Plan Review Details - Permit 19101609
Plan Review Stops For Permit 19101609
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-12-24 Cont ID  
Sent By jgomez Date 2019-12-24 Time 13:55 Rev Time 0.00
Received By jgomez Date 2019-12-24 Time 13:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-11-22 Cont ID  
Sent By jgomez Date 2019-11-22 Time 16:25 Rev Time 0.00
Received By jgomez Date 2019-11-22 Time 15:27 Sent To  
Notes
2019-11-22 16:26:52RESIDENTIAL (R3) ALTERATION BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE.
  
 1- SCOPE OF WORK IS NOT CLEAR. SEC. 107.2.1 CITY
 AMENDMENTS. PERMIT APPLICATION CALLS FOR BATH AND
 KITCHEN REMODELING ONLY BUT PLANS SUBMITTED INCLUDE ALL
 KIND OF ADDITIONAL WORK. REVISE SCOPE OF WORK ON PERMIT
 APPLICATION AND PLANS TO MATCH.
 PLANS NEED TO BE CLEAR ON SCOPE OF WORK TO BE
 CONSIDERED FOR THIS PERMIT. CLEARLY SPECIFY WHAT IS NEW
 AND WHAT IS EXISTING. CLEARLY DEFINE ALL PROPOSED SCOPE
 OF WORK AND REVISE VALUATION ACCORDIGNLY. SEC. 109.3
 CITY AMENDMENTS.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-12-25 Cont ID  
Sent By jpearson Date 2019-12-25 Time 08:55 Rev Time 0.00
Received By jpearson Date 2019-12-25 Time 08:55 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-11-19 Cont ID  
Sent By jpearson Date 2019-11-19 Time 17:49 Rev Time 0.00
Received By jpearson Date 2019-11-19 Time 13:01 Sent To  
Notes
2019-11-19 17:04:48CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN STATES THAT THERE IS A UPGRADED 100 AMP SERVICE
 ON THIS STRUCTURE. IS THIS A NEW SERVICE, OR IS IT
 BEING UPGRADED FROM AN EXISTING SERVICE? PROVIDE
 CLARIFICATION. PROVIDE RISER DIAGRAM, SHOWING ALL
 DETAILS OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD
 SERVICE, WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO
 ANY SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; WPB FBC 107.2.1
 2. IF THIS IS A NEW OR REBUILT SERVICE, PROVIDE
 AVAILABLE SHORT CIRCUIT CALCULATION FOR SERVICE
 INCLUDING INFORMATION FROM THE POWER COMPANY STATING
 WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE
 SERVICE TO CONFIRM THE STATED AIC RATING OF THE SERVICE
 EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC RE
 E3606.3
 3. SINCE ONCE SERVICE DROP IS PERMITTED PER RESIDENTIAL
 ADDRESS, PROVIDE LOAD CALCULAITON FOR BOTH SERVICES TO
 CONFIRM THE RATING OF THE SERVICE WIRE IS SUFFICIENT.
 NEC 220; FBC RE E3602.2
 4. ELECTRICAL NOTE NUMBER 8 IS NOT CODE COMPLANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902; FBC EX 607.1.1 OR 801.1,
 801.2, OR 901.2 AS APPLICABLE.
 5. ELECTRICAL NOTE NUMBER 19 STATES THAT LIGHTING IN
 CLOTHES CLOSETS SHALL COMPLY WITH NEC 4/10.8/D/1, WHICH
 DOESN?T EXIST. PROVIDE CORRECTION. NEC 410.16; FBC RE
 E4003.12
 6. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE
 OUTLETS IN GARAGE, INCLUDING THE GARAGE DOOR OPENER.
 PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.2
 7. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET. THE WALL SPACING REQUIREMENTS
 FOR KITCHEN COUNTER SPACE STATE THAT RECEPTACLE OUTLETS
 SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE
 IS MORE THAN 24 INCHES MEASURED HORIZONTALLY FROM A
 RECEPTACLE OUTLET IN THAT SPACE. THE PLAN PROVIDED DOES
 NOT MEET THIS CODE IN SOME AREAS. PROVIDE CORRECTION.
 NEC 210.52(C)(1); FBC RE E3901
 8. NOT LESS THAN ONE RECEPTACLE OUTLET, IN ADDITION TO
 ANY PROVIDED FOR SPECIFIC EQUIPMENT, SHALL BE INSTALLED
 IN EACH SEPARATE UNFINISHED PORTION OF A BASEMENT, IN
 EACH ATTACHED GARAGE, AND IN EACH DETACHED GARAGE OR
 ACCESSORY BUILDING THAT IS PROVIDED WITH ELECTRICAL
 POWER. THE BRANCH CIRCUIT SUPPLYING THE RECEPTACLE(S)
 IN A GARAGE SHALL NOT SUPPLY OUTLETS OUTSIDE OF THE
 GARAGE AND NOT LESS THAN ONE RECEPTACLE OUTLET SHALL BE
 INSTALLED FOR EACH MOTOR VEHICLE SPACE. PROVIDE
 CORRECTION. NEC 210.52(G)(1), (2), AND (3); FBC RE
 E3901.9
 9. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR
 SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE
 EQUIPMENT PER CODE. NEC 210.63; FBC RE E3901.12
 10. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST
 ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND
 NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE
 INSTALLED AT THE FRONT AND BACK OF THE DWELLING.
 PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE E3901.7
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2019-11-26 Cont ID  
Sent By fmittner Date 2019-11-26 Time 16:42 Rev Time 0.00
Received By fmittner Date 2019-11-26 Time 16:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-12-25 Time   Rev Time 0.00
Received By lmarchan Date 2019-12-13 Time 13:21 Sent To  
Notes
2019-12-16 13:21:55R23

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-11-27 Cont ID  
Sent By cpuell Date 2019-11-27 Time 11:48 Rev Time 0.00
Received By cpuell Date 2019-10-30 Time 14:52 Sent To  
Notes
2019-10-31 14:53:00R23

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-12-19 Cont ID  
Sent By jesmith Date 2019-12-19 Time 15:12 Rev Time 0.00
Received By jesmith Date 2019-12-19 Time 15:09 Sent To  
Notes
2019-12-19 15:12:29PLUMBING COMMENTS: APPROVED
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-11-12 Cont ID  
Sent By jesmith Date 2019-11-12 Time 16:20 Rev Time 0.00
Received By jesmith Date 2019-11-12 Time 16:20 Sent To  
Notes
2019-11-12 16:20:38PLUMBING COMMENTS: APPROVED W/PROVISO
 1. SEE RED LINED COMMENTS AND CORRECTIONS FOR PLUMBING
 RISER FOR M.B.R ON PLAN PAGE P01. INSPECTOR TO CONFIRM
 THERE IS AN EXISTING VENT TO THE EXTERIOR FOR THIS
 BUILDING DRAIN OR REQUIRE THE STUDOR VENT CHANGE TO
 VENT TO THE EXTERIOR.
 2. SEE RED LINED COMMENTS ON TYPICAL WALL SECTION AND
 SHOWER PAN/CURB DETAIL; SHOWER COMPARTMENT SHALL COMPLY
 WITH THE REQUIREMENTS OF FBC RES P2709
  