| Plan Review Stops For Permit 19110041 |
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
3 |
Status |
P |
Date |
2020-03-09 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-03-09 |
Time |
18:18 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-03-09 |
Time |
18:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
2 |
Status |
F |
Date |
2019-12-13 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-12-13 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-12-13 |
Time |
16:09 |
Sent To |
|
|
| Notes |
| 2019-12-13 16:09:31 | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | | | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | | [email protected]. THE INFORMATION SHOULD BE IN PDF | | | FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE | | | THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE. | | | | | | |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2019-11-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-11-12 |
Time |
07:34 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-11-12 |
Time |
07:34 |
Sent To |
|
|
| Notes |
| 2019-11-12 07:35:37 | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | | | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | | [email protected]. THE INFORMATION SHOULD BE IN PDF | | | FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE | | | THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2020-07-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-07-01 |
Time |
08:47 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-07-01 |
Time |
07:36 |
Sent To |
|
|
| Notes |
| 2020-07-01 08:47:58 | APPROVED WITH PROVISO | | | FBC 110.3.9 SPECIAL INSPECTOR DOCUMENTS FOR STRUCTURAL | | | WORK TO BE PROVIDED UNDER LANDLORD'S PERMIT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2020-04-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-04-08 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-04-07 |
Time |
18:10 |
Sent To |
|
|
| Notes |
| 2020-04-08 14:29:57 | PLAN | | | REVIEW COMMENTS | | | | | | 4TH REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | | | | 1) FBC 110.3.9 SPECIAL INSPECTOR DOCUMENTS FOR | | | STRUCTURAL WORK TO BE PROVIDED UNDER LANDLORD'S PERMIT. | | | THERE WERE NO SPECIAL INSPECTOR DOCUMENTS SUBMITTED FOR | | | THE STRUCTURAL WORK WITH THE LANDLORD'S PERMIT | | | #20030637. | | | | | | 2) THE INDEX SHEET G100 DOES NOT HAVE A DIGITAL | | | SIGNATURE. FS 471 | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2020-03-18 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-03-18 |
Time |
10:30 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-03-16 |
Time |
18:34 |
Sent To |
|
|
| Notes |
| 2020-03-18 09:31:08 | PLAN | | | REVIEW COMMENTS | | | | | | 3RD REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | | | | 1) THE PLANS FOR THIS PROJECT HAS NOTES INDICATING THAT | | | SOME OF THE WORK SHOWN IS THE RESPONSIBILITY OF THE | | | OWNER UNDER A SEPARATE PERMIT. THIS RAISES SOME | | | CONCERNS THAT WILL NEED TO BE ADDRESSED PRIOR TO | | | APPROVAL OF THIS PERMIT. | | | A) WILL THE SAME CONTRACTOR BE USED FOR BOTH THE | | | LANDLORD'S AND THE TENANT'S PROPOSED SCOPE OF WORK? | | | B) IF DIFFERENT CONTRACTORS ARE USED, WILL THE SCOPE OF | | | WORK FOR THE LANDLORD'S CONTRACTOR BE COMPLETED AND | | | FINAL-ED BEFORE THE TENANT'S CONTRACTOR STARTS THEIR | | | BUILDOUT? | | | B) IF THE WORK TWO DIFFERENT CONTRACTORS WILL BE | | | CONCURRENT, A LETTER OF UNDERSTANDING FROM THE LANDLORD | | | WILL BE REQUIRED. THE LETTER NEEDS TO CLEARLY INDICATE | | | THE SCOPE OF WORK TO BE PERFORMED BY EACH CONTRACTOR | | | AND WHO WILL BE RESPONSIBLE FOR RESOLVING ANY DISPUTES | | | THAT MAY ARISE. THE CITY/ BUILDING DEPARTMENT WILL NOT | | | BE RESPONSIBLE FOR RESOLVING CONTRACT DISPUTES. THE | | | LETTER SHALL BE SIGNED BY THE LANDLORD AND EACH OF THE | | | CONTRACTORS. | | | | | | 2) THE PLANS FOR THE PROPOSED WORK TO BE PERFORMED BY | | | THE LANDLORD'S CONTRACTOR NEEDS TO BE SUBMITTED FOR | | | COMPARISON WITH THE TENANTS PLANS, BEFORE THIS PERMIT | | | IS ISSUED. FBC 107.2.1.2 | | | | | | 3) FBC 107.3.4.1 DEFERRED SUBMITTAL. FBC 107.3.4 - | | | PROVIDE TWO SETS OF PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC 61G20-3.001 PER | | | FLORIDA STATUTE 553.842 (5) THAT HAVE BEEN REVIEWED AND | | | APPROVED IN WRITING BY THE DESIGNER OF RECORD. PROVIDE | | | TWO COMPLETE PRODUCT APPROVALS WITH FL OR NOA NUMBERS | | | INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN | | | PRESSURES FOR THE SKYLIGHT. | | | | | | 4) FBC 107.3.4.1 DEFERRED SUBMITTAL. SUBMIT SHOP | | | DRAWINGS FOR THE STAIRS FROM THE DELEGATE ENGINEER THAT | | | HAVE BEEN REVIEWED AND APPROVED BY THE DESIGNER OF | | | RECORD. FAC 61G15-30.003 ENGINEERING DOCUMENT | | | CLASSIFICATION. FL 61G-15-30.006 (3) THE DELEGATED | | | ENGINEER SHALL FORWARD THE DELEGATED ENGINEERING | | | DOCUMENTS TO THE ENGINEER OF RECORD FOR REVIEW. | | | | | | 5) FBC 110.3.9 SPECIAL INSPECTOR DOCUMENTS FOR | | | STRUCTURAL WORK TO BE PROVIDED UNDER LANDLORD'S PERMIT. | | | | | | 6) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A | | | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE | | | CITY RE-SUBMITTAL FORM. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2019-12-13 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-12-13 |
Time |
17:06 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-12-13 |
Time |
17:00 |
Sent To |
|
|
| Notes |
| 2019-12-13 17:06:11 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING - THE COMMENTS FROM THE FIRST REVIEW | | | WERE NOT ADDRESSED. | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE PLANS ARE REQUIRED TO BE APPROVED BY CITY PLACE | | | MANAGEMENT. THE CITY PLACE APPROVAL STAMP IS REQUIRED | | | TO BE ON THE DRAWINGS. | | | | | | 2) EXTERIOR SIGNS WILL REQUIRE A SEPARATE PERMIT. FBC | | | 105.1 | | | | | | 3) A SEPARATE ROOFING REPAIR PERMIT WILL BE REQUIRED TO | | | PATCH THE ROOF AT THE SKYLIGHT AND RELOCATED EQUIPMENT. | | | FBC 105.1 | | | | | | 4) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC | | | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE | | | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER | | | OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH | | | FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS | | | AND MAXIMUM DESIGN PRESSURES FOR THE SKYLIGHT. | | | | | | 5) PLEASE REVISE THE CODE INFORMATION ON THE | | | COVERSHEET. THE 2017 CHAPTER 1 AMENDMENTS SHOULD BE | | | REFERENCED AND NOT THE 2010. | | | | | | 6) THE OCCUPANT LOAD FACTOR FOR THE GROUND FLOOR SALES | | | AREA OF 30 GROSS IS INCORRECT. THE OCCUPANT LOAD FACTOR | | | FOR MERCANTILE IS 60 GROSS PER FBC 2017 TABLE 1004.1.2. | | | THIS WAS CHANGED FROM THE 2014 FBC. | | | | | | 7) THE ACCESSIBLE FITTING ROOM BENCH HEIGHT IS | | | SPECIFIED AS 1'-6" AFF ON SHEET A450 AND 1'-7" ON SHEET | | | A526. PLEASE COORDINATE. FBC 107.2.1 | | | | | | 8) ON SHEET A101, THERE IS A ROOM LABELED "VISUAL" WITH | | | ONE HOUR FIRE RATED WALLS AND A 60 MINUTE FIRE RATED | | | DOOR. PLEASE EXPLAIN THE USE OF THIS ROOM AND IDENTIFY | | | THE TYPE AND QUANTITIES OF ANY HAZARDOUS MATERIALS THAT | | | MAY BE PRESENT. FBC 107.2.1 AND 107.2.1.2 | | | | | | 9) THE LIFE SAFETY PLANS ARE NOT COMPLETE. THE LIFE | | | SAFETY PLANS NEED TO SHOW THE FOLLOWING: | | | A) NUMBER OF OCCUPANTS IN EACH AREA FBC 1004.1 | | | B) CUMULATIVE OCCUPANT LOADS FBC 1004.1.1 | | | C) EXIT SEPARATION DISTANCE FBC 1015.2.1 | | | D) COMMON PATH OF EGRESS TRAVEL DISTANCE FBC 1014.3 | | | E) EXIT ACCESS TRAVEL DISTANCE FBC 1016.3 | | | F) CLEAR WIDTH OF THE EXIT OR EXIT ACCESS DOORS FBC | | | 1008.1.1 | | | G) CAPACITY OF EGRESS DOORS, OCCUPANT LOAD SERVED AND | | | MEANS OF EGRESS FACTOR FBC1005.3.2 | | | H) DISTRIBUTION OF EGRESS CAPACITY FBC1005.5 | | | | | | 10) WELDED OR BOLTED CONNECTIONS | | | THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE | | | SPECIFICATIONS & WELDER OPERATOR PERFORMANCE | | | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED | | | STANDARDS AT TIME OF INSPECTION. | | | 2017 FBC-B 2204.1 WELDING | | | 2017 FBC-B 2204.2 BOLTING. | | | | | | 11) SUBMIT SHOP DRAWINGS FOR THE STAIRS FROM THE | | | DELEGATE ENGINEER THAT HAVE BEEN REVIEWED AND APPROVED | | | BY THE DESIGNER OF RECORD. FAC 61G15-30.003 ENGINEERING | | | DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE | | | DELEGATED ENGINEER SHALL FORWARD THE DELEGATED | | | ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR | | | REVIEW. | | | | | | 12) SUBMIT SHORING PLANS FOR THE OPENING FOR THE NEW | | | STAIRS THAT HAVE BEEN REVIEWED AND APPROVED BY THE | | | DESIGNER OF RECORD. FAC 61G15-30.003 ENGINEERING | | | DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE | | | DELEGATED ENGINEER SHALL FORWARD THE DELEGATED | | | ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR | | | REVIEW. | | | | | | 13) THE STRUCTURAL GENERAL NOTES ON SHEET S000 REQUIRE | | | A REGISTERED ENGINEER OR TEST AGENCY WITH EXPERIENCED | | | TECHNICIANS UNDER THE DIRECT SUPERVISION OF A | | | REGISTERED ENGINEER TO PERFORM THE DUTIES OF THE | | | SPECIAL INSPECTOR FOR THE STRUCTURAL INSPECTIONS. 2017 | | | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER | | | INSPECTIONS SERVICES. RESIDENT INSPECTOR. THE BUILDING | | | OFFICIAL MAY MAKE, OR CAUSE TO BE MADE BY OTHERS, THE | | | INSPECTIONS REQUIRED BY SECTION 109. HE/SHE MAY ACCEPT | | | REPORTS OF INSPECTORS OF RECOGNIZED INSPECTION | | | SERVICES, PROVIDED THAT AFTER INVESTIGATION HE/SHE IS | | | SATISFIED AS TO THEIR QUALIFICATIONS AND RELIABILITY. A | | | CERTIFICATE CALLED FOR BY ANY PROVISION OF THE | | | TECHNICAL CODES SHALL NOT BE BASED ON SUCH REPORTS | | | UNLESS THE SAME ARE IN WRITING AND CERTIFIED BY A | | | RESPONSIBLE OFFICER OF SUCH SERVICE. THE BUILDING | | | OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY AN INSPECTION | | | SERVICE IN THE FOLLOWING INSTANCES: | | | 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II | | | CONSTRUCTION | | | 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS | | | 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE | | | STRENGTH (F ?C) IN EXCESS OF 3000 | | | POUNDS PER SQUARE INCH | | | 4. FOR PILE DRIVING | | | 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE | | | FOOT | | | 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT | | | 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR | | | METHODS OF CONSTRUCTION | | | RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL PARTIES | | | NOTARIZED AND RETURNED TO THE BUILDING DEPARTMENT. FOR | | | THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME' OF | | | INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME' | | | MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED | | | HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL | | | REVIEW THE RESUME'. PLEASE CONTACT ME WITH AN EMAIL | | | ADDRESS AND I WILL BE HAPPY TO SEND YOU A COPY OF THE | | | OCTOBER 2018 GUIDELINES AND POLICIES FOR PROJECTS | | | CONCERNING THRESHOLD/SPECIAL INSPECTORS AND RESIDENT | | | INSPECTORS. | | | | | | 14) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A | | | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE | | | CITY RE-SUBMITTAL FORM. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-11-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-11-20 |
Time |
14:06 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-11-19 |
Time |
07:17 |
Sent To |
|
|
| Notes |
| 2019-11-20 11:34:58 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE PLANS ARE REQUIRED TO BE APPROVED BY CITY PLACE | | | MANAGEMENT. THE CITY PLACE APPROVAL STAMP IS REQUIRED | | | TO BE ON THE DRAWINGS. | | | | | | 2) EXTERIOR SIGNS WILL REQUIRE A SEPARATE PERMIT. FBC | | | 105.1 | | | | | | 3) A SEPARATE ROOFING REPAIR PERMIT WILL BE REQUIRED TO | | | PATCH THE ROOF AT THE SKYLIGHT AND RELOCATED EQUIPMENT. | | | FBC 105.1 | | | | | | 4) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC | | | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE | | | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER | | | OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH | | | FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS | | | AND MAXIMUM DESIGN PRESSURES FOR THE SKYLIGHT. | | | | | | 5) PLEASE REVISE THE CODE INFORMATION ON THE | | | COVERSHEET. THE 2017 CHAPTER 1 AMENDMENTS SHOULD BE | | | REFERENCED AND NOT THE 2010. | | | | | | 6) THE OCCUPANT LOAD FACTOR FOR THE GROUND FLOOR SALES | | | AREA OF 30 GROSS IS INCORRECT. THE OCCUPANT LOAD FACTOR | | | FOR MERCANTILE IS 60 GROSS PER FBC 2017 TABLE 1004.1.2. | | | THIS WAS CHANGED FROM THE 2014 FBC. | | | | | | 7) THE ACCESSIBLE FITTING ROOM BENCH HEIGHT IS | | | SPECIFIED AS 1'-6" AFF ON SHEET A450 AND 1'-7" ON SHEET | | | A526. PLEASE COORDINATE. FBC 107.2.1 | | | | | | 8) ON SHEET A101, THERE IS A ROOM LABELED "VISUAL" WITH | | | ONE HOUR FIRE RATED WALLS AND A 60 MINUTE FIRE RATED | | | DOOR. PLEASE EXPLAIN THE USE OF THIS ROOM AND IDENTIFY | | | THE TYPE AND QUANTITIES OF ANY HAZARDOUS MATERIALS THAT | | | MAY BE PRESENT. FBC 107.2.1 AND 107.2.1.2 | | | | | | 9) THE LIFE SAFETY PLANS ARE NOT COMPLETE. THE LIFE | | | SAFETY PLANS NEED TO SHOW THE FOLLOWING: | | | A) NUMBER OF OCCUPANTS IN EACH AREA FBC 1004.1 | | | B) CUMULATIVE OCCUPANT LOADS FBC 1004.1.1 | | | C) EXIT SEPARATION DISTANCE FBC 1015.2.1 | | | D) COMMON PATH OF EGRESS TRAVEL DISTANCE FBC 1014.3 | | | E) EXIT ACCESS TRAVEL DISTANCE FBC 1016.3 | | | F) CLEAR WIDTH OF THE EXIT OR EXIT ACCESS DOORS FBC | | | 1008.1.1 | | | G) CAPACITY OF EGRESS DOORS, OCCUPANT LOAD SERVED AND | | | MEANS OF EGRESS FACTOR FBC1005.3.2 | | | H) DISTRIBUTION OF EGRESS CAPACITY FBC1005.5 | | | | | | 10) WELDED OR BOLTED CONNECTIONS | | | THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE | | | SPECIFICATIONS & WELDER OPERATOR PERFORMANCE | | | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED | | | STANDARDS AT TIME OF INSPECTION. | | | 2017 FBC-B 2204.1 WELDING | | | 2017 FBC-B 2204.2 BOLTING. | | | | | | 11) SUBMIT SHOP DRAWINGS FOR THE STAIRS FROM THE | | | DELEGATE ENGINEER THAT HAVE BEEN REVIEWED AND APPROVED | | | BY THE DESIGNER OF RECORD. FAC 61G15-30.003 ENGINEERING | | | DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE | | | DELEGATED ENGINEER SHALL FORWARD THE DELEGATED | | | ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR | | | REVIEW. | | | | | | 12) SUBMIT SHORING PLANS FOR THE OPENING FOR THE NEW | | | STAIRS THAT HAVE BEEN REVIEWED AND APPROVED BY THE | | | DESIGNER OF RECORD. FAC 61G15-30.003 ENGINEERING | | | DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE | | | DELEGATED ENGINEER SHALL FORWARD THE DELEGATED | | | ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR | | | REVIEW. | | | | | | 13) THE STRUCTURAL GENERAL NOTES ON SHEET S000 REQUIRE | | | A REGISTERED ENGINEER OR TEST AGENCY WITH EXPERIENCED | | | TECHNICIANS UNDER THE DIRECT SUPERVISION OF A | | | REGISTERED ENGINEER TO PERFORM THE DUTIES OF THE | | | SPECIAL INSPECTOR FOR THE STRUCTURAL INSPECTIONS. 2017 | | | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER | | | INSPECTIONS SERVICES. RESIDENT INSPECTOR. THE BUILDING | | | OFFICIAL MAY MAKE, OR CAUSE TO BE MADE BY OTHERS, THE | | | INSPECTIONS REQUIRED BY SECTION 109. HE/SHE MAY ACCEPT | | | REPORTS OF INSPECTORS OF RECOGNIZED INSPECTION | | | SERVICES, PROVIDED THAT AFTER INVESTIGATION HE/SHE IS | | | SATISFIED AS TO THEIR QUALIFICATIONS AND RELIABILITY. A | | | CERTIFICATE CALLED FOR BY ANY PROVISION OF THE | | | TECHNICAL CODES SHALL NOT BE BASED ON SUCH REPORTS | | | UNLESS THE SAME ARE IN WRITING AND CERTIFIED BY A | | | RESPONSIBLE OFFICER OF SUCH SERVICE. THE BUILDING | | | OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY AN INSPECTION | | | SERVICE IN THE FOLLOWING INSTANCES: | | | 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II | | | CONSTRUCTION | | | 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS | | | 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE | | | STRENGTH (F ?C) IN EXCESS OF 3000 | | | POUNDS PER SQUARE INCH | | | 4. FOR PILE DRIVING | | | 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE | | | FOOT | | | 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT | | | 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR | | | METHODS OF CONSTRUCTION | | | RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL PARTIES | | | NOTARIZED AND RETURNED TO THE BUILDING DEPARTMENT. FOR | | | THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME' OF | | | INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME' | | | MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED | | | HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL | | | REVIEW THE RESUME'. PLEASE CONTACT ME WITH AN EMAIL | | | ADDRESS AND I WILL BE HAPPY TO SEND YOU A COPY OF THE | | | OCTOBER 2018 GUIDELINES AND POLICIES FOR PROJECTS | | | CONCERNING THRESHOLD/SPECIAL INSPECTORS AND RESIDENT | | | INSPECTORS. | | | | | | 14) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A | | | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE | | | CITY RE-SUBMITTAL FORM. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2020-06-30 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-06-30 |
Time |
09:32 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-06-25 |
Time |
12:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2020-03-17 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-03-17 |
Time |
12:48 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-03-09 |
Time |
12:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2019-11-18 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-11-18 |
Time |
08:26 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-11-18 |
Time |
08:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2020-06-19 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2020-06-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2020-06-19 |
Time |
10:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2020-03-25 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2020-03-25 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2020-03-25 |
Time |
09:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2020-03-10 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2020-03-10 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2020-03-10 |
Time |
12:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2019-11-27 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-11-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-11-27 |
Time |
10:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2019-11-20 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-11-20 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-11-18 |
Time |
10:17 |
Sent To |
|
|
| Notes |
| 2019-11-20 11:14:42 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) SHEET G 100 - THERE ARE NO INDICATIONS OF REVIEW OR | | | COMPLIANCE WITH THE FLORIDA FIRE PREVENTION CODE. | | | | | | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE | | | 6TH EDITION OF FLORIDA FIRE PREVENTION CODE WHICH | | | INCLUDES THE 2015 EDITION OF NFPA 1 AND NFPA 101. | | | | | | THE BELOW LIST ARE THE MOST COMMON REFERENCED CODES: | | | | | | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS | | | OF NFPA 13, 2013 EDITION. | | | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF | | | NFPA 72, 2013 EDITION. | | | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF | | | NFPA 241, 2013 EDITION. | | | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS | | | OF NFPA 10, 2013 EDITION. | | | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2014 EDITION. | | | | | | PLEASE REVIEW AND ENSURE COMPLIANCE AS THESE ARE WHAT | | | THE PROJECT WILL BE INSPECTED WITH. | | | | | | | | | | | | 2) SHEET FA 100 - THE PROPOSED FIRE ALARM SHALL BE | | | INSTALLED UNDER SEPARATE SUBMITTED PERMIT AND SHOP | | | DRAWINGS BY CERTIFIED FA CONTRACTOR. | | | | | | PLEASE ENSURE COMPLIANCE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2020-07-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-07-06 |
Time |
13:41 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-06-18 |
Time |
10:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2020-04-15 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2020-04-15 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-03-24 |
Time |
13:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2020-03-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-03-23 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-03-06 |
Time |
08:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-12-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-12-17 |
Time |
19:23 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-11-25 |
Time |
10:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-11-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-11-20 |
Time |
14:06 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-11-05 |
Time |
13:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
N |
Date |
2020-03-09 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-03-09 |
Time |
18:17 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-03-09 |
Time |
18:17 |
Sent To |
|
|
| Notes |
| 2020-03-09 18:17:44 | SPOKE WITH MICHELLE BONNANI ON ANOTHER PROJECT; CHANGE | | | OF OCCUPANCY FROM ASSEMBLY TO MERCANTILE AT CITY PLACE | | | DOES NOT REQUIRE IMPACT FEES | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2019-11-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-11-19 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-11-19 |
Time |
07:17 |
Sent To |
|
|
| Notes |
| 2019-11-19 11:05:26 | THE SECOND FLOOR IS A CHANGE OF OCCUPANCY FROM AN | | | ASSEMBLY ( BAR/RESTAURANT) TO A MERCANTILE. THE PLANS | | | WILL NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR | | | IMPACT FEES. PLANS WILL BE REVIEWED BY THE PBC IMPACT | | | FEE OFFICE DIGITALLY VIA PROJECTDOX UPON NOTIFICATION | | | BY THIS OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE | | | NEAREST FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT | | | FEE OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE | | | MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT | | | AND NAME THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. | | | THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZ | | | B/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE | | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] . |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2020-06-24 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-06-24 |
Time |
14:44 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-06-24 |
Time |
14:39 |
Sent To |
|
|
| Notes |
| 2020-06-24 14:43:59 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | MECHANICAL REVIEW APPROVED WITH PROVISO: | | | | | | SEPARATE PERMIT BY LANDLORD REQUIRED FOR THE FAN COIL | | | UNITS. | | | CCOLE? 3/16/20 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2020-03-16 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-03-16 |
Time |
10:26 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2020-03-16 |
Time |
07:55 |
Sent To |
|
|
| Notes |
| 2020-03-16 10:27:54 | MECHANICAL PROVISO: | | | | | | SEPARATE PERMIT BY LANDLORD REQUIRED FOR THE FAN COIL | | | UNITS. | | | CCOLE- 3/16/20 | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2019-12-06 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-12-06 |
Time |
11:20 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-12-06 |
Time |
09:16 |
Sent To |
|
|
| Notes |
| 2019-12-06 11:24:27 | 2ND REVIEW FBC-2017 MECHANICAL | | | PERMIT #19110041 | | | 12/6/19 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | IT APPEARS THAT NO CORRECTIONS OR CHANGES TO THE PLAN | | | HAVE BEEN MADE BASED ON THE FIRST REVIEW COMMENTS | | | PRINTED BELOW- PLEASE COMPLY. | | | | | | 1) THE PLANS INDICATE THE NEW FCU'S UNDER A SEPARATE | | | PERMIT, HOWEVER CURRENTLY THERE IS NO PERMIT APPLIED | | | FOR, OR ISSUED FOR THE UNITS. PLEASE PROVIDE MORE | | | INFORMATION, AND NOTE THAT SIZING CALCULATIONS MAY BE | | | REQUIRED UNDER THIS PERMIT AND AN INCREASE IN VALUE FOR | | | THE COST OF THE UNITS- SECTION 107.2.1 & 109.3 WPB. | | | | | | 2) SHEET M101: EXHAUST VENTILATION AT A RATE OF 0.25 | | | CFMS PER SF. IS REQUIRED FOR THE FITTING ROOMS PER | | | TABLE 403.3.1.1 FBC M. PLEASE REVISE THE PLANS | | | ACCORDINGLY. | | | | | | 3) M101: THE CORRIDOR (HALLWAY) CANNOT BE USED TO | | | RETURN AIR FROM THE ROOMS TO THE MECHANICAL ROOM- | | | SECTION 601.2 FBC M. | | | | | | 4) M101: CLARIFY THE NEED FOR THE EXHAUST FANS EF-1 & 2 | | | IN THE VISUAL AND OFFICE ROOMS. PROVIDE FAN SIZING | | | CALCULATIONS AND THE SEQUENCES OF OPERATION- SECTION | | | 107.2.1 WPB. | | | | | | 5) M300: THE ROOF MOUNTED FAN DETAIL IS INCOMPLETE. | | | INDICATE HOW THE CURB WILL BE ATACHED TO THE STRUCTURE, | | | AND THE FAN ATTACHED TO THE CURB. WHICH TYPE OF ANCHORS | | | AND FASTENERS WILL BE USED- SECTION 301.15 FBC M. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2019-11-18 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-11-18 |
Time |
16:12 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-11-18 |
Time |
13:41 |
Sent To |
|
|
| Notes |
| 2019-11-18 16:48:24 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #19110041 | | | 11/18/19 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE PLANS INDICATE THE NEW FCU'S UNDER A SEPARATE | | | PERMIT, HOWEVER CURRENTLY THERE IS NO PERMIT APPLIED | | | FOR, OR ISSUED FOR THE UNITS. PLEASE PROVIDE MORE | | | INFORMATION, AND NOTE THAT SIZING CALCULATIONS MAY BE | | | REQUIRED UNDER THIS PERMIT AND AN INCREASE IN VALUE FOR | | | THE COST OF THE UNITS- SECTION 107.2.1 & 109.3 WPB. | | | | | | 2) SHEET M101: EXHAUST VENTILATION AT A RATE OF 0.25 | | | CFMS PER SF. IS REQUIRED FOR THE FITTING ROOMS PER | | | TABLE 403.3.1.1 FBC M. PLEASE REVISE THE PLANS | | | ACCORDINGLY. | | | | | | 3) M101: THE CORRIDOR (HALLWAY) CANNOT BE USED TO | | | RETURN AIR FROM THE ROOMS TO THE MECHANICAL ROOM- | | | SECTION 601.2 FBC M. | | | | | | 4) M101: CLARIFY THE NEED FOR THE EXHAUST FANS EF-1 & 2 | | | IN THE VISUAL AND OFFICE ROOMS. PROVIDE FAN SIZING | | | CALCULATIONS AND THE SEQUENCES OF OPERATION- SECTION | | | 107.2.1 WPB. | | | | | | 5) M300: THE ROOF MOUNTED FAN DETAIL IS INCOMPLETE. | | | INDICATE HOW THE CURB WILL BE ATACHED TO THE STRUCTURE, | | | AND THE FAN ATTACHED TO THE CURB. WHICH TYPE OF ANCHORS | | | AND FASTENERS WILL BE USED- SECTION 301.15 FBC M. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2020-03-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-03-23 |
Time |
10:26 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-03-23 |
Time |
08:15 |
Sent To |
|
|
| Notes |
| 2020-03-23 10:26:51 | OK PER JAMES BAKER, PE | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2019-12-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-12-17 |
Time |
19:22 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-12-16 |
Time |
17:07 |
Sent To |
|
|
| Notes |
| 2019-12-17 19:23:05 | 2ND PLUMBING REVIEW**DENIED** COMMENTS FROM 1ST REVIEW | | | HAVE NOT BEEN ADDRESSED. FAILURE TO FULLY COMPLY ON THE | | | NEXT SUBMITTAL COULD LEAD TO A 4X PLAN REVIEW FEE. | | | 553.80 (B)?WITH RESPECT TO EVALUATION OF DESIGN | | | PROFESSIONALS? DOCUMENTS, IF A LOCAL GOVERNMENT FINDS | | | IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE | | | FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT | | | DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE | | | TIMES FOR FAILURE TO CORRECT A CODE VIOLATION | | | SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION, | | | INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION, | | | STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING, | | | VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS | | | SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF | | | THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO | | | CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH | | | TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED | | | FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT | | | OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS | | | REVIEW. | | | | | | 1) SHOW ELEVATOR SUMP PUMP AND DISCHARGE CHARGE PIPING. | | | FBC 107.3.5 | | | 2) SHT. G100 LIST THE AMENDMENTS YEAR AS 2010. PLEASE | | | CORRECT AND LIST 2017. FBC 107.2.1 | | | 3) SHOW BREAK ROOM SINK AS HAVING CLEAR FLOOR SPACE | | | MATCHING ALL SHEETS THAT SHOW TOILET ROOM CLEAR FLOOR | | | SPACE. FBC 107.3.5 | | | 4) SHOW SEPARATE CLEAR FLOOR SPACE OUTSIDE THE ARC OF | | | THE DOOR SWING AS REQUIRED IN FBC-ACC 603.2.3 | | | 5) SHT. A-555 SHOW THE REAR GRAB BAR AS MOUNTING 12? | | | FROM THE CENTER OF TOILET OVER TOWARDS THE SIDE WALL. | | | FBC-ACC 604.5.2 | | | 6) SHOW HOT WATER RETURN LINE AS IT APPEARS THE | | | DISTANCE EXCEEDS THE MAX ALLOWED FROM THE SOURCE OF HOT | | | WATER. FBC-ENERGY C404.5.1, FBC-PLB 607.2 | | | 7) CALL OUT MIN ALLOWED PIPE INSULATIONS IS 1? WALL. | | | SHT. P400 CALLS OUT ALL PIPING 2? AND UNDER MIN 1? | | | WALL. SEE TABLE C403.2.10 FBC 107.2.1 | | | 8) SHT.P-200 DETAIL (D) CALLS OUT WATER HEATER IS POINT | | | OF USE BUT SHOW TANK TYPE. PLEASE CLARIFY. FBC-107.2 | | | 9) PROVIDE WATER HEATER INSTALLATION MANUAL SHOW IT | | | COMPLIES WITH MIN ENERGY REQUIREMENTS. FBC-ENERGY | | | C404.2 | | | TIM HUNT | | | PLUMBING PLAN EXAMINER | | | CITY OF WEST PALM BEACH ( CGA SOLUTIONS) | | | [email protected] | | | 561-248-2703 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2019-11-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-11-12 |
Time |
07:18 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-11-07 |
Time |
08:02 |
Sent To |
|
|
| Notes |
| 2019-11-12 07:18:54 | 1ST PLUMBING REVIEW**DENIED** | | | | | | 1) SHOW ELEVATOR SUMP PUMP AND DISCHARGE CHARGE PIPING. | | | FBC 107.3.5 | | | 2) SHT. G100 LIST THE AMENDMENTS YEAR AS 2010. PLEASE | | | CORRECT AND LIST 2017. FBC 107.2.1 | | | 3) SHOW BREAK ROOM SINK AS HAVING CLEAR FLOOR SPACE | | | MATCHING ALL SHEETS THAT SHOW TOILET ROOM CLEAR FLOOR | | | SPACE. FBC 107.3.5 | | | 4) SHOW SEPARATE CLEAR FLOOR SPACE OUTSIDE THE ARC OF | | | THE DOOR SWING AS REQUIRED IN FBC-ACC 603.2.3 | | | 5) SHT. A-555 SHOW THE REAR GRAB BAR AS MOUNTING 12? | | | FROM THE CENTER OF TOILET OVER TOWARDS THE SIDE WALL. | | | FBC-ACC 604.5.2 | | | 6) SHOW HOT WATER RETURN LINE AS IT APPEARS THE | | | DISTANCE EXCEEDS THE MAX ALLOWED FROM THE SOURCE OF HOT | | | WATER. FBC-ENERGY C404.5.1, FBC-PLB 607.2 | | | 7) CALL OUT MIN ALLOWED PIPE INSULATIONS IS 1? WALL. | | | FBC 107.2.1 | | | 8) SHT.P-200 DETAIL (D) CALLS OUT WATER HEATER IS POINT | | | OF USE BUT SHOW TANK TYPE. PLEASE CLARIFY. FBC-107.2 | | | 9) PROVIDE WATER HEATER INSTALLATION MANUAL SHOW IT | | | COMPLIES WITH MIN ENERGY REQUIREMENTS. FBC-ENERGY | | | C404.2 | | | TIM HUNT | | | PLUMBING PLAN EXAMINER | | | CITY OF WEST PALM BEACH ( CGA SOLUTIONS) | | | [email protected] | | | 561-248-2703 | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
5 |
Status |
P |
Date |
2020-07-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-07-01 |
Time |
08:40 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-07-01 |
Time |
08:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
F |
Date |
2020-04-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-04-08 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-04-08 |
Time |
14:30 |
Sent To |
|
|
| Notes |
| 2020-04-08 14:31:21 | SHEET G100 VERSION 3 HAS NOT BEEN DIGITALLY SEALED. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2020-03-21 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-03-21 |
Time |
12:00 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-03-21 |
Time |
12:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2019-12-13 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-12-13 |
Time |
16:11 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-12-13 |
Time |
16:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2019-11-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-11-12 |
Time |
07:34 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-11-12 |
Time |
07:34 |
Sent To |
|
|
| Notes |
| 2019-11-12 07:34:38 | ADVISED K.HERBERT, PE VIA EMAIL THAT SELF CERTIFYING | | | SIGNATURE NOT PERMITTED (MECHANICAL); OBTAIN 3RD PARTY | | | SIGNATURE FOR FUTURE PROJECTS, THIS COMMENT DOES NOT | | | AFFECT THIS PERMIT | | | | | | | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
P |
Date |
2020-06-30 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2020-06-30 |
Time |
13:20 |
Rev Time |
1.00 |
| Received By |
eschneid |
Date |
2020-06-30 |
Time |
11:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
F |
Date |
2020-04-15 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2020-04-15 |
Time |
10:00 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2020-04-14 |
Time |
16:24 |
Sent To |
|
|
| Notes |
| 2020-04-15 10:00:55 | FAILED | | | | | | PROVIDE WRITTEN RESPONSES TO COMMENTS. | | | | | | 1) REPEAT COMMENT: ALL EXTERIOR SIGNAGE NEEDS TO BE | | | REMOVED FROM SHEETS A200 AND A201. NOTE: EXTERIOR | | | SIGNAGE REQUIRES A SEPARATE PERMIT AND IS NOT REVIEWED | | | AS PART OF THE INTERIOR BUILD OUT PERMIT. THESE SHEETS | | | HAVE NOT BEEN REMOVED AS STATED IN THE COMMENT | | | RESPONSE. | | | | | | 2) UPDATED COMMENT: THE 2ND LEVEL FLOOR PLAN INDICATES | | | THAT THE EXTERIOR WALLS AT THE CORNER OF THE BAY, WHERE | | | THE FITTING ROOMS ARE PROPOSED) ARE EXISTING SOLID | | | WALLS (EXISTING STUCCO SURFACE FACADE ON SHEETS A200 | | | AND A201). THIS IS NOT ACCURATE. CONTRARY TO THE | | | COMMENT RESPONSE, SHEETS A200 AND A201 HAVE NOT BEEN | | | REMOVED. WHILE THE LANDLORD HAS SUBMITTED PERMIT | | | 20030637 FOR EXTERIOR WORK, ZONING STAFF HAS NOT | | | APPROVED THE PERMIT. ONE ISSUE IS THE PROPOSED BLOCKING | | | IN THE GLAZING AT THE CORNER OF THIS IMPORTANT SPACE. | | | THIS CORNER NEEDS TO REMAIN WITH GLAZING. IF YOU MUST | | | LOCATE THE FITTING ROOMS IN THIS LOCATION, WHICH SEEMS | | | THAT IT WOULD BE BETTER SERVED TO HAVE VIEW INTO THE | | | STORE, THEN SET THE FITTING ROOM BACK SO THAT THAT | | | THERE CAN BE MERCHANDISE DISPLAYED BETWEEN STOREFRONT | | | GLAZING AND THE REAR OF THE FITTING ROOMS. LIFESTYLE | | | IMAGERY CAN THEN BE INSTALLED ON THE BACK OF THE | | | FITTING ROOMS WALLS. | | | | | | 3) NEW COMMENT: THE RESPONSE COMMENTS STATE THAT THERE | | | IS NO FACADE/EXTERIOR STOREFRONT WORK ASSOCIATED WITH | | | THIS INTERIOR BUILD OUT PERMIT. THE SECOND FLOOR | | | EXTERIOR INCLUDED AS A BASE FOR THIS PERMIT DOES NOT | | | MATCH WHAT IS SHOWN ON THE LANDLORD EXTERIOR WORK | | | PERMIT. THIS INCLUDES THE ENTRY DOOR LOCATION (NORTH | | | VS. WEST FACADE) AND THE PROPOSED SOLID WALL INFILL | | | (NOT APPROVED BY ZONING - SEE COMMENT 2). UNLESS YOU | | | ARE GOING TO CHANGE WHAT THE LANDLORD IS INSTALLING, | | | ALL THE PLANS NEED TO SHOW THE EXTERIOR MATCHING WHAT | | | THE FINAL APPROVED PERMIT FOR THE LANDLORD WORK SHOWS. | | | IF YOU ARE CHANGING WHAT IS APPROVED FOR THE LANDLORD, | | | THEN YOU WILL NEED TO INCLUDE THE DETAILS FOR THE NEW | | | EXTERIOR DEMOLITION AND CONSTRUCTION WITH THIS PERMIT. | | | | | | 4) UPDATED REPEAT COMMENT: SHEETS M101 AND M201 | | | SPECIFICALLY CALL OUT THE INSTALLATION OF NEW EXHAUST | | | FANS TO BE INSTALLED ON THE ROOF WITH THIS PERMIT. THE | | | LANDLORD IS NOT INSTALLING ROOFTOP EQUIPMENT AS PART OF | | | PERMIT 20030637 OR ANY OTHER PERMIT. IN ACCORDANCE WITH | | | THE CITYPLACE DRI, PLEASE PROVIDE VERIFICATION THAT THE | | | NEW EXHAUST FANS (NEW ROOFTOP MECHANICAL EQUIPMENT), | | | ARE SCREENED FROM PUBLIC VIEW THROUGH ANY COMBINATION | | | OF LANDSCAPING, WALLS AND EQUIPMENT LOCATION. | | | VERIFICATION CAN BE PROVIDED BY PLANS OR OTHER EVIDENCE | | | THAT THE NEW ROOFTOP MECHANICAL EQUIPMENT WILL BE | | | SCREENED FROM PUBLIC VIEW. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2020-03-13 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2020-03-13 |
Time |
11:40 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2020-03-13 |
Time |
10:57 |
Sent To |
|
|
| Notes |
| 2020-03-13 11:41:05 | FAILED | | | | | | PROVIDE WRITTEN RESPONSES TO COMMENTS. | | | | | | 1) ALL SIGNAGE NEEDS TO BE REMOVED FROM SHEETS A200 AND | | | A201. | | | | | | 2) REPEAT COMMENT: THE 2ND LEVEL FLOOR PLAN INDICATES | | | THAT THE EXTERIOR WALLS AT THE CORNER OF THE BAY, WHERE | | | THE FITTING ROOMS ARE PROPOSED) ARE EXISTING SOLID | | | WALLS (EXISTING STUCCO SURFACE FACADE ON SHEETS A200 | | | AND A201). THIS IS NOT ACCURATE. THE OPENINGS HAVE A | | | KNEE WALL WITH STOREFRONT GLAZING. THE EXISTING | | | OPENINGS MAY NOT BE FILLED IN, BLACKED OUT OR OTHERWISE | | | HAVE CONSTRUCTION TO OBSTRUCT THE VIEW INTO THE STORE. | | | ---- THE STOREFRONT ELEVATIONS ON SHEETS A200 AND A201 | | | CONTINUE TO SHOW INACCURATE CONDITIONS. THERE IS NO | | | PERMIT TO CLOSE IN THE EXISTING STOREFRONT ON WHERE THE | | | CHANGING ROOMS ARE PROPOSED. YOU MAY NOT SHOW | | | INACCURATE PLANS AND THEN SAY THAT IT IS NOT PART OF | | | YOUR SCOPE OF WORK. | | | | | | 3) REPEAT COMMENT: IT APPEARS THAT THERE IS NEW | | | EQUIPMENT BEING INSTALLED ON THE ROOF. IN ACCORDANCE | | | WITH THE CITYPLACE DRI, PLEASE PROVIDE VERIFICATION | | | THAT ALL ROOFTOP MECHANICAL EQUIPMENT, INCLUDING BUT | | | NOT LIMITED TO SUCH ITEMS AS PUBLIC AND PRIVATE UTILITY | | | SERVICE CONNECTIONS; HEATING, VENTILATING, AND AIR | | | CONDITIONING SYSTEMS; COMMUNICATIONS DEVICES; AND | | | RELATED EQUIPMENT, SHALL BE SCREENED FROM PUBLIC VIEW | | | THROUGH ANY COMBINATION OF LANDSCAPING, WALLS AND | | | EQUIPMENT LOCATION. PLEASE PROVIDE PLANS OR OTHER | | | EVIDENCE THAT THE NEW ROOFTOP MECHANICAL EQUIPMENT WILL | | | BE SCREENED FROM PUBLIC VIEW. ---- THE RESPONSE LETTER | | | MENTIONS SEPARATE PERMITS FOR THE ROOFTOP EQUIPMENT, | | | YET STAFF HAS FOUND NO EVIDENCE OF A SEPARATE PERMIT; | | | THEREFORE, YOU NEED TO PROVIDE THE DRAWINGS TO VERIFY | | | THAT THE EQUIPMENT MEETS THE SCREENING REQUIREMENTS. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2019-12-09 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2019-12-09 |
Time |
14:01 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2019-12-09 |
Time |
11:52 |
Sent To |
|
|
| Notes |
| 2019-12-09 14:03:04 | FAILED | | | | | | PROVIDE WRITTEN RESPONSES TO COMMENTS. | | | | | | 1) REPEAT COMMENT: THE PLANS ARE EITHER REQUIRED TO | | | HAVE THE CITYPLACE RETAIL, LLC, APPROVAL STAMP ON THEM, | | | OR YOU MUST PROVIDE A SEPARATE LETTER FROM CITYPLACE | | | RETAIL, LLC, APPROVING THE SPECIFIC PLANS THAT YOU HAVE | | | SUBMITTED. | | | | | | 2) REPEAT COMMENT: SIGNAGE REQUIRES SEPARATE PERMIT | | | WITH PLANS. NOTE: THE SIGNS DO NOT APPEAR TO CONFORM TO | | | THE ROSEMARY SQUARE MASTER SIGN PLAN. | | | | | | 3) REPEAT COMMENT: THE 2ND LEVEL FLOOR PLAN INDICATE | | | THAT THE EXTERIOR WALLS AT THE CORNER OF THE BAY, WHERE | | | THE FITTING ROOMS ARE PROPOSED) ARE EXISTING SOLID | | | WALLS (EXISTING STUCCO SURFACE FACADE ON SHEETS A200 | | | AND A201). THIS IS NOT ACCURATE. THE OPENINGS HAVE A | | | KNEE WALL WITH STOREFRONT GLAZING. THE EXISTING | | | OPENINGS MAY NOT BE FILLED IN, BLACKED OUT OR OTHERWISE | | | HAVE CONSTRUCTION TO OBSTRUCT THE VIEW INTO THE STORE. | | | | | | 4) REPEAT COMMENT: IT APPEARS THAT THERE IS NEW | | | EQUIPMENT BEING INSTALLED ON THE ROOF. IN ACCORDANCE | | | WITH THE CITYPLACE DRI, PLEASE PROVIDE VERIFICATION | | | THAT ALL ROOFTOP MECHANICAL EQUIPMENT, INCLUDING BUT | | | NOT LIMITED TO SUCH ITEMS AS PUBLIC AND PRIVATE UTILITY | | | SERVICE CONNECTIONS; HEATING, VENTILATING, AND AIR | | | CONDITIONING SYSTEMS; COMMUNICATIONS DEVICES; AND | | | RELATED EQUIPMENT, SHALL BE SCREENED FROM PUBLIC VIEW | | | THROUGH ANY COMBINATION OF LANDSCAPING, WALLS AND | | | EQUIPMENT LOCATION. PLEASE PROVIDE PLANS OR OTHER | | | EVIDENCE THAT THE NEW ROOFTOP MECHANICAL EQUIPMENT WILL | | | BE SCREENED FROM PUBLIC VIEW. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2019-11-18 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2019-11-18 |
Time |
14:34 |
Rev Time |
0.75 |
| Received By |
eschneid |
Date |
2019-11-08 |
Time |
09:26 |
Sent To |
|
|
| Notes |
| 2019-11-18 14:37:33 | FAILED | | | | | | 1) THE PLANS ARE EITHER REQUIRED TO HAVE THE CITYPLACE | | | RETAIL, LLC, APPROVAL STAMP ON THEM, OR YOU MUST | | | PROVIDE A SEPARATE LETTER FROM CITYPLACE RETAIL, LLC, | | | APPROVING THE SPECIFIC PLANS THAT YOU HAVE SUBMITTED. | | | | | | 2) SIGNAGE REQUIRES SEPARATE PERMIT WITH PLANS. NOTE: | | | THE SIGNS DO NOT APPEAR TO CONFORM TO THE ROSEMARY | | | SQUARE MASTER SIGN PLAN. | | | | | | 3) THE 2ND LEVEL FLOOR PLAN INDICATE THAT THE EXTERIOR | | | WALLS AT THE CORNER OF THE BAY, WHERE THE FITTING ROOMS | | | ARE PROPOSED) ARE EXISTING SOLID WALLS (EXISTING STUCCO | | | SURFACE FA?ADE ON SHEETS A200 AND A201). THIS IS NOT | | | ACCURATE. THE OPENINGS HAVE A KNEE WALL WITH STOREFRONT | | | GLAZING. THE EXISTING OPENINGS MAY NOT BE FILLED IN, | | | BLACKED OUT OR OTHERWISE HAVE CONSTRUCTION TO OBSTRUCT | | | THE VIEW INTO THE STORE. | | | | | | 4) IT APPEARS THAT THERE IS NEW EQUIPMENT BEING | | | INSTALLED ON THE ROOF. IN ACCORDANCE WITH THE CITYPLACE | | | DRI, PLEASE PROVIDE VERIFICATION THAT ALL ROOFTOP | | | MECHANICAL EQUIPMENT, INCLUDING BUT NOT LIMITED TO SUCH | | | ITEMS AS PUBLIC AND PRIVATE UTILITY SERVICE | | | CONNECTIONS; HEATING, VENTILATING, AND AIR CONDITIONING | | | SYSTEMS; COMMUNICATIONS DEVICES; AND RELATED EQUIPMENT, | | | SHALL BE SCREENED FROM PUBLIC VIEW THROUGH ANY | | | COMBINATION OF LANDSCAPING, WALLS AND EQUIPMENT | | | LOCATION. PLEASE PROVIDE PLANS OR OTHER EVIDENCE THAT | | | THE NEW ROOFTOP MECHANICAL EQUIPMENT WILL BE SCREENED | | | FROM PUBLIC VIEW. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | | [email protected] | | | |
|
|