Plan Review Details - Permit 19110314
Plan Review Stops For Permit 19110314
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-12-01 Cont ID  
Sent By jpearson Date 2019-12-01 Time 13:56 Rev Time 0.00
Received By jpearson Date 2019-12-01 Time 13:56 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-11-16 Cont ID  
Sent By bwoods Date 2019-11-16 Time   Rev Time  
Received By bwoods Date 2019-11-15 Time   Sent To E
Notes
2019-11-16 12:10:22 
 PERMIT #19110314
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 SHALL COMPLY WITH NFPA 101 CHAPTER 7 MEANS OF EGRESS
  
 7.2.1.5.6 ELECTRICALLY CONTROLLED EGRESS DOOR
 ASSEMBLIES.
 DOOR ASSEMBLIES IN THE MEANS OF EGRESS SHALL BE
 PERMITTED TO
 BE ELECTRICALLY LOCKED IF EQUIPPED WITH APPROVED,
 LISTED HARDWARE,
 PROVIDED THAT ALL OF THE FOLLOWING CONDITIONS ARE
 MET:(1) THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK
 IS AFFIXED TO
 THE DOOR LEAF.
 (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION
 THAT IS
 READILY OPERATED IN THE DIRECTION OF EGRESS.
 (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE
 HAND
 IN THE DIRECTION OF EGRESS.
 (4) OPERATION OF THE HARDWARE INTERRUPTS THE POWER
 SUPPLY
 DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE DOOR
 ASSEMBLY
 IN THE DIRECTION OF EGRESS.
 (5)*LOSS OF POWER TO THE LISTED RELEASING HARDWARE
 AUTOMATICALLY
 UNLOCKS THE DOOR ASSEMBLY IN THE DIRECTION OF EGRESS.
 (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN
 ACCORDANCE WITH
 ANSI/UL 294, STANDARD FOR ACCESS CONTROL SYSTEM UNITS.
  
  
  
 7.2.1.6.2* ACCESS-CONTROLLED EGRESS DOOR ASSEMBLIES.
 WHERE
 PERMITTED IN CHAPTERS 11 THROUGH 43, DOOR ASSEMBLIES IN
 THE
 MEANS OF EGRESS SHALL BE PERMITTED TO BE EQUIPPED WITH
 ELECTRICAL
 LOCK HARDWARE THAT PREVENTS EGRESS, PROVIDED THAT ALL
 OF
 THE FOLLOWING CRITERIA ARE MET:
 (1) A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE,
 ARRANGED TO
 UNLOCK THE DOOR LEAF IN THE DIRECTION OF EGRESS UPON
 DETECTION
 OF AN APPROACHING OCCUPANT.(2) DOOR LEAVES SHALL
 AUTOMATICALLY UNLOCK IN THE DIRECTION OF
 EGRESS UPON LOSS OF POWER TO THE SENSOR OR TO THE PART
 OF
 THE ACCESS CONTROL SYSTEM THAT LOCKS THE DOOR LEAVES.
 (3) DOOR LOCKS SHALL BE ARRANGED TO UNLOCK IN THE
 DIRECTION OF
 EGRESS FROM A MANUAL RELEASE DEVICE COMPLYING WITH ALL
 OF
 THE FOLLOWING CRITERIA:
 (A) THE MANUAL RELEASE DEVICE SHALL BE LOCATED ON THE
 EGRESS SIDE, 40 IN. TO 48 IN. (1015 MM TO 1220 MM)
 VERTICALLY ABOVE THE FLOOR, AND WITHIN 60 IN.
 (1525 MM) OF THE SECURED DOOR OPENINGS.
 (B) THE MANUAL RELEASE DEVICE SHALL BE READILY
 ACCESSIBLE
 AND CLEARLY IDENTIFIED BY A SIGN THAT READS AS FOLLOWS:
 PUSH TO EXIT.
 (C) WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL
 RESULT
 IN DIRECT INTERRUPTION OF POWER TO THE LOCK ?
 INDEPENDENT OF THE LOCKING SYSTEM ELECTRONICS?AND
 THE LOCK SHALL REMAIN UNLOCKED FOR NOT LESS THAN
 30 SECONDS.
 (4) ACTIVATION OF THE BUILDING FIRE-PROTECTIVE
 SIGNALING SYSTEM,
 IF PROVIDED, SHALL AUTOMATICALLY UNLOCK THE DOOR LEAVES
 IN
 THE DIRECTION OF EGRESS, AND THE DOOR LEAVES SHALL
 REMAIN
 UNLOCKED UNTIL THE FIRE-PROTECTIVE SIGNALING SYSTEM HAS
 BEEN MANUALLY RESET.
 (5) THE ACTIVATION OF MANUAL FIRE ALARM BOXES THAT
 ACTIVATE THE
 BUILDING FIRE-PROTECTIVE SIGNALING SYSTEM SPECIFIED IN
 7.2.1.6.2(4) SHALL NOT BE REQUIRED TO UNLOCK THE DOOR
 LEAVES.
 (6) ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER OR
 FIRE DETECTION
 SYSTEM, IF PROVIDED, SHALL AUTOMATICALLY UNLOCK THE
 DOOR LEAVES IN THE DIRECTION OF EGRESS, AND THE DOOR
 LEAVES
 SHALL REMAIN UNLOCKED UNTIL THE FIRE-PROTECTIVE
 SIGNALING
 SYSTEM HAS BEEN MANUALLY RESET.
 (7) THE EGRESS SIDE OF ACCESS-CONTROLLED EGRESS DOORS,
 OTHER THAN
 EXISTING ACCESS-CONTROLLED EGRESS DOORS, SHALL BE
 PROVIDED
 WITH EMERGENCY LIGHTING IN ACCORDANCE WITH SECTION 7.9.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-12-01 Time   Rev Time 0.00
Received By lmarchan Date 2019-11-06 Time 15:00 Sent To  
Notes
2019-11-06 15:00:50ROUTED TO FIRE INBOX