Plan Review Details - Permit 19101484
Plan Review Stops For Permit 19101484
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-12-20 Cont ID  
Sent By dbattles Date 2019-12-20 Time 16:21 Rev Time 0.00
Received By dbattles Date 2019-12-20 Time 16:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-11-18 Cont ID  
Sent By dbattles Date 2019-11-18 Time 11:05 Rev Time 0.00
Received By dbattles Date 2019-11-18 Time 08:07 Sent To  
Notes
2019-11-18 11:05:49BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19101484
 REVIEWED: NOVEMBER 18, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 107.5.3 FBC[AMENDED]PLEASE PROVIDE PLANS TO SHOW
 LOCATIONS THE SMOKE CURTAINS, OR STATE THE REVISION
 NUMBER UNDER WHICH IT WAS SUBMITTED.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-12-13 Cont ID  
Sent By pleduc Date 2019-12-13 Time   Rev Time 0.00
Received By pleduc Date 2019-12-13 Time 13:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-11-15 Cont ID  
Sent By pleduc Date 2019-11-15 Time   Rev Time 0.00
Received By pleduc Date 2019-11-15 Time 11:03 Sent To  
Notes
2019-11-15 16:43:58THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) IT IS UNCLEAR WHERE OR HOW MANY SMOKE CURTAINS HAVE
 BEEN INSTALLED. IT IS MY RECOLLECTION THAT ONLY A FEW
 LOWER FLOORS IN A FEW SEPECIFC AREAS AHD SMOKE CURTAINS
 INSTALLED.
  
 PLEASE PROVIDE A NARRATIVE AND PLAN SHEET FOR REVIEW
 AND CLARIFICATION PURPOSES.
  
  
 2) THE SMOKE CONTROL ANALYSIS IS PROVIDED HOWEVER,
 THERE ARE NO INDICATIONS OF WHAT OR WHERE ANY REVISIONS
 TO THIS DOCUMENT ARE RECORED.
  
 THE CHANGE NARRATIVE SHEET ONLY INDICATES MS0.08.
  
 ANY REVISION TO THE SMOKE CONTROL DOCUMENT NEEDS TO BE
 CALLED OUT IN DETAIL.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFYIN DETAILED
 NARRATIVE.
  
  
 3) SHEET MS 0.08 - THERE IS A REVISION CLOUD INDICATING
 COMMENTS 1) & 2) ABOUT ALL SMOKE CURTAINS ELEVATOR
 LOBBIES BEING ACTIVATED AND SMOKE DETECTORS IN ALL
 ELEVATOR LOBBIES (5-25) ACTIVATING THE ENTIRE BANK
 SMOKE CURTAINS.
  
 PLEASE CLARIFY HOW MANY SMOKE CURTAINS HAVE BEEN
 INSTALLED AND WHERE EXACTLY AND REVIEW THIS SEQUENCE OF
 OPERATION FOR ACCURACY.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-12-30 Time   Rev Time 0.00
Received By lmarchan Date 2019-12-10 Time 13:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-11-18 Cont ID  
Sent By dbattles Date 2019-11-18 Time 11:05 Rev Time 0.00
Received By dbattles Date 2019-10-29 Time 11:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-12-30 Cont ID  
Sent By ccole Date 2019-12-30 Time 14:57 Rev Time 0.00
Received By ccole Date 2019-12-30 Time 14:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-11-14 Cont ID  
Sent By ccole Date 2019-11-14 Time 08:04 Rev Time 0.00
Received By ccole Date 2019-11-13 Time 10:39 Sent To  
Notes
2019-11-14 08:43:051ST REVIEW FBC-2010 MECHANICAL
 REVISION #19101484
 THE BRISTOL
 PERMIT #15111020
 11/13/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE- 2010
 FBC M- FLORIDA MECHANICAL CODE- 2010
 FBC EC- FLORIDA ENERGY CONSERVATION CODE- 2010
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS- 2010
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M5.08: INDICATE IN THE SEQUENCE OF OPERATION
 WHERE THE SMOKE CURTAINS ARE LOCATED- ON WHICH FLOORS
 AND WHICH ELEVATORS. THE NOTES SEEM TO INDICATE ALL
 ELEVATORS ON FLOORS 5-25. IS THAT CORRECT?- SECTION
 107.2.1 WPB.
  
 2) PLEASE REVISE THE SMOKE ANALYSIS TO INDIICATE THE
 LOCATIONS OF THE SMOKE CURTAINS AND THE SEQUENCE OF
 OPERATION- SECTION 107.2.1 WPB.
  
 3) PROVIDE A SPEC SHEET FOR THE SMOKE CURTAIN WITH AN
 APPROVAL SIGNATURE BY THE ENGINEER OF RECORD- SECTION
 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-12-20 Cont ID  
Sent By dbattles Date 2019-12-20 Time 16:22 Rev Time 0.00
Received By dbattles Date 2019-12-20 Time 16:22 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-11-13 Cont ID  
Sent By ccole Date 2019-11-13 Time 11:07 Rev Time 0.00
Received By ccole Date 2019-11-13 Time 11:07 Sent To  
Notes
2019-11-13 11:12:031ST REVIEW FBC-2010 MECHANICAL
 REVISION #19101484
 THE BRISTOL
 PERMIT #15111020
 11/13/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE- 2010
 FBC M- FLORIDA MECHANICAL CODE- 2010
 FBC EC- FLORIDA ENERGY CONSERVATION CODE- 2010
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS- 2010
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE REVISED SMOKE CONTROL RATIONAL ANALYSIS BY SLS
 FIRE PROTECTION ENGINEERS REQUIRES ELECTRONIC SEALS AND
 SIGNATURES BY THE ENGINEER OF RECORD- FL. STATUTE
 471.025 AND SECTION 61G15-23.005 FLORIDA ADMINISTRATIVE
 CODE.
  
 2) SHEET M5.08: ENGINEERS MAY NOT SELF-CERTIFY
 ELECTRONIC SIGNATURES AND SEALS. CERTIFICATION SHALL BE
 BY A THIRD-PARTY AGENCY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  