| 2019-11-12 13:12:13 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| | NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | NFPA 99 = HEALTH CARE FACILITIES CODE |
| | NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 1ST REVIEW |
| | |
| | PLUMBING COMMENTS: DENIED |
| | 1. PROVISO: AT THE PLUMBING INSPECTOR'S DISCRETION, |
| | SHOW THAT ANY EXISTING PLUMBING INFRASTRUCTURE, |
| | INCLUSIVE OF PIPING, PLUMBING FIXTURES AND APPLIANCES |
| | SHOWN ON THE DEMOLITION PLAN, IS CODE COMPLIANT. THIS |
| | MAY REQUIRE PROVIDING DOCUMENTATION OF, OPENING OF |
| | WALLS AND FLOORS, PRESSURE TESTS, VIDEO CAM OF BURIED |
| | SANITARY, ETC., AS DETERMINED BY THE PLUMBING |
| | INSPECTOR. PLEASE CALL TIM LARGE AT 561-805-6692 FOR |
| | ADDITIONAL INFORMATION OR CLARIFICATION. |
| | 2. SEE REDLINED COMMENTS ON PLAN: |
| | A. SANITARY RISER DIAGRAM; PROVIDE VENT FOR WATER |
| | CLOSET AND SHOWER COMPLYING WITH FBC RES P3108 |
| | B. SHOWER COMPARTMENTS LESS THAN 30" WIDE (FINISH |
| | DIMENSION) SHALL BE A MINIMUM 25 INCHES WIDE AND HAVE |
| | MINIMUM 1300 SQUARE INCHES CROSS SECTIONAL PER FBC RES |
| | PO2708.1. |
| | C. SHOWER COMPARTMENT ACCESS/EGRESS SHALL HAVE A CLEAR, |
| | UNOBSTRUCTED WIDTH OF NOT LESS THAN 22" PER FBC RES |
| | P2708.1.1. |
| | D. SEE SHOWER DETAIL; LINER SHALL TURN UP A MINIMUM OF |
| | 2 INCHES FROM THE TOP DOWN TO THE THRESHOLD AT THE CURB |
| | SHALL BE MINIMUM OF 2 INCHES |
| | E. SEE SHOWER DETAIL; PROVIDE SHOWER DRAIN IN |
| | ACCORDANCE WITH FBC RES P2709.4. |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |
| | 19101435 727 KANUGA DR |
| | |
| | |
| | |