| 2019-11-18 15:36:22 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19101626 / CANOPIES FOR NEW COMMERCIAL |
| | SHELL BUILDING |
| | ADD: 1760 PALM BEACH LAKES BLVD |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL/ CONTACT: DIGITAL/ ANNE BUTLER |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 1ST REVIEW |
| | DATE: MON. NOV.18/ 2018 |
| | ACTION: DENIED |
| | |
| | 1) WITH THE SHEETS PROVIDED A3.3 WALL SECTION, A3.4 |
| | WALL SECTION, A4.1 ROOF PLAN & (2) S6.3 PLANS. NONE OF |
| | THESE PLANS INDICATE TO WHAT WIND DESIGN CRITERIA WAS |
| | USED FOR THE INSTALLATION. PLEASE SHOW COMPLIANCE FROM |
| | THE 2017 FBC-B EITHER SECTION: |
| | 1A) 3105.5.1 CANOPIES/ RIGID AWNINGS TO BE LEFT IN THE |
| | OPEN POSITON, PROVIDE WIND DESIGN. |
| | |
| | 1B) 3105.5.2 CANOPIES/ RIGID AWNINGS ARE TO BE FOLDED |
| | OR REPOSITIONED TO CLOSE AN OPENING WHEN THE BUILDING |
| | IS UNATTENDED OR ACT AS A STORM SHUTTER, THE DESIGN IN |
| | THE CLOSED POSITION. SHALL ALSO COMPLY WITH CHAPTER 16 |
| | FOR WIND AND SHALL BE IMPACT RESISTANT IN ACCORDANCE |
| | WITH 1609.1.2. |
| | |
| | 1C) 3105.5.3. STRUCTURES DESIGNED TO BE READILY REMOVED |
| | OR REPOSITIONED DURING PERIODS OF HIGH WIND VELOCITY |
| | SHALL BE POSTED WITH A LEGIBLE AND READILY VISIBLE |
| | DECAL OR PAINTED INSTRUCTIONS TO THE OWNER OR TENANT TO |
| | REMOVE OR REPOSITION THE STRUCTURE OR PART THEREOF |
| | DURING SUCH PERIODS OF TIME AS ARE DESIGNATED BY THE |
| | U.S. WEATHER BUREAU AS BEING A HURRICANE WARNING OR |
| | ALERT. |
| | |
| | 1D) SHEET S6.3 WAS LOADED INTO THE FILE TWICE, THERE |
| | ARE NO AWNING ON THIS SHEET. 107.2.1.2. ADDITIONAL |
| | INFORMATION IS REQUIRED. SHEET A3.2 HAS THE SAME |
| | DETAILS, NOT APPLICABLE, NO CANOPIES ON THESE |
| | SHEETS????????????????????????????????????????????SHEET |
| | A3.4 AND SHEET A3.4.1 BOTH SHOW MAPES |
| | |
| | 1E) SHEET A3.3 BOTH HAVE A STANDING SEAM METAL PANEL. |
| | PLEASE PROVIDE THE PRODUCT APPROVAL FOR THE ROOFING |
| | STANDING SEAM (STRUCTURAL ROOFING, NO SOLID DECKING IS |
| | SHOWN) WITH THE SPACING OF THE HORIZONTAL PURLINS. |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: (31)(D) ROOFING PRODUCTS AND ASSEMBLIES |
| | |
| | 1F) PLEASE SHOW ENGINEERING FOR THE 1 ? ALUMINUM FRAME, |
| | TYPE OF WELDS THICKNESS OF TUBES, CALCULATIONS FOR |
| | UPLIFT AS WELL AS ANCHORING FOR THE WIND DESIGN |
| | REQUIRED IN CHAPTER 1609 FOR OPEN STRUCTURES. |
| | |
| | 1G) THE SUBMITTED PLANS A3.3 SHOW A DETAIL 4 SHEET A8.2 |
| | FOR THE LOWER ANCHORING OF THIS RIGID AWNING. MISSING |
| | FROM THIS PERMIT PACKAGE. 107.2.1.2. ADDITIONAL |
| | INFORMATION REQUIRED. |
| | |
| | 1H) THE SUBMITTED PLANS A3.3 SHOW S AN UPPER CONNECTION |
| | TO THE RIGID AWNING BUT THE PLAN ONLY SHOWS FRT |
| | BLOCKING FOR THE CANOPY, NO INFORMATION AS TO HOW TO |
| | ANCHOR THE BACKING, NO SLEEVE INFORMATION, TO RESIST |
| | CRUSHING OF THE EFIS, GIVE CALCULATIONS, AND ANCHOR |
| | SIZE, HOW WILL THE ANCHOR KEEP FROM CRUSHING THE 1 ? |
| | ALUMINUM TUBING. NO FRAMING INFORMATION HAS BEEN |
| | PROVIDE. |
| | |
| | 2) SHEET A3.4 AND A4.1 BOTH SHOW MAPES SOME SORT OF SUN |
| | SHADE, THERE IS NOT ENOUGH INFORMATION TO COMMENT ON. |
| | 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | |