Plan Review Details - Permit 19101612
Plan Review Stops For Permit 19101612
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2019-11-15 Cont ID  
Sent By jwitmer Date 2019-11-15 Time 13:03 Rev Time 0.00
Received By jwitmer Date 2019-11-15 Time 10:12 Sent To  
Notes
2019-11-15 13:03:02ASBESTOS COMMERCIAL. BUILT IN 1983. PLEASE PROVIDE A
 SIGNED ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON
 LETTERHEAD, STATING THAT THE INSTRUCTIONS ON THE
 WEBSITE OF ASBESTOS PROGRAM COORDINATOR, FLORIDA
 DEPARTMENT OF HEALTH PALM BEACH COUNTY WILL BE FOLLOWED
 AND THAT NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL
 INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE
 FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-11-15 Cont ID  
Sent By jwitmer Date 2019-11-15 Time 13:20 Rev Time 0.00
Received By jwitmer Date 2019-11-15 Time 10:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-11-22 Cont ID  
Sent By jpearson Date 2019-11-22 Time 15:57 Rev Time 0.00
Received By jpearson Date 2019-11-22 Time 14:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-11-05 Cont ID  
Sent By pleduc Date 2019-11-05 Time   Rev Time 0.00
Received By pleduc Date 2019-11-05 Time 11:56 Sent To  
Notes
2019-11-05 11:58:02THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ANY AND ALL WORK ON THE FIRE ALARM SYSTEM OR DEVICES
 SHALL BE DONE UNDER SEPARATE PERMITS AND SHOP DRAWINGS.
  
  
 2) THE EXISTING FIRE ALARM SYSTEM DEVICES SHALL BE
 MAINTAINED AND REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-11-22 Time   Rev Time 0.00
Received By lmarchan Date 2019-10-30 Time 14:57 Sent To  
Notes
2019-10-31 14:57:47B15

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-11-19 Cont ID  
Sent By jesmith Date 2019-11-19 Time 13:35 Rev Time 0.00
Received By jesmith Date 2019-11-19 Time 12:27 Sent To  
Notes
2019-11-19 13:35:40CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
  
 PLUMBING COMMENTS: DENIED
 1. PER WPB FBC 107.2.1, PROVIDE DETAILS AND INSTRUCTION
 FOR REMOVAL OF APPURTENANCES SUCH AS ABANDONED WATER
 CLOSET CARRIERS AND MODIFICATIONS OF SANITARY SYSTEM TO
 ACCOMMODATE BATHROOM RECONFIGURATIONS.
 2. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3 PER FBC PL 416.5.
 3. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER?S
 SPECIFICATION FOR SPECIFIED TANKLESS WATER HEATER
 SHOWING GPM DELIVERY THAT WILL ACCOMMODATE THE
 LAVATORIES DEMAND.
 4. RE: PLAN SHEET A-2. LAVATORIES AND SINKS SHALL BE
 INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR
 COUNTER SURFACE 34 INCHES (865 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND PER FBC ACC 606.3. DETAIL 3/A-2
 INDICATES FIXTURE RIM TO BE ABOVE THE MAXIMUM ALLOWABLE
 HEIGHT. PER WPB FBC 107.2.1, CORRECT AS REQUIRED.
 5. RE: PLAN SHEET A-2; DETAIL 2/A-2. PER WPB FBC
 107.2.1, SHOW CLEAR FLOOR SPACES FOR LAVATORIES. PER
 FBC ACC 603.2.3, DOORS SHALL NOT SWING INTO THE CLEAR
 FLOOR SPACE OR CLEARANCE REQUIRED FOR ANY FIXTURE.
 6. RE: PLAN SHEET A-2. DETAIL 4/A-2; PER FBC ACC
 604.5.1, THE SIDE WALL GRAB BAR SHALL BE 42 INCHES
 (1065 MM) LONG MINIMUM, LOCATED 12 INCHES (305 MM)
 MAXIMUM FROM THE REAR WALL AND EXTENDING 54 INCHES
 (1370 MM) MINIMUM FROM THE REAR WALL. PER WPB FBC
 107.2.1, INDICATE THE SAME.
 7. RE: PLAN SHEET A-2. DETAIL 4/A-2; PER FBC ACC 604.7,
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL
 NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES
 NOT ALLOW CONTINUOUS PAPER FLOW. PER WPB FBC 107.2.1,
 INDICATE THE SAME.
 8. RE: PLAN SHEET A-2. DETAIL 52A-2; PER FBC ACC
 604.5.1, THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915
 MM) LONG MINIMUM AND EXTEND FROM THE CENTERLINE OF THE
 WATER CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND
 24 INCHES (610 MM) MINIMUM ON THE OTHER SIDE. PER WPB
 FBC 107.2.1, INDICATE THE SAME.
 9. RE: PLAN SHEET A-2. DETAIL 52A-2; PER FBC ACC 604.2,
 THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM
 TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR
 PARTITION. PER WPB FBC 107.2.1, INDICATE THE SAME.
  
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19101612 1601 BELVEDERE RD
  
  