| 2019-11-19 13:35:40 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| | NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | NFPA 99 = HEALTH CARE FACILITIES CODE |
| | NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 1ST REVIEW |
| | |
| | PLUMBING COMMENTS: DENIED |
| | 1. PER WPB FBC 107.2.1, PROVIDE DETAILS AND INSTRUCTION |
| | FOR REMOVAL OF APPURTENANCES SUCH AS ABANDONED WATER |
| | CLOSET CARRIERS AND MODIFICATIONS OF SANITARY SYSTEM TO |
| | ACCOMMODATE BATHROOM RECONFIGURATIONS. |
| | 2. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES |
| | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET |
| | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND |
| | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| | CONFORMS TO ASSE 1070 OR CSA B125.3 PER FBC PL 416.5. |
| | 3. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER?S |
| | SPECIFICATION FOR SPECIFIED TANKLESS WATER HEATER |
| | SHOWING GPM DELIVERY THAT WILL ACCOMMODATE THE |
| | LAVATORIES DEMAND. |
| | 4. RE: PLAN SHEET A-2. LAVATORIES AND SINKS SHALL BE |
| | INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR |
| | COUNTER SURFACE 34 INCHES (865 MM) MAXIMUM ABOVE THE |
| | FINISH FLOOR OR GROUND PER FBC ACC 606.3. DETAIL 3/A-2 |
| | INDICATES FIXTURE RIM TO BE ABOVE THE MAXIMUM ALLOWABLE |
| | HEIGHT. PER WPB FBC 107.2.1, CORRECT AS REQUIRED. |
| | 5. RE: PLAN SHEET A-2; DETAIL 2/A-2. PER WPB FBC |
| | 107.2.1, SHOW CLEAR FLOOR SPACES FOR LAVATORIES. PER |
| | FBC ACC 603.2.3, DOORS SHALL NOT SWING INTO THE CLEAR |
| | FLOOR SPACE OR CLEARANCE REQUIRED FOR ANY FIXTURE. |
| | 6. RE: PLAN SHEET A-2. DETAIL 4/A-2; PER FBC ACC |
| | 604.5.1, THE SIDE WALL GRAB BAR SHALL BE 42 INCHES |
| | (1065 MM) LONG MINIMUM, LOCATED 12 INCHES (305 MM) |
| | MAXIMUM FROM THE REAR WALL AND EXTENDING 54 INCHES |
| | (1370 MM) MINIMUM FROM THE REAR WALL. PER WPB FBC |
| | 107.2.1, INDICATE THE SAME. |
| | 7. RE: PLAN SHEET A-2. DETAIL 4/A-2; PER FBC ACC 604.7, |
| | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 |
| | MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| | THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE |
| | DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48 |
| | INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND |
| | SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL |
| | NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES |
| | NOT ALLOW CONTINUOUS PAPER FLOW. PER WPB FBC 107.2.1, |
| | INDICATE THE SAME. |
| | 8. RE: PLAN SHEET A-2. DETAIL 52A-2; PER FBC ACC |
| | 604.5.1, THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 |
| | MM) LONG MINIMUM AND EXTEND FROM THE CENTERLINE OF THE |
| | WATER CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND |
| | 24 INCHES (610 MM) MINIMUM ON THE OTHER SIDE. PER WPB |
| | FBC 107.2.1, INDICATE THE SAME. |
| | 9. RE: PLAN SHEET A-2. DETAIL 52A-2; PER FBC ACC 604.2, |
| | THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR |
| | PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE |
| | OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM |
| | TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR |
| | PARTITION. PER WPB FBC 107.2.1, INDICATE THE SAME. |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |
| | 19101612 1601 BELVEDERE RD |
| | |
| | |