| 2020-03-17 15:34:06 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 96= STANDARD FOR VENTILATION CONTROLAND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 1ST REVIEW |
| | 19110260 2970 N MILITARY TRAIL |
| | |
| | PLUMBING COMMEMTS: DENIED |
| | |
| | I.REGARDING MASTER PERMIT 19020380 REVIEW #2 DATED |
| | 7/25/19 |
| | THIS ISSUE HAS NEVER BEEN ADDRESSED. PLUMBING RESPONSE |
| | NOTE 11 ONLY ADDRESSES THE ROOF HYDRANT AND THE |
| | SUBMITTED NIDEL #50 BACKFLOW PREVENTER INDICATED ON |
| | PLAN C8.1 AND C8 DOES NOT PROVIDE PROTECTION OF THE |
| | POTABLE WATER SUPPLY. THE Y34 YARD HYDRANT HAS A STOP |
| | AND WASTE VALVE AT THE BASE OF THE RISER WHICH WILL |
| | ALLOW GROUND WATER AND CONTAMINATES TO ENTER THE |
| | SYSTEM. PROVIDE A DEDICATED REDUCED PRESSURE BACKFLOW |
| | PREVENTER IN THE SUPPLY LINE UPSTREAM OF THE YARD |
| | HYDRANTS. SHOW LOCATION, PROVIDE SPECIFICATION AND A |
| | DETAIL. REFER TO ALL NOTES LISTED IN 2ND REQUEST NOTED |
| | BELOW AND COMPLY. |
| | ***2ND REQUEST*** |
| | 1. SEE MARK UPS ON PLAN SHEET C8 AND SD1; THESE ITEMS |
| | MUST BE SATISFACTORILY ADDRESSED BEFORE A PLUMBING |
| | PERMIT WILL BE ISSUED. |
| | A. C8 AND SD1/DETAIL 12: SD1/DETAIL 12 CREATES A |
| | HAZARDOUS CONDITION. IN ACCORDANCE WITH FBC 608.7, |
| | 608.8.1 AND 608.8.2, PROVIDE A BACKFLOW PREVENTER FOR |
| | THE DEDICATED SUPPLY, SIGNAGE AT THE HYDRANTS AND |
| | EXPOSED PIPING SHALL BE COLOR PURPLE AND LABELED. |
| | 1) FBC PL 608.7 VALVES AND OUTLETS PROHIBITED BELOW |
| | GRADE. FREEZEPROOF YARD HYDRANTS THAT DRAIN THE RISER |
| | INTO THE GROUND SHALL BE PERMITTED TO BE INSTALLED, |
| | PROVIDED THAT THE POTABLE WATER SUPPLY TO SUCH HYDRANTS |
| | IS PROTECTED UPSTREAM OF THE HYDRANTS IN ACCORDANCE |
| | WITH SECTION 608 AND THE HYDRANTS ARE PERMANENTLY |
| | IDENTIFIED AS NON-POTABLE OUTLETS BY APPROVED SIGNAGE |
| | THAT READS AS FOLLOWS: ?CAUTION, NON-POTABLE WATER. DO |
| | NOT DRINK.? |
| | A.FBC PL608.8.1 SIGNAGE REQUIRED. |
| | NONPOTABLE WATER OUTLETS, SUCH AS HOSE CONNECTIONS, |
| | OPEN ENDED PIPES AND FAUCETS, SHALL BE IDENTIFIED WITH |
| | SIGNAGE THAT READS AS FOLLOWS: ?NON-POTABLE WATER IS |
| | UTILIZED FOR [APPLICATION NAME]. CAUTION: NONPOTABLE |
| | WATER ? DO NOT DRINK.? THE WORDS SHALL BE LEGIBLY AND |
| | INDELIBLY PRINTED ON A TAG OR SIGN CONSTRUCTED OF |
| | CORROSION-RESISTANT WATERPROOF MATERIAL OR SHALL BE |
| | INDELIBLY PRINTED ON THE FIXTURE. THE LETTERS OF THE |
| | WORDS SHALL BE NOT LESS THAN 0.5 INCH (12.7 MM) IN |
| | HEIGHT AND IN COLORS IN CONTRAST TO THE BACKGROUND ON |
| | WHICH THEY ARE APPLIED. IN ADDITION TO THE REQUIRED |
| | WORDAGE, THE PICTOGRAPH SHOWN IN FBC PL FIGURE 608.8.1 |
| | SHALL APPEAR ON THE REQUIRED SIGNAGE. |
| | B. FBC PL 608.8.2 DISTRIBUTION PIPE LABELING AND |
| | MARKING. |
| | C. NON-POTABLE DISTRIBUTION PIPING SHALL BE PURPLE IN |
| | COLOR AND SHALL BE EMBOSSED, OR INTEGRALLY STAMPED OR |
| | MARKED, WITH THE WORDS: ?CAUTION: NONPOTABLE WATER ? DO |
| | NOT DRINK? OR THE PIPING SHALL BE INSTALLED WITH A |
| | PURPLE IDENTIFICATION TAPE OR WRAP. PIPE IDENTIFICATION |
| | SHALL INCLUDE THE CONTENTS OF THE PIPING SYSTEM AND AN |
| | ARROW INDICATING THE DIRECTION OF FLOW. HAZARDOUS |
| | PIPING SYSTEMS SHALL ALSO CONTAIN INFORMATION |
| | ADDRESSING THE NATURE OF THE HAZARD. PIPE |
| | IDENTIFICATION SHALL BE REPEATED AT INTERVALS NOT |
| | EXCEEDING 25 FEET (7620 MM) AND AT EACH POINT WHERE THE |
| | PIPING PASSES THROUGH A WALL, FLOOR OR ROOF. LETTERING |
| | SHALL BE READILY OBSERVABLE WITHIN THE ROOM OR SPACE |
| | WHERE THE PIPING IS LOCATED. |
| | B.ADDITIONAL COMMENT: PER WPB FBC 1097.2.1, ADD SPEC |
| | AND DETAIL FOR BACKFLOW PREVENTER AND SHOW LOCATION ON |
| | THE PLAN |
| | II. REGARDING THE GREASE INTERCEPTOR, THERE IS NO |
| | EXCEPTION TAKEN. RESUBMIT AS IS WITH NEXT RESUBMITTAL. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | |
| | |
| | 19110260 2970 N MILITARY TRAIL |
| | MASTER PERMIT 19020380 2970 N MILITARY TRAIL |
| | RACETRAC #1367 JAY BOSWELL |
| | [email protected] OFFICE: 954-426-5144 |
| | CELL: 954-295-1764 |
| | |
| | GDP GROUP MARK S. SALOPEK, LLC 330-802-6255 |
| | |
| | |
| | |