Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-11-01 Cont ID  
Sent By sathomas Date 2019-11-01 Time 00:00 Rev Time 0.00
Received By sathomas Date 2019-11-01 Time 00:00 Sent To M
Notes
2019-11-01 10:46:131. PROVIDE A K-TYPE PORTABLE FIRE EXTINGUISHER AND
 ASSOCIATED SIGNAGE IN KITCHEN AREA.
  
 2. KITCHEN HOOD SUPPRESSION SYSTEM SHALL BE TIED INTO
 THE BUILDING FIRE ALARM SYSTEM TO INITIATE A GENERAL
 FIRE ALARM CONDITION.
  
 3. DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE
 HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE
 THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT
 TEMPERATURE REACHES 475F DEGREES AT 1-INCH BELOW THE
 SURFACE.
  
 4. PROVIDE AN 8" TALL STEEL BAFFLE OR PROVIDE 16" OF
 SPACE BETWEEN THE DEEP FAT FRYER AND SURFACE FLAMES OF
 THE ADJACENT EQUIPMENT.
  
 5. WHERE APPLICABLE, ANY AND ALL WORK ON THE FIRE ALARM
 SYSTEM SHALL BE DONE BY A FIRE ALARM CONTRACTOR. A
 SEPARATE SHOP DRAWING COMPLIANT WITH NFPA 72 IS
 REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY THE
 FIRE PREVENTION BUREAU PRIOR TO ANY INSTALLATION.
  
 6. ALL KITCHEN EQUIPMENT AND OPERATIONS SHALL COMPLY
 WITH NFPA 96, STANDARD FOR VENTILATION CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS.
 EXTINGUISHMENT AND VENTILATION SYSTEM SHOP DRAWINGS
 SHALL BE SUBMITTED SEPARATELY FOR APPROVAL.
  
 7. PLEASE PROVIDE MANUFACTURER'S SPECIFICATION SHEETS
 FOR ALL EQUIPMENT TO BE EXCHANGED (I.E. NOZZLES,
 FUSIBLE LINKS, CYLINDERS, ETC.)
  
 S. THOMAS
 561-804-4728
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-11-05 Time   Rev Time 0.00
Received By lmarchan Date 2019-10-30 Time 13:41 Sent To  
Notes
2019-10-31 13:41:27ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-11-05 Cont ID  
Sent By ccole Date 2019-11-05 Time 08:04 Rev Time 0.00
Received By ccole Date 2019-11-05 Time 08:04 Sent To I
Notes
2019-11-05 08:07:471ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19101600
 11/5/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A BRIEF SCOPE OF WORK OUTLINE ON THE
 PLAN THAT CLARIFIES AND ITEMIZES ALL COMPONENTS OF THE
 SYSTEM THAT WILL BE UNDERGOING REPAIR- SECTION 107.2.1
 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  