Plan Review Details - Permit 19110360
Plan Review Stops For Permit 19110360
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-12-11 Cont ID  
Sent By jpearson Date 2019-12-11 Time 08:17 Rev Time 0.00
Received By jpearson Date 2019-12-11 Time 08:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-11-12 Cont ID  
Sent By jpearson Date 2019-11-12 Time 12:51 Rev Time 0.00
Received By jpearson Date 2019-11-12 Time 12:51 Sent To  
Notes
2019-11-12 12:25:47CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THIS WAS SUBMITTED AS A REVISION TO PERMIT 16061443.
 I COULD NOT FIND ANY OF THESE SHEETS IN THAT PERMIT. IS
 THIS PERHAPS A SEPARATE PERMIT AND NOT A REVISION? WHY
 ARE PLANS ONLY INCLUDED FOR FLOORS 1, 2, 6 AND 13? WHAT
 PERMIT NUMBER ARE THE ORIGINAL PLANS UNDER? PROVIDE
 CLARIFICATIONS AND/OR CORRECTIONS AS NEEDED. WPB FBC
 107.2.1
 2. PROVIDE SCOPE OF WORK FOR THE ITEMS DETAILED IN THIS
 REVISION. WHAT IS THE VALUE OF THE PROPOSED WORK,
 INCLUDING ALL MATERIALS AND LABOR? WPB FBC 109.3
 3. ITEMS SUBMITTED FOR THIS PROJECT ARE REQUIRED TO BE
 SUBMITTED IN DIGITAL FORMAT. PROVIDE CORRECTION. WPB
 FBC 107.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-12-11 Time   Rev Time 0.00
Received By cpuell Date 2019-11-22 Time 11:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-11-12 Time   Rev Time 0.00
Received By cpuell Date 2019-11-07 Time 10:08 Sent To  
Notes
2019-11-09 10:09:13JPEARSON'S DESK

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-12-12 Cont ID  
Sent By jpearson Date 2019-12-12 Time 08:21 Rev Time 0.00
Received By jpearson Date 2019-12-12 Time 08:21 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-12-11 Cont ID  
Sent By jpearson Date 2019-12-11 Time 08:17 Rev Time 0.00
Received By jpearson Date 2019-12-11 Time 08:17 Sent To  
Notes
2019-12-11 08:17:15CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN SHEETS FOR FLOORS 1, 2, 6, AND 13 ARE NOT
 SIGNED BY THE PERSON RESPONSIBLE FOR THE DESIGN. ALL
 OTHER SHEETS HAVE THE CORRECT DIGITAL SIGNATURES. PER
 THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN IS
 REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. PROVIDE CORRECTION. WPB FBC 107.1; FS
 471/481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved