| Plan Review Stops For Permit 19110249 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2020-01-31 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2020-01-31 |
Time |
14:29 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2020-01-31 |
Time |
13:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2019-12-31 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-12-31 |
Time |
16:23 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-12-31 |
Time |
15:26 |
Sent To |
|
|
| Notes |
| 2019-12-31 16:23:40 | ALTERATION SECOND BUILDING REVIEW COMMENTS | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | PERMIT #19110249 | | | | | | NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | ORIGINAL COMMENT: | | | 1- USE OF THIS BUILDING IS NOT CLEAR. PLANS SHOW THE | | | LAYOUT OF A SINGLE FAMILY RESIDENCE BUT ALL THE | | | INFORMATION SHOWN UNDER THE AREA CALCULATIONS IS FOR | | | BUSINESS TYPE USE. CLARIFY/REVISE AS REQUIRED. CLEARLY | | | DEFINE THE USE OF THE BUILDING. SEC. 107.2.1 CITY | | | AMENDMENTS AND SEC. 301.1 FBC-BUILDING. | | | | | | RESPONSE: | | | A) PLANS SUBMITTED NOW ARE INCOMPLETE. ONLY ONE SHEET | | | OF ARCHITECTURAL DRAWING A-000 WAS SUBMITTED AND | | | REVISED SHEET A-100 WAS NOT SUBMITTED. NEED TO PROVIDE | | | TWO COMPLETE SETS. SEC. 107.1 AND 107.2.1 CITY | | | AMENDMENTS. | | | | | | B) THE BUILDING DATA ON SHEET A-000 STATES THAT THIS | | | BUILDING IS CONSTRUCTION TYPE II-B. TYPICALLY SINGLE | | | FAMILY RESIDENCES ARE CONSTRUCTION TYPE VB. PROVIDE | | | PROOF THAT THIS A TYPE II-B BUILDING WITH | | | NON-COMBUSTIBLE MATERIALS AS REQUIRED BY SEC. 602.2 | | | FBC-BUILDING OR REVISE TYPE OF CONSTRUCTION AS | | | REQUIRED. | | | | | | ORIGINAL COMMENT: | | | 2- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED | | | BY SEC. 811.1 FBC-EXISTING BUILDING. | | | NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL | | | REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID | | | CONFLICTS/DELAYS. | | | | | | RESPONSE: | | | A) ENERGY CALCULATIONS FORM IS REQUIRED TO BE CERTIFIED | | | AT THE BOTTOM OF THE FORM BY THE OWNER, THE OWNER'S | | | ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY | | | THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY | | | SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, 6TH EDITION | | | (2017). | | | | | | B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, | | | INCLUDING OWNER'S NAME. SEC. R101.5.1.1.2 FBC-ENERGY | | | CONSERVATION. | | | | | | ORIGINAL COMMENT: | | | 3-CLEARLY SPECIFY TYPE AND SIZE OF EXISTING BEDROOM | | | WINDOWS AND TYPE AND SIZE OF PROPOSED WINDOWS TO VERIFY | | | COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. 702.5 | | | FBC-EXISTING BUILDING. | | | NOTE: NEED TO VERIFY MANUFACTURER'S LARGEST STANDARD | | | SIZE WINDOW THAT WILL FIT WITHIN THE EXISTING FRAME OR | | | EXISTING ROUGH OPENING AND THAT WILL NOT REDUCE THE | | | EGRESS SIZE OPENING OF EXISTING WINDOW AS REQUIRED BY | | | SEC. 702.5. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOTE: COORDINATE WITH ITEM #1 ABOVE. | | | INCOMPLETE PLANS SUBMITTED. | | | | | | | | | ORIGINAL COMMENT: | | | 4-DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | | | RESPONSE: | | | UNABLE TO VERIFY IF PRODUCT APPROVALS WERE REVIEWED BY | | | THE DESIGNER OF RECORD. ALSO, THERE ARE NEW PRODUCT | | | APPROVALS SUBMITTED. PROVIDE TWO SETS OF EACH PRODUCT | | | APPROVAL REVIEWED AND APPROVED IN WRITING BY THE | | | ARCHITECT OF RECORD. | | | | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND | | | REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE | | | DON'T STAPLE OLD DRAWINGS/DOCUMENTS. SUBMIT OLD | | | DRAWINGS/DOCUMENTS FOR REFERENCE. | | | | | | | | | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE | | | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE | | | COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-11-25 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-11-25 |
Time |
13:41 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-11-25 |
Time |
10:04 |
Sent To |
|
|
| Notes |
| 2019-11-25 13:41:53 | ALTERATION BUILDING REVIEW COMMENTS | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | PERMIT #19110249 | | | | | | NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 1- USE OF THIS BUILDING IS NOT CLEAR. PLANS SHOW THE | | | LAYOUT OF A SINGLE FAMILY RESIDENCE BUT ALL THE | | | INFORMATION SHOWN UNDER THE AREA CALCULATIONS IS FOR | | | BUSINESS TYPE USE. CLARIFY/REVISE AS REQUIRED. CLEARLY | | | DEFINE THE USE OF THE BUILDING. SEC. 107.2.1 CITY | | | AMENDMENTS AND SEC. 301.1 FBC-BUILDING. | | | | | | 2- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED | | | BY SEC. 811.1 FBC-EXISTING BUILDING. | | | NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL | | | REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID | | | CONFLICTS/DELAYS. | | | | | | 3-CLEARLY SPECIFY TYPE AND SIZE OF EXISTING BEDROOM | | | WINDOWS AND TYPE AND SIZE OF PROPOSED WINDOWS TO VERIFY | | | COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. 702.5 | | | FBC-EXISTING BUILDING. | | | NOTE: NEED TO VERIFY MANUFACTURER'S LARGEST STANDARD | | | SIZE WINDOW THAT WILL FIT WITHIN THE EXISTING FRAME OR | | | EXISTING ROUGH OPENING AND THAT WILL NOT REDUCE THE | | | EGRESS SIZE OPENING OF EXISTING WINDOW AS REQUIRED BY | | | SEC. 702.5. | | | | | | 4-DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND | | | REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE | | | DON'T STAPLE OLD DRAWINGS/DOCUMENTS. SUBMIT OLD | | | DRAWINGS/DOCUMENTS FOR REFERENCE. | | | | | | | | | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE | | | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE | | | COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2020-01-31 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2020-01-31 |
Time |
12:16 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2020-01-31 |
Time |
12:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2020-01-07 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2020-01-07 |
Time |
09:07 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2020-01-07 |
Time |
08:16 |
Sent To |
I |
|
| Notes |
| 2020-01-07 09:07:19 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | NO ELECTRICAL RESPONSE PROVIDED. ONLY ONE SET OF PLANS | | | IN SET, AND NO ELECTRICAL SHEETS IN THAT SET. PROVIDE | | | TWO COPIES OF PLAN FOR REVIEW, AND ANSWER PREVIOS | | | COMMENTS. WPB FBC 107.2.1 | | | | | | 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR | | | SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY | | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | | SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC | | | RE E3606.3 | | | 2. PLAN STATES RECEPTACLES MARKED TP ARE TO BE TAMPER | | | PROOF, AND THEN SOME OF THE OUTLETS ARE MARKED TR, BUT | | | NOT ALL OF THEM. PROVIDE CORRECTION. EACH RECEPTACLE | | | DOES NOT HAVE TO BE MARKED, A NOTE WILL SUFFICE THAT | | | ALL RECEPTACLE OUTLETS MUST BE TAMPER RESISTANT. NEC | | | 406.12; FBC RE E4002.14 | | | 3. PROVIDE ACCURATE LOAD CALCULATION PER THE METHOD | | | PRESCRIBED IN FBC RESIDENTIAL. NEC 220; FBC RE E3602.2 | | | 4. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A | | | TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST | | | ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND | | | NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE | | | INSTALLED AT THE FRONT AND BACK OF THE DWELLING. | | | PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE E3901.7 | | | 5. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR | | | SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE | | | EQUIPMENT PER CODE. NEC 210.63; FBC RE E3901.12 | | | 6. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING | | | REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE | | | INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG | | | THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET | | | FROM A RECEPTACLE OUTLET. THE WALL SPACING REQUIREMENTS | | | FOR KITCHEN COUNTER SPACE STATE THAT RECEPTACLE OUTLETS | | | SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE | | | IS MORE THAN 24 INCHES MEASURED HORIZONTALLY FROM A | | | RECEPTACLE OUTLET IN THAT SPACE, AND SHOULD BE | | | INSTALLED IN EACH LOCATION WHERE THE COUNTER TOP IS 12 | | | INCHES OR GREATER. THE PLAN PROVIDED DOES NOT MEET THIS | | | CODE IN SOME AREAS. PROVIDE CORRECTION. NEC | | | 210.52(C)(1); FBC RE E3901 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH | | | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. | | | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL | | | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. | | | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD | | | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-11-20 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-11-20 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-11-20 |
Time |
13:31 |
Sent To |
|
|
| Notes |
| 2019-11-20 15:43:09 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR | | | SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY | | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | | SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC | | | RE E3606.3 | | | 2. PLAN STATES RECEPTACLES MARKED TP ARE TO BE TAMPER | | | PROOF, AND THEN SOME OF THE OUTLETS ARE MARKED TR, BUT | | | NOT ALL OF THEM. PROVIDE CORRECTION. EACH RECEPTACLE | | | DOES NOT HAVE TO BE MARKED, A NOTE WILL SUFFICE THAT | | | ALL RECEPTACLE OUTLETS MUST BE TAMPER RESISTANT. NEC | | | 406.12; FBC RE E4002.14 | | | 3. PROVIDE ACCURATE LOAD CALCULATION PER THE METHOD | | | PRESCRIBED IN FBC RESIDENTIAL. NEC 220; FBC RE E3602.2 | | | 4. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A | | | TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST | | | ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND | | | NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE | | | INSTALLED AT THE FRONT AND BACK OF THE DWELLING. | | | PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE E3901.7 | | | 5. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR | | | SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE | | | EQUIPMENT PER CODE. NEC 210.63; FBC RE E3901.12 | | | 6. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING | | | REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE | | | INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG | | | THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET | | | FROM A RECEPTACLE OUTLET. THE WALL SPACING REQUIREMENTS | | | FOR KITCHEN COUNTER SPACE STATE THAT RECEPTACLE OUTLETS | | | SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE | | | IS MORE THAN 24 INCHES MEASURED HORIZONTALLY FROM A | | | RECEPTACLE OUTLET IN THAT SPACE, AND SHOULD BE | | | INSTALLED IN EACH LOCATION WHERE THE COUNTER TOP IS 12 | | | INCHES OR GREATER. THE PLAN PROVIDED DOES NOT MEET THIS | | | CODE IN SOME AREAS. PROVIDE CORRECTION. NEC | | | 210.52(C)(1); FBC RE E3901 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH | | | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. | | | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL | | | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. | | | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD | | | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
N |
Date |
2019-12-03 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-12-03 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-12-03 |
Time |
10:59 |
Sent To |
|
|
| Notes |
| 2019-12-03 11:05:18 | SFR REVIEW NOT REQUIRED BY FIRE |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
3 |
Status |
P |
Date |
2020-01-30 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2020-01-30 |
Time |
16:22 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2020-01-30 |
Time |
16:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
P |
Date |
2019-12-23 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2019-12-23 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2019-12-23 |
Time |
15:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2019-12-11 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2019-12-11 |
Time |
15:15 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2019-12-11 |
Time |
15:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2020-01-31 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2020-01-31 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2020-01-13 |
Time |
13:42 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2020-01-07 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-12-18 |
Time |
14:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-12-12 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2019-12-12 |
Time |
13:30 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2019-11-05 |
Time |
10:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2020-01-31 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2020-01-31 |
Time |
14:29 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2020-01-31 |
Time |
14:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2020-01-06 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2020-01-06 |
Time |
11:16 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2020-01-06 |
Time |
10:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2019-11-25 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-11-25 |
Time |
13:42 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-11-25 |
Time |
13:42 |
Sent To |
|
|
| Notes |
| 2019-11-25 13:45:37 | RESIDENTIAL (R3) ALTERATION LEVEL 2, MECHANICAL REVIEW | | | COMMENTS | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | PERMIT #19110249 | | | | | | NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 1- PROVIDE EQUIPMENT SIZING CALCULATIONS (2 COPIES) AS | | | REQUIRED BY SEC. 811.1 FBC-EXISTING BUILDING AND SEC. | | | R403.7.1 FBC-ENERGY CONSERVATION. | | | NOTE: COORDINATE EQUIPMENT WITH EQUIPMENT SPECIFIED ON | | | PLANS TO AVOID CONFLICTS/DELAYS. | | | | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND | | | REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE | | | DON'T STAPLE OLD DRAWINGS/DOCUMENTS. SUBMIT OLD | | | DRAWINGS/DOCUMENTS FOR REFERENCE. | | | | | | | | | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE | | | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE | | | COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2019-11-19 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2019-11-19 |
Time |
12:03 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2019-11-19 |
Time |
12:02 |
Sent To |
|
|
| Notes |
| 2019-11-19 12:03:10 | PLUMBING COMMENTS: APPROVED W/PROVISO | | | 1. ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD | | | INSPECTOR'S APPROVAL | | | 2. WATER HEATER SHALL BE ACCESSIBLE FOR OBSERVATION, | | | MAINTENANCE, SERVICING AND PEPLACEMENT PER FBC RES | | | P2801.4 | | | 3. PROVIDE THERMAL RELIEF VALVE IN COLD WATER SUPPLY | | | PER P2903.4.2 | | | 4. PROVIDE WATER HAMMER ARRESTORS, NOT AIR CHAMBERS FOR | | | CONTROL OF WATER HAMMER PER FBC RES P2903.5 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2020-01-30 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2020-01-30 |
Time |
16:22 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2020-01-30 |
Time |
16:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2019-12-23 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2019-12-23 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2019-12-23 |
Time |
15:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2019-12-11 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2019-12-11 |
Time |
15:15 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2019-12-11 |
Time |
15:15 |
Sent To |
|
|
| Notes |
|
|