| 2019-11-06 17:06:45 | 11/06/2019 1ST GAS REVIEW **DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. NOTE: THE CITY OF WEST PALM BEACH HAS NO RECORD OF |
| | EXISTING GAS. A FULL EVALUATION OF ALL GAS EQUIPMENT |
| | WILL BE DONE AT THIS TIME BE BOUT UP TO CODE |
| | COMPLIANCE. THIS WILL REQUIRE A LAYOUT OF THE WATER |
| | HEATER UNIT; |
| | A. ARE THEY OUTSIDE OR INSIDE OR IN A ROOM DEDICATED |
| | FOR MAINTENANCE? |
| | B. DO THEY HAVE PROPER VENTILATION AND COMBUSTION AIR? |
| | C. THEY WILL NEED MANUFACTURES SPECIFICATIONS AND TOTAL |
| | BTU'S FOR ALL HEATERS. |
| | |
| | 2. GAS RISER DIAGRAM (ISOMETRIC) REQUIRED WPB |
| | AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL |
| | GAS. SUBMIT ON THE ISOMETRIC DRAWING AND CLEARLY SHOWS |
| | THE LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC |
| | RES. SECS. G2413.4.1, G2413.4.2. |
| | 3. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON |
| | PLANS IN FULL, NUMBER, STREET, CITY, STATE AND ZIP CODE |
| | PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 4. TYPE OF GAS (LP OR NATURAL). WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM ON |
| | THE PLAN PER 2017 FBC RES. SEC. G2413.2. |
| | 5. SIGNATURE IS REQUIRED BY THE PERSON SUBMITTING |
| | ISOMETRIC (EX. LICENSE CONTRACTOR) IN ACCORDANCE WITH |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA |
| | STATUTE 471. |
| | 6. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE, |
| | TERMINATION POINT, HEIGHT ABOVE THE ROOF AND ANCHORING |
| | DETAILS OF THE GAS VENT(S) PER THE 2017 FBC RES. SECS. |
| | G2426 THRU G2429.1. |
| | 7. SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE |
| | DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS |
| | OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR |
| | ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS |
| | SYSTEM PER THE 2017 FBC RES. SEC. G2413.3 |
| | 8. PLEASE LABEL THE SHUTOFF VALVE ON GAS ISOMERIC PER |
| | THE 2017 FBC RES. SEC. G2401.1.3. |
| | 9. SHOW DRIP LEG ON EQUIPMENT INSTALLED PER THE 2017 |
| | FBC RES. SEC. G2419.2. |
| | 10. IT IS RECOMMENDED TO CONTACT PLAN REVIEW AND OR DO |
| | A COURTESY INSPECTION OUT IN THE FIELD TO ACCESS THE |
| | GAS SYSTEM. YOU MAY CONTACT ME TO DISCUSS FURTHER |
| | ACTION ON THIS REVIEW FOR COMPLIANCE AT THE NUMBER |
| | BELOW. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | |