Plan Review Details - Permit 19101472
Plan Review Stops For Permit 19101472
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-04-07 Cont ID  
Sent By rmcphers Date 2020-04-07 Time 15:49 Rev Time 0.00
Received By rmcphers Date 2020-04-07 Time 15:13 Sent To  
Notes
2020-04-07 15:51:16CORRECTIONS FROM PREVIOUS COMMENTS OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-03-18 Cont ID  
Sent By dbattles Date 2020-03-18 Time 12:37 Rev Time 0.00
Received By jgomez Date 2020-03-18 Time 10:41 Sent To  
Notes
2020-03-18 12:46:33REVISION SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 ORIGINAL COMMENT FROM PREVIOUS PLAN REVIEWER;
 1- 405.7.4 FBC[A]CHANGE IN DIRECTION.RAMPS THAT CHANGE
 DIRECTION BETWEEN RUNS AT LANDINGS SHALL HAVE A CLEAR
 LANDING 60 INCHES (1525 MM) MINIMUM BY 60 INCHES (1525
 MM) MINIMUM. ADVISORY 405.7 LANDINGS. RAMPS THAT DO NOT
 HAVE LEVEL LANDINGS AT CHANGES IN DIRECTION CAN CREATE
 A COMPOUND SLOPE THAT WILL NOT MEET THE REQUIREMENTS OF
 THIS CODE.
 -PLEASE SHOW AND DIMENSION CHANGE IN DIRECTION THAT
 MEETS 405.7.4 FOR SIZE AND SLOPE.
  
 RESPONSE:
 ARCHITECT'S RESPONSE LETTER STATED TO SEE REVISED
 REVISED SHEET A1.1.2A. REVISED SHEET A1.1.2A IS OK, BUT
 THERE ARE TWO RAMPS FOR THIS RETAIL SPACE. THE COMMENTS
 WERE FOR THE RAMP LOCATED ON THE SOUTH SIDE. PLEASE
 SHOW COMPLIANCE FOR THIS RAMP.
  
 ORIGINAL COMMENT FROM PREVIOUS PLAN REVIEWER;
 2- 505.10.1 FBC[A]TOP AND BOTTOM EXTENSION AT
 RAMPS.RAMP HANDRAILS SHALL EXTEND HORIZONTALLY ABOVE
 THE LANDING FOR 12 INCHES (305 MM) MINIMUM BEYOND THE
 TOP AND BOTTOM OF RAMP RUNS. EXTENSIONS SHALL RETURN TO
 A WALL, GUARD, OR THE LANDING SURFACE, OR SHALL BE
 CONTINUOUS TO THE HANDRAIL OF AN ADJACENT RAMP RUN.
 -PLEASE SHOW HANDRAIL EXTENSIONS AT BOTTOM OF RAMP.
  
 RESPONSE:
 RESPONSE:
 ARCHITECT'S RESPONSE LETTER STATED TO SEE REVISED
 REVISED SHEET A1.1.2A. REVISED SHEET A1.1.2A IS OK, BUT
 THERE ARE TWO RAMPS FOR THIS RETAIL SPACE. THE COMMENTS
 WERE FOR THE RAMP LOCATED ON THE SOUTH SIDE. PLEASE
 SHOW COMPLIANCE FOR THIS RAMP.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. (NOTE: SUBMIT OLD DRAWINGS FOR REFERENCE). A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
  
  
 BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19101472
 2ND REVIEW: JANUARY 31, 2020
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[A] = FBC ACCESSIBILITY
  
 405.7.4 FBC[A]CHANGE IN DIRECTION.RAMPS THAT CHANGE
 DIRECTION BETWEEN RUNS AT LANDINGS SHALL HAVE A CLEAR
 LANDING 60 INCHES (1525 MM) MINIMUM BY 60 INCHES (1525
 MM) MINIMUM. ADVISORY 405.7 LANDINGS. RAMPS THAT DO NOT
 HAVE LEVEL LANDINGS AT CHANGES IN DIRECTION CAN CREATE
 A COMPOUND SLOPE THAT WILL NOT MEET THE REQUIREMENTS OF
 THIS CODE.
 -PLEASE SHOW AND DIMENSION CHANGE IN DIRECTION THAT
 MEETS 405.7.4 FOR SIZE AND SLOPE.
  
 505.10.1 FBC[A]TOP AND BOTTOM EXTENSION AT RAMPS.RAMP
 HANDRAILS SHALL EXTEND HORIZONTALLY ABOVE THE LANDING
 FOR 12 INCHES (305 MM) MINIMUM BEYOND THE TOP AND
 BOTTOM OF RAMP RUNS. EXTENSIONS SHALL RETURN TO A WALL,
 GUARD, OR THE LANDING SURFACE, OR SHALL BE CONTINUOUS
 TO THE HANDRAIL OF AN ADJACENT RAMP RUN.
 -PLEASE SHOW HANDRAIL EXTENSIONS AT BOTTOM OF RAMP.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-01-31 Cont ID  
Sent By dbattles Date 2020-01-31 Time 14:11 Rev Time 0.00
Received By dbattles Date 2020-01-31 Time 14:11 Sent To  
Notes
2020-02-05 16:40:43BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19101472
 2ND REVIEW: JANUARY 31, 2020
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[A] = FBC ACCESSIBILITY
  
 405.7.4 FBC[A]CHANGE IN DIRECTION.RAMPS THAT CHANGE
 DIRECTION BETWEEN RUNS AT LANDINGS SHALL HAVE A CLEAR
 LANDING 60 INCHES (1525 MM) MINIMUM BY 60 INCHES (1525
 MM) MINIMUM. ADVISORY 405.7 LANDINGS. RAMPS THAT DO NOT
 HAVE LEVEL LANDINGS AT CHANGES IN DIRECTION CAN CREATE
 A COMPOUND SLOPE THAT WILL NOT MEET THE REQUIREMENTS OF
 THIS CODE.
 -PLEASE SHOW AND DIMENSION CHANGE IN DIRECTION THAT
 MEETS 405.7.4 FOR SIZE AND SLOPE.
  
 505.10.1 FBC[A]TOP AND BOTTOM EXTENSION AT RAMPS.RAMP
 HANDRAILS SHALL EXTEND HORIZONTALLY ABOVE THE LANDING
 FOR 12 INCHES (305 MM) MINIMUM BEYOND THE TOP AND
 BOTTOM OF RAMP RUNS. EXTENSIONS SHALL RETURN TO A WALL,
 GUARD, OR THE LANDING SURFACE, OR SHALL BE CONTINUOUS
 TO THE HANDRAIL OF AN ADJACENT RAMP RUN.
 -PLEASE SHOW HANDRAIL EXTENSIONS AT BOTTOM OF RAMP.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-12-10 Cont ID  
Sent By shill Date 2019-12-04 Time 10:50 Rev Time 0.00
Received By dbattles Date 2019-12-03 Time 14:01 Sent To  
Notes
2019-12-10 10:10:081) 404.2.4 MANEUVERING CLEARANCES. MINIMUM MANEUVERING
 CLEARANCES AT DOORS AND GATES SHALL COMPLY
 WITH 404.2.4. MANEUVERING CLEARANCES SHALL EXTEND THE
 FULL WIDTH OF THE DOORWAY AND THE REQUIRED
 LATCH SIDE OR HINGE SIDE CLEARANCE.
 SHOW CLEARANCE FOR SIDE APPROACH ON PLANS
  
 2) PLEASE ADJUST ACCESSIBILITY RAMP TO MEET THE
 FOLLOWING BUILDING CODE PROVISIONS FOR ENCROACHMENT
 INTO THE RIGHT OF WAY.
 3202.2 ENCROACHMENTS ABOVE GRADE AND BELOW 8 FEET IN
 HEIGHT. ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
 ABOVE
 GRADE AND BELOW 8 FEET (2438 MM) IN HEIGHT SHALL BE
 PROHIBITED
 EXCEPT AS PROVIDED FOR IN SECTIONS 3202.2.1 THROUGH
 3202.2.3. DOORS AND WINDOWS SHALL NOT OPEN OR PROJECT
 INTO
 THE PUBLIC RIGHT-OF-WAY.
 3202.2.1 STEPS. STEPS SHALL NOT PROJECT MORE THAN 12
 INCHES (305 MM) AND SHALL BE GUARDED BY APPROVED
 DEVICES NOT LESS THAN 3 FEET (914 MM) IN HEIGHT, OR
 SHALL BE
 LOCATED BETWEEN COLUMNS OR PILASTERS.
 3202.2.2 ARCHITECTURAL FEATURES. COLUMNS OR PILASTERS,
 INCLUDING BASES AND MOLDINGS, SHALL NOT PROJECT MORE
 THAN
 12 INCHES (305 MM). BELT COURSES, LINTELS, SILLS,
 ARCHITRAVES,
 PEDIMENTS AND SIMILAR ARCHITECTURAL FEATURES SHALL
 NOT PROJECT MORE THAN 4 INCHES (102 MM).

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-12-03 Cont ID  
Sent By jpearson Date 2019-12-03 Time 09:18 Rev Time 0.00
Received By jpearson Date 2019-12-03 Time 09:18 Sent To  
Notes
2019-12-03 08:59:03NO NOTES

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-12-04 Cont ID  
Sent By pleduc Date 2019-12-04 Time   Rev Time 0.00
Received By pleduc Date 2019-11-18 Time 10:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-04-07 Cont ID  
Sent By rmcphers Date 2020-04-07 Time 16:00 Rev Time 0.00
Received By rmcphers Date 2020-04-02 Time 10:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-03-18 Cont ID  
Sent By jgomez Date 2020-03-18 Time 12:46 Rev Time 0.00
Received By jgomez Date 2020-03-10 Time 12:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-01-31 Cont ID  
Sent By dbattles Date 2020-01-31 Time 14:11 Rev Time 0.00
Received By dbattles Date 2020-01-22 Time 14:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-12-09 Cont ID  
Sent By cpuell Date 2019-12-09 Time 15:15 Rev Time 0.00
Received By cpuell Date 2019-11-12 Time 14:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-12-05 Cont ID  
Sent By ccole Date 2019-12-05 Time 11:17 Rev Time 0.00
Received By ccole Date 2019-12-05 Time 07:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-12-09 Cont ID  
Sent By gjohnson Date 2019-12-09 Time 10:28 Rev Time 0.00
Received By gjohnson Date 2019-11-22 Time 16:59 Sent To  
Notes
2019-12-12 17:19:34REVIEWED REMOTELY BY GEORGE JOHNSON
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-04-07 Cont ID  
Sent By rmcphers Date 2020-04-07 Time 16:00 Rev Time 0.00
Received By rmcphers Date 2020-04-07 Time 16:00 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-03-18 Cont ID  
Sent By jgomez Date 2020-03-18 Time 12:46 Rev Time 0.00
Received By jgomez Date 2020-03-18 Time 12:46 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2019-12-04 Cont ID  
Sent By dbattles Date 2019-12-04 Time 10:53 Rev Time 0.00
Received By dbattles Date 2019-12-04 Time 10:53 Sent To  
Notes
2019-12-03 09:19:14ELECTRICAL SHEETS OK.

Review Stop Z ZONING
Rev No 1 Status P Date 2019-12-09 Cont ID  
Sent By aaponte Date 2019-12-09 Time 12:00 Rev Time 0.00
Received By aaponte Date 2019-12-09 Time 12:00 Sent To  
Notes
2019-12-09 12:00:57PROVISO: ADA RAMP ON NORTH SIDE OF COMMERCIAL SPACE
 (OLIVE AVE) SHALL BE REDESIGNED NOT TO ENCROACH INTO
 THE ROW.