2017 MECHANICAL
 PERMIT-19110402
  
 CODES IN EFFECT:
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) NOT ENOUGH INFORMATION INCLUDED IN THIS SUBMISSION
 TO DO THIS GAS LINE REVIEW: PLEASE SHOW A DETAIL OF THE
 NEW PIPE CONNECTION INTO THE EXISTING SYSTEM. WHAT IS
 THE PRESSURE OF THE EXISTING SYSTEM? FBC FS 107.2.1,
 FBC RES G2412.4
  
 2) PLEASE SHOW THE LOCATION OF THE REGULATOR, ALSO
 PROVIDE SPECS ON THE REGULATOR USED. FBC RES G2421.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2019-12-20 Cont ID  
Sent By lcrespo Date 2019-12-20 Time 19:07 Rev Time 0.00
Received By lcrespo Date 2019-12-20 Time 19:07 Sent To  
Notes
2019-12-20 19:08:3712/20/2019 2ND GAS REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF
 THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH
 FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA
 STATUTE 471. WPB AMENDMENTS TO THE FBC SEC. 107.1
 GENERAL.
 2. PLEASE SHOW ON ISOMETRIC REGULATOR, UNION, DRIP
 LEGS, AND BTU'S OF GENERATOR (IF NEEDED PER UNIT) PER
 THE 2017 FBC FG SEC. 409.4.
 3. THE PHYSICAL ADDRESS OF THE PROJECT MUST BE ON PLANS
 IN FULL, NUMBER, STREET, CITY, STATE, AND ZIP CODE PER
 THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
 30. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE 2017 FBC RES. SEC. G2421.1.
 5. TYPE OF GAS (LP OR NATURAL). WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 6. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE ISOMETRIC PER 2017 FBC FG SEC. 402.2 OR 2017 FBC
 RES. SEC. G2413.2.
 7. THE CITY RECORDS INDICATE AN EXISTING GAS METER. THE
 BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO
 THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES
 PER THE 2017 FBC RES. SECS. G2412.4, G2412.8, G2413.1,
 G2413.2, G2413.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-11-18 Cont ID  
Sent By lcrespo Date 2019-11-18 Time 06:57 Rev Time 0.00
Received By lcrespo Date 2019-11-18 Time 06:57 Sent To  
Notes
2019-11-18 06:59:3911/19/2019 1ST GAS REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON THE ELECTRICAL SHOW A 16 KW CIRCLED AND ON THE
 PLUMBING IT HAS A 22 KW WHICH ONE IS IT HAS THE HAVE
 DIFFERENT BTU'S, PLEASE CLARIFY PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 2. PLEASE LABEL SHUTOFF VALVES, UNIONS, DRIP LEGS,
 BTU'S OF GENERATOR AND REGULATORS (IF NEEDED PER UNIT)
 ON ISOMETRIC PER THE 2017 FBC FG SEC. 409.4.
 3. THE PHYSICAL ADDRESS OF THE PROJECT MUST BE ON PLANS
 IN FULL, NUMBER, STREET, CITY, STATE, AND ZIP CODE PER
 THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS
 4. SUBMIT COPIES OF THE SIZING TABLE USED IN THE DESIGN
 FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS OF
 PLANS LISTING THE SIZING TABLES FROM GAS CODES OR
 ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM PER THE 2017 FBC FG SEC. 402.
 5. TYPE OF GAS (LP OR NATURAL). WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 6. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC FG SEC. 402.2 OR 2017 FBC RES.
 SEC. G2413.2.
 7. THE CITY RECORDS INDICATE AN EXISTING GAS METER. THE
 BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO
 THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES
 PER THE 2017 FBC RES. SECS. G2412.4, G2412.8, G2413.1,
 G2413.2, G2413.3.
 8. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF
 THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH
 FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA
 STATUTE 471. WPB AMENDMENTS TO THE FBC SEC. 107.1
 GENERAL.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-06-22 Cont ID  
Sent By ccarvaja Date 2020-06-22 Time 13:48 Rev Time 0.00
Received By ccarvaja Date 2020-06-12 Time 16:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-06-08 Cont ID  
Sent By shill Date 2020-06-08 Time 12:04 Rev Time 0.00
Received By shill Date 2020-05-04 Time 10:57 Sent To  
Notes
2020-05-13 10:57:32CONVERTED TO DIGITAL. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-01-02 Cont ID  
Sent By rmcdouga Date 2020-01-02 Time 11:04 Rev Time 0.00
Received By rmcdouga Date 2019-12-20 Time 14:50 Sent To  
Notes
2019-12-20 14:51:03RESUB ROUTED TO LCRESPO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-11-18 Cont ID  
Sent By lcrespo Date 2019-11-18 Time 07:01 Rev Time 0.00
Received By lcrespo Date 2019-11-07 Time 10:31 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-06-22 Cont ID  
Sent By cthroop Date 2020-06-22 Time 11:21 Rev Time 0.00
Received By cthroop Date 2020-06-22 Time 11:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-06-08 Cont ID  
Sent By rmcdouga Date 2020-06-08 Time 12:04 Rev Time 0.00
Received By shill Date 2020-06-08 Time 12:04 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-07-23 Cont ID  
Sent By medwards Date 2020-07-23 Time 14:49 Rev Time 0.00
Received By medwards Date 2020-07-23 Time 14:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-06-19 Cont ID  
Sent By rmcdouga Date 2020-06-19 Time 10:43 Rev Time 0.00
Received By rmcdouga Date 2020-06-19 Time 10:43 Sent To  
Notes
2020-06-19 10:45:36THE ELECTRONICALLY SUBMITTED GENERATOR PAD DRAWING IS
 REQUIRED TO BE DIGITALLY SIGNED BY THE ENGINEER. FS 471
 & FAC 61 G15

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-05-15 Cont ID  
Sent By rmcdouga Date 2020-05-15 Time 14:47 Rev Time 0.00
Received By rmcdouga Date 2020-05-15 Time 14:47 Sent To  
Notes
2020-05-15 14:49:03 
 THE GENERATOR PAD AND ANCHORING PLANS FROM AN ENGINEER
 ARE REQUIRED TO HAVE THE ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATIRE. ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS WHICH MUST
 BE SIGNED, DATED AND SEALED IN ACCORDANCE WITH THE
 PROVISIONS OF SECTION 471.025, F.S., AND RULE
 61G15-23.001, F.A.C. MUST BE PHYSICALLY SIGNED, DATED
 AND SEALED AS PROVIDED HEREIN BY THE PROFESSIONAL
 ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE
 USED.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-05-12 Cont ID  
Sent By shill Date 2020-05-12 Time 12:58 Rev Time 0.00
Received By shill Date 2020-05-12 Time 12:58 Sent To  
Notes
2020-05-12 12:59:41****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SEE PREVIOUS BUILDING COMMENTS; ORIGINAL SIGNED AND
 SEALED ENGINEERING IS REQUIRED, FS471. EITHER EMAIL A
 DIGITALLY SIGNED PLAN TO ME, OR YOU CAN DROP OFF ONE
 ORIGINAL TO THE BUILDING DIVISION WITH A PLAN REVIEW
 REQUEST FORM, DESCRIPTION "SIGNATURE DOCUMENTS".
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2019-11-13 Cont ID  
Sent By lcrespo Date 2019-11-18 Time 07:01 Rev Time 0.00
Received By rfalcone Date 2019-11-13 Time 09:42 Sent To  
Notes
***NONE***