Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-11-27 Cont ID  
Sent By jgomez Date 2019-11-27 Time 09:56 Rev Time 0.00
Received By jgomez Date 2019-11-27 Time 09:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-11-18 Cont ID  
Sent By jgomez Date 2019-11-18 Time 18:01 Rev Time 0.00
Received By jgomez Date 2019-11-18 Time 14:22 Sent To  
Notes
2019-11-18 18:17:32SCREEN ENCLOSURE BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- DESIGN WIND PRESSURES USED FOR CALCULATIONS ON SHEET
 "B" DON'T MATCH DESIGN WIND PRESSURES SHOWN ON TABLE
 2002.4 FBC-BUILDING. REVISE INFORMATION ON THE TOP
 RIGHT CORNER OF THE SHEET AS REQUIRED. SEE TABLE 2002.4
 FBC-BUILDING.
 NOTE: ALSO, REVISE INFORMATION ON SHEET 1 OF 1 WHERE
 THE SITE SPECIFIC LAYOUT IS SHOWN.
  
 2- SCREEN ENCLOSURES PRIMARY STRUCTURAL MEMBERS SHALL
 BE DESIGNED FOR A 300 POUND LOAD APPLIED VERTICALLY
 DOWNWARD ALONG ANY 1 FOOT OF ANY MEMBER, NON OCCURRING
 SIMULTANEOUSLY WITH WIND LOAD). REVISE CALCULATIONS
 INFORMATION SHOWN ON SHEET B. SEE SEC. 2002.4
 FBC-BUILDING.
  
 3- THIS SCREEN ENCLOSURE IS FOR A POOL ENCLOSURE. SHOW
 HOW COMPLYING WITH THE RESIDENTIAL SWIMMING BARRIER
 REQUIREMENTS. PROVIDE SPECIFICATIONS FOR THE GATE
 SHOWING COMPLIANCE WITH SEC. R4501.17 FBC-RESIDENTIAL.
  
 4- THERE ARE TOO MANY GENERAL DETAILS IN THIS
 SUBMITTAL. CLEARLY MARK ALL THE DETAILS THAT APPLY TO
 THIS PROJECT. SEC. 107.2.1 CITY AMENDMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-11-27 Cont ID  
Sent By jgomez Date 2019-11-27 Time 09:56 Rev Time 0.00
Received By jgomez Date 2019-11-25 Time 13:15 Sent To I
Notes
2019-11-26 13:15:34RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-11-18 Cont ID  
Sent By jgomez Date 2019-11-18 Time 18:17 Rev Time 0.00
Received By jgomez Date 2019-10-29 Time 13:31 Sent To I
Notes
2019-10-31 13:32:02ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2019-11-01 Cont ID  
Sent By rfalcone Date 2019-11-01 Time 09:56 Rev Time 0.00
Received By rfalcone Date 2019-11-01 Time 09:56 Sent To B
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved