Plan Review Details - Permit 19110249
Plan Review Stops For Permit 19110249
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-01-31 Cont ID  
Sent By jgomez Date 2020-01-31 Time 14:29 Rev Time 0.00
Received By jgomez Date 2020-01-31 Time 13:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-12-31 Cont ID  
Sent By jgomez Date 2019-12-31 Time 16:23 Rev Time 0.00
Received By jgomez Date 2019-12-31 Time 15:26 Sent To  
Notes
2019-12-31 16:23:40ALTERATION SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
 PERMIT #19110249
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 ORIGINAL COMMENT:
 1- USE OF THIS BUILDING IS NOT CLEAR. PLANS SHOW THE
 LAYOUT OF A SINGLE FAMILY RESIDENCE BUT ALL THE
 INFORMATION SHOWN UNDER THE AREA CALCULATIONS IS FOR
 BUSINESS TYPE USE. CLARIFY/REVISE AS REQUIRED. CLEARLY
 DEFINE THE USE OF THE BUILDING. SEC. 107.2.1 CITY
 AMENDMENTS AND SEC. 301.1 FBC-BUILDING.
  
 RESPONSE:
 A) PLANS SUBMITTED NOW ARE INCOMPLETE. ONLY ONE SHEET
 OF ARCHITECTURAL DRAWING A-000 WAS SUBMITTED AND
 REVISED SHEET A-100 WAS NOT SUBMITTED. NEED TO PROVIDE
 TWO COMPLETE SETS. SEC. 107.1 AND 107.2.1 CITY
 AMENDMENTS.
  
 B) THE BUILDING DATA ON SHEET A-000 STATES THAT THIS
 BUILDING IS CONSTRUCTION TYPE II-B. TYPICALLY SINGLE
 FAMILY RESIDENCES ARE CONSTRUCTION TYPE VB. PROVIDE
 PROOF THAT THIS A TYPE II-B BUILDING WITH
 NON-COMBUSTIBLE MATERIALS AS REQUIRED BY SEC. 602.2
 FBC-BUILDING OR REVISE TYPE OF CONSTRUCTION AS
 REQUIRED.
  
 ORIGINAL COMMENT:
 2- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED
 BY SEC. 811.1 FBC-EXISTING BUILDING.
 NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL
 REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID
 CONFLICTS/DELAYS.
  
 RESPONSE:
 A) ENERGY CALCULATIONS FORM IS REQUIRED TO BE CERTIFIED
 AT THE BOTTOM OF THE FORM BY THE OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY
 THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, 6TH EDITION
 (2017).
  
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER'S NAME. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 ORIGINAL COMMENT:
 3-CLEARLY SPECIFY TYPE AND SIZE OF EXISTING BEDROOM
 WINDOWS AND TYPE AND SIZE OF PROPOSED WINDOWS TO VERIFY
 COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. 702.5
 FBC-EXISTING BUILDING.
 NOTE: NEED TO VERIFY MANUFACTURER'S LARGEST STANDARD
 SIZE WINDOW THAT WILL FIT WITHIN THE EXISTING FRAME OR
 EXISTING ROUGH OPENING AND THAT WILL NOT REDUCE THE
 EGRESS SIZE OPENING OF EXISTING WINDOW AS REQUIRED BY
 SEC. 702.5.
  
 RESPONSE:
 REPEAT COMMENT. NOTE: COORDINATE WITH ITEM #1 ABOVE.
 INCOMPLETE PLANS SUBMITTED.
  
  
 ORIGINAL COMMENT:
 4-DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 RESPONSE:
 UNABLE TO VERIFY IF PRODUCT APPROVALS WERE REVIEWED BY
 THE DESIGNER OF RECORD. ALSO, THERE ARE NEW PRODUCT
 APPROVALS SUBMITTED. PROVIDE TWO SETS OF EACH PRODUCT
 APPROVAL REVIEWED AND APPROVED IN WRITING BY THE
 ARCHITECT OF RECORD.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE
 DON'T STAPLE OLD DRAWINGS/DOCUMENTS. SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-11-25 Cont ID  
Sent By jgomez Date 2019-11-25 Time 13:41 Rev Time 0.00
Received By jgomez Date 2019-11-25 Time 10:04 Sent To  
Notes
2019-11-25 13:41:53ALTERATION BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
 PERMIT #19110249
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1- USE OF THIS BUILDING IS NOT CLEAR. PLANS SHOW THE
 LAYOUT OF A SINGLE FAMILY RESIDENCE BUT ALL THE
 INFORMATION SHOWN UNDER THE AREA CALCULATIONS IS FOR
 BUSINESS TYPE USE. CLARIFY/REVISE AS REQUIRED. CLEARLY
 DEFINE THE USE OF THE BUILDING. SEC. 107.2.1 CITY
 AMENDMENTS AND SEC. 301.1 FBC-BUILDING.
  
 2- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED
 BY SEC. 811.1 FBC-EXISTING BUILDING.
 NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL
 REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID
 CONFLICTS/DELAYS.
  
 3-CLEARLY SPECIFY TYPE AND SIZE OF EXISTING BEDROOM
 WINDOWS AND TYPE AND SIZE OF PROPOSED WINDOWS TO VERIFY
 COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. 702.5
 FBC-EXISTING BUILDING.
 NOTE: NEED TO VERIFY MANUFACTURER'S LARGEST STANDARD
 SIZE WINDOW THAT WILL FIT WITHIN THE EXISTING FRAME OR
 EXISTING ROUGH OPENING AND THAT WILL NOT REDUCE THE
 EGRESS SIZE OPENING OF EXISTING WINDOW AS REQUIRED BY
 SEC. 702.5.
  
 4-DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE
 DON'T STAPLE OLD DRAWINGS/DOCUMENTS. SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-01-31 Cont ID  
Sent By jpearson Date 2020-01-31 Time 12:16 Rev Time 0.00
Received By jpearson Date 2020-01-31 Time 12:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-01-07 Cont ID  
Sent By jpearson Date 2020-01-07 Time 09:07 Rev Time 0.00
Received By jpearson Date 2020-01-07 Time 08:16 Sent To I
Notes
2020-01-07 09:07:19CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 NO ELECTRICAL RESPONSE PROVIDED. ONLY ONE SET OF PLANS
 IN SET, AND NO ELECTRICAL SHEETS IN THAT SET. PROVIDE
 TWO COPIES OF PLAN FOR REVIEW, AND ANSWER PREVIOS
 COMMENTS. WPB FBC 107.2.1
  
 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC
 RE E3606.3
 2. PLAN STATES RECEPTACLES MARKED TP ARE TO BE TAMPER
 PROOF, AND THEN SOME OF THE OUTLETS ARE MARKED TR, BUT
 NOT ALL OF THEM. PROVIDE CORRECTION. EACH RECEPTACLE
 DOES NOT HAVE TO BE MARKED, A NOTE WILL SUFFICE THAT
 ALL RECEPTACLE OUTLETS MUST BE TAMPER RESISTANT. NEC
 406.12; FBC RE E4002.14
 3. PROVIDE ACCURATE LOAD CALCULATION PER THE METHOD
 PRESCRIBED IN FBC RESIDENTIAL. NEC 220; FBC RE E3602.2
 4. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST
 ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND
 NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE
 INSTALLED AT THE FRONT AND BACK OF THE DWELLING.
 PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE E3901.7
 5. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR
 SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE
 EQUIPMENT PER CODE. NEC 210.63; FBC RE E3901.12
 6. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET. THE WALL SPACING REQUIREMENTS
 FOR KITCHEN COUNTER SPACE STATE THAT RECEPTACLE OUTLETS
 SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE
 IS MORE THAN 24 INCHES MEASURED HORIZONTALLY FROM A
 RECEPTACLE OUTLET IN THAT SPACE, AND SHOULD BE
 INSTALLED IN EACH LOCATION WHERE THE COUNTER TOP IS 12
 INCHES OR GREATER. THE PLAN PROVIDED DOES NOT MEET THIS
 CODE IN SOME AREAS. PROVIDE CORRECTION. NEC
 210.52(C)(1); FBC RE E3901
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-11-20 Cont ID  
Sent By jpearson Date 2019-11-20 Time 15:52 Rev Time 0.00
Received By jpearson Date 2019-11-20 Time 13:31 Sent To  
Notes
2019-11-20 15:43:09CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC
 RE E3606.3
 2. PLAN STATES RECEPTACLES MARKED TP ARE TO BE TAMPER
 PROOF, AND THEN SOME OF THE OUTLETS ARE MARKED TR, BUT
 NOT ALL OF THEM. PROVIDE CORRECTION. EACH RECEPTACLE
 DOES NOT HAVE TO BE MARKED, A NOTE WILL SUFFICE THAT
 ALL RECEPTACLE OUTLETS MUST BE TAMPER RESISTANT. NEC
 406.12; FBC RE E4002.14
 3. PROVIDE ACCURATE LOAD CALCULATION PER THE METHOD
 PRESCRIBED IN FBC RESIDENTIAL. NEC 220; FBC RE E3602.2
 4. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST
 ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND
 NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE
 INSTALLED AT THE FRONT AND BACK OF THE DWELLING.
 PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE E3901.7
 5. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR
 SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE
 EQUIPMENT PER CODE. NEC 210.63; FBC RE E3901.12
 6. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET. THE WALL SPACING REQUIREMENTS
 FOR KITCHEN COUNTER SPACE STATE THAT RECEPTACLE OUTLETS
 SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE
 IS MORE THAN 24 INCHES MEASURED HORIZONTALLY FROM A
 RECEPTACLE OUTLET IN THAT SPACE, AND SHOULD BE
 INSTALLED IN EACH LOCATION WHERE THE COUNTER TOP IS 12
 INCHES OR GREATER. THE PLAN PROVIDED DOES NOT MEET THIS
 CODE IN SOME AREAS. PROVIDE CORRECTION. NEC
 210.52(C)(1); FBC RE E3901
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2019-12-03 Cont ID  
Sent By pleduc Date 2019-12-03 Time   Rev Time 0.00
Received By pleduc Date 2019-12-03 Time 10:59 Sent To  
Notes
2019-12-03 11:05:18SFR REVIEW NOT REQUIRED BY FIRE

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2020-01-30 Cont ID  
Sent By fmittner Date 2020-01-30 Time 16:22 Rev Time 0.00
Received By fmittner Date 2020-01-30 Time 16:22 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2019-12-23 Cont ID  
Sent By fmittner Date 2019-12-23 Time 15:07 Rev Time 0.00
Received By fmittner Date 2019-12-23 Time 15:07 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2019-12-11 Cont ID  
Sent By fmittner Date 2019-12-11 Time 15:15 Rev Time 0.00
Received By fmittner Date 2019-12-11 Time 15:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-01-31 Cont ID  
Sent By jgomez Date 2020-01-31 Time 14:30 Rev Time 0.00
Received By jgomez Date 2020-01-13 Time 13:42 Sent To I
Notes
2020-01-14 13:43:39R11

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-01-07 Time   Rev Time 0.00
Received By lmarchan Date 2019-12-18 Time 14:47 Sent To  
Notes
2019-12-19 14:47:18B01

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-12-12 Cont ID  
Sent By cpuell Date 2019-12-12 Time 13:30 Rev Time 0.00
Received By cpuell Date 2019-11-05 Time 10:30 Sent To  
Notes
2019-11-06 10:30:30B14

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-01-31 Cont ID  
Sent By jgomez Date 2020-01-31 Time 14:29 Rev Time 0.00
Received By jgomez Date 2020-01-31 Time 14:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-01-06 Cont ID  
Sent By jgomez Date 2020-01-06 Time 11:16 Rev Time 0.00
Received By jgomez Date 2020-01-06 Time 10:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-11-25 Cont ID  
Sent By jgomez Date 2019-11-25 Time 13:42 Rev Time 0.00
Received By jgomez Date 2019-11-25 Time 13:42 Sent To  
Notes
2019-11-25 13:45:37RESIDENTIAL (R3) ALTERATION LEVEL 2, MECHANICAL REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
 PERMIT #19110249
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1- PROVIDE EQUIPMENT SIZING CALCULATIONS (2 COPIES) AS
 REQUIRED BY SEC. 811.1 FBC-EXISTING BUILDING AND SEC.
 R403.7.1 FBC-ENERGY CONSERVATION.
 NOTE: COORDINATE EQUIPMENT WITH EQUIPMENT SPECIFIED ON
 PLANS TO AVOID CONFLICTS/DELAYS.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE
 DON'T STAPLE OLD DRAWINGS/DOCUMENTS. SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-11-19 Cont ID  
Sent By jesmith Date 2019-11-19 Time 12:03 Rev Time 0.00
Received By jesmith Date 2019-11-19 Time 12:02 Sent To  
Notes
2019-11-19 12:03:10PLUMBING COMMENTS: APPROVED W/PROVISO
 1. ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
 2. WATER HEATER SHALL BE ACCESSIBLE FOR OBSERVATION,
 MAINTENANCE, SERVICING AND PEPLACEMENT PER FBC RES
 P2801.4
 3. PROVIDE THERMAL RELIEF VALVE IN COLD WATER SUPPLY
 PER P2903.4.2
 4. PROVIDE WATER HAMMER ARRESTORS, NOT AIR CHAMBERS FOR
 CONTROL OF WATER HAMMER PER FBC RES P2903.5

Review Stop Z ZONING
Rev No 3 Status P Date 2020-01-30 Cont ID  
Sent By fmittner Date 2020-01-30 Time 16:22 Rev Time 0.00
Received By fmittner Date 2020-01-30 Time 16:22 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2019-12-23 Cont ID  
Sent By fmittner Date 2019-12-23 Time 15:07 Rev Time 0.00
Received By fmittner Date 2019-12-23 Time 15:07 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-12-11 Cont ID  
Sent By fmittner Date 2019-12-11 Time 15:15 Rev Time 0.00
Received By fmittner Date 2019-12-11 Time 15:15 Sent To  
Notes
***NONE***