Plan Review Details - Permit 19101628
Plan Review Stops For Permit 19101628
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-11-18 Cont ID  
Sent By jpearson Date 2019-11-18 Time 14:53 Rev Time 0.00
Received By jpearson Date 2019-11-18 Time 14:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-11-05 Cont ID  
Sent By jpearson Date 2019-11-05 Time 10:24 Rev Time 0.00
Received By jpearson Date 2019-11-05 Time 10:24 Sent To I
Notes
2019-11-05 10:24:34CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE ORIGINAL PLAN SUBMISSIONS FOR THIS PERMIT WERE
 IN DIGITAL FORMAT. FOR RECORD KEEPING PURPOSES, ANY
 REVISION SUBMITTED MUST ALSO BE IN DIGITAL FORMAT.
 PROVIDE CORRECTION. WPB FBC 107.1
 2. THE PANEL SCHEDULE FOR PANEL B STATES THAT THERE IS
 A 150 AMP MAIN BREAKER IN THIS PANEL. THE RISER DIAGRAM
 SHOWS A 200 AMP BREAKER ON 1/0 WIRE. CORRECT
 DISCREPANCIES. WPB FBC 107.2.1; NEC 240.4,
 310.15(B)(16)
 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC
 RE E3606.3
 4. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 5. RISER SHOWS PANEL HP AS EXISTING. AS THERE WAS A 125
 AMP PANEL THERE PREVIOUSLY, THIS WOULD BE A NEW PANEL.
 PROVIDE CORRECTION. WPB FBC 107.2.1
 6. PROVIDE RISER DIAGRAM OF LANDLORD SERVICE INDICATING
 SIZE. NEC 215.5
 7. PROVIDE ACCURATE LOAD CALCULATION FOR LANDLORD
 SERVICE, INCLUDE EXISTING AND NEW LOADS TO CONFIRM
 CAPACITY OF SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30
 8. RISER DIAGRAM SHOWS PANEL C AS A 100 AMP MAIN
 BREAKER PANEL. THE PANEL SCHEDULE SHOWS THAT THIS IS A
 125 AMP MAIN BREAKER PANEL. THERE IS NOT INDICATION OF
 WIRE SIZE ON THE RISER DIAGRAM. PROVIDE CLARIFICATIONS
 AND CORRECTIONS AS NEEDED. WPB FBC 107.2.1; NEC 215.5;
 240.4, 310.15(B)(16)
 9. PROVIDE CORRECTED LOAD CALCULATION FOR TRANSFORMER
 TLPC INCLUDING ALL LOADS CONNECTED. NEC 110.3, 220
 10. PROVIDE REVISED FLOOR PLAN SHOWING LOCATION OF
 PANEL C. WPB FBC 107.2.1
 11. PROVIDE GFCI PROTECTION FOR RECEPTACLE OUTLETS
 LOCATED WITHIN 6 FEET OF SINK. NEC 210.8
 12. PROVIDE NARRATIVE OF REVISIONS. THERE IS NO NEED TO
 SUBMIT SHEETS THAT ARE NOT BEING REVISED. ALL REVISIONS
 SHOULD BE CLOUDED ON PLAN. WPB FBC 107.2.1
 13. VALUE FOR WORK STATED ON REVISION APPLICATION
 APPEARS LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE
 AND VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR
 FOR WORK DETAILED IN REVISION. WPB FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-11-18 Time   Rev Time 0.00
Received By lmarchan Date 2019-11-15 Time 13:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-11-05 Time   Rev Time 0.00
Received By lmarchan Date 2019-10-31 Time 14:06 Sent To  
Notes
2019-11-01 14:06:14REVISION ROUTED TO JPEARSON

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2019-11-18 Cont ID  
Sent By jpearson Date 2019-11-18 Time 14:54 Rev Time 0.00
Received By jpearson Date 2019-11-18 Time 14:54 Sent To  
Notes
***NONE***