| 2019-11-14 14:01:08 | 1. PER FLORIDA ADMINISTRATIVE CODE SECTION |
| | 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS |
| | SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER |
| | SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE |
| | TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR |
| | EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN |
| | DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT |
| | FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION |
| | SUCH AS PRE-ENGINEERED SYSTEMS. |
| | 2. A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE |
| | COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION |
| | SUBMITTED ON THE PLANS. THIS PLAN DOES NOT INCLUDE ANY |
| | INFORMATION PERTAINING TO THE FIRE SPRINKLER SYSTEM |
| | WHICH IT REFERENCES, AND IN FACT SHOULD BE ATTACHED |
| | WITH THE MASTER PLANS AND PERMIT. ADDITIONAL PLAN |
| | REVIEW COMMENTS MAY BE GENERATED DURING PLAN |
| | RESUBMISSION. |
| | 3.ENGINEERED FIRE ALARM AND FIRE SPRINKLER CONSTRUCTION |
| | DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT. |
| | AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE |
| | SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS |
| | (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS) |
| | FOR A SUB-PERMIT. IF THE FIRE SPRINKLER DRAWINGS ARE |
| | CREATED BY AN ENGINEER DIFFERING FROM WHO SIGNED THE |
| | MASTER DRAWINGS, NOTIFICATION SHOULD BE PROVIDED IN THE |
| | SUBMITTAL PACKET AS TO WHICH ENGINEER IS DEFERING TO |
| | WHOM. |
| | |