| 2019-11-26 11:23:40 | PLAN REVIEW - ELECTRICAL |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. PROVIDE EXHAUST FAN IN NEW BATHROOM. |
| | |
| | M1507.4 LOCAL EXHAUST RATES. |
| | |
| | LOCAL EXHAUST SYSTEMS SHALL BE DESIGNED TO HAVE THE |
| | CAPACITY TO EXHAUST THE MINIMUM AIR FLOW RATE |
| | DETERMINED IN ACCORDANCE WITH TABLE M1507.4. |
| | |
| | TABLE M1507.4 |
| | |
| | MINIMUM REQUIRED LOCAL EXHAUST RATES FOR ONE- AND |
| | TWO-FAMILY DWELLINGS |
| | |
| | AREA TO BE EXHAUSTED |
| | EXHAUST RATES |
| | KITCHENS 100 CFM INTERMITTENT OR 25 CFM CONTINUOUS |
| | BATHROOMS-TOILET ROOMS |
| | MECHANICAL EXHAUST CAPACITY OF 50 CFM INTERMITTENT OR |
| | 20 CFM CONTINUOUS |
| | |
| | 2. PROVIDE EXTERIOR OUTLET AT BALCONY. |
| | NOT LESS THAN ONE RECEPTACLE OUTLET THAT IS READILY |
| | ACCESSIBLE FROM GRADE LEVEL AND LOCATED NOT MORE THAN 6 |
| | FEET, 6 INCHES (1981 MM) ABOVE GRADE, SHALL BE |
| | INSTALLED OUTDOORS AT THE FRONT AND BACK OF EACH |
| | DWELLING UNIT HAVING DIRECT ACCESS TO GRADE LEVEL. |
| | BALCONIES, DECKS, AND PORCHES THAT ARE ACCESSIBLE FROM |
| | INSIDE OF THE DWELLING UNIT SHALL HAVE AT LEAST ONE |
| | RECEPTACLE OUTLET INSTALLED WITHIN THE PERIMETER OF THE |
| | BALCONY, DECK, OR PORCH. THE RECEPTACLE SHALL BE |
| | LOCATED NOT MORE THAN 6 FEET, 6 INCHES (1981 MM) ABOVE |
| | THE BALCONY, DECK, OR PORCH SURFACE. [210.52(E)] FBC RE |
| | 3901.7 |
| | |
| | 3. PROVIDE PANEL SCHEDULE. |
| | PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| | WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5, |
| | 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | |
| | |
| | |
| | |
| | |