| 2019-11-15 13:14:55 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 19110144 |
| | REVIEWED: NOVEMBER 15, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK |
| | BELOW) |
| | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ |
| | BUILDING-PERMIT-FORMS |
| | FBC[B] = FBC BUILDING |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | |
| | 1) PLEASE PROVIDE RESUMES FOR THE INSPECTORS THAT ARE |
| | LISTED ON THE RESIDENT INSPECTORS AGREEMENT. |
| | KEITH LEBLANC |
| | SVEN JETZKEWITZ |
| | DOUGLAS ADAM SMITH |
| | THESE ARE TO SHOW EXPERIENCE IN THE TYPE OF INSPECTIONS |
| | BEING PERFORMED ON THIS PROJECT (WELDING AND BOLT |
| | INSPECTIONS AND TESTING) |
| | |
| | THESE CAN BE SENT VIA E-MAIL AND WILL BE APPROVED BY |
| | THE CHIEF BUILDING INSPECTOR. |
| | [email protected] |
| | IF BOLTING IS BEING USED AT THE STEEL JOISTS THAN |
| | PLEASE UPDATE THE RESIDENT AGREEMENT TO INCLUDE BOLTS |
| | AS WELL AS WELDED CONNECTIONS. |
| | |
| | 2) THESE DRAWINGS ARE PRODUCED BY AN ENGINEER AND |
| | ,WHILE THEY WERE ELCTRONICALLY SIGNED, THEY WILL NEED |
| | TO HAVE ORIGINAL SIGNATURE AND DATE BECAUSE THEY ARE |
| | PAPER COPIES. |
| | |
| | SUCH INSPECTORS SHALL BE ADEQUATELY PRESENT AT TIMES |
| | WORK IS UNDERWAY ON THE STRUCTURAL ELEMENTS OF THE |
| | BUILDING. SUCH INSPECTORS SHALL BE A REGISTERED |
| | ARCHITECT, OR ENGINEER, OR A PERSON LICENSED UNDER |
| | CHAPTER 468, PART XII, FLORIDA STATUTES. SUCH |
| | INSPECTORS SHALL SUBMIT WEEKLY PROGRESS REPORTS |
| | INCLUDING THE DAILY INSPECTIONS TO THE BUILDING |
| | OFFICIAL, AND INCLUDING A CODE COMPLIANCE OPINION OF |
| | THE RESIDENT INSPECTOR. AT THE COMPLETION OF THE |
| | CONSTRUCTION WORK OR PROJECT, SUCH INSPECTORS SHALL |
| | SUBMIT A CERTIFICATE OF COMPLIANCE TO THE BUILDING |
| | OFFICIAL, STATING THAT THE WORK WAS DONE IN COMPLIANCE |
| | WITH THIS CODE AND IN ACCORDANCE WITH THE PERMITTED |
| | DRAWING. FINAL INSPECTION SHALL BE MADE BY THE BUILDING |
| | OFFICIAL BEFORE A CERTIFICATE OF OCCUPANCY OR |
| | CERTIFICATE OF COMPLETION IS ISSUED; AND CONFIRMATION |
| | INSPECTIONS MAY BE MADE AT ANY TIME TO MONITOR |
| | ACTIVITIES AND RESIDENT INSPECTORS. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |