Plan Review Details - Permit 19101431
Plan Review Stops For Permit 19101431
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2020-01-28 Cont ID  
Sent By pvalenti Date 2020-01-28 Time 15:33 Rev Time 0.00
Received By jwitmer Date 2020-02-24 Time 06:10 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2019-11-04 Cont ID  
Sent By jwitmer Date 2019-11-04 Time 15:12 Rev Time 0.00
Received By jwitmer Date 2019-11-04 Time 14:43 Sent To  
Notes
2019-11-04 15:12:52ASBESTOS COMMERCIAL. PLEASE PROVIDE A SIGNED
 ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD,
 STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF
 ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF
 HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT
 NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL
 INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE
 FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-02-24 Cont ID  
Sent By jwitmer Date 2020-02-24 Time 07:33 Rev Time 0.00
Received By jwitmer Date 2020-02-24 Time 06:11 Sent To  
Notes
2020-02-24 07:33:492017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19101431
 ADD: 3515 S DIXIE HWY
 CONT: POWER ENTERPRISE CORP
 TEL: 305-216-9782
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: MON. FEB. 24TH/ 2020
 ACTION: BUILDING PROVISO
 1) WALK IN COOLERS ARE UNDER A SEPARATE PERMIT, WITH
 ASSOCIATED FEES AND REVIEWS. 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE CHAPTER 1OF THE
 ADMINISTRATIVE CODE SECTION 105.1 PERMITS.
  
 2) THE PROPOSED FLOOR PLAN DOES INDICATE THE SERVICE/
 CASHIERS COUNTER IS EXISTING, NO INFORMATION IS GIVEN.
 COMPLIANCE WITH SERVICE COUNTERS CANNOT BE ESTABLISHED
 CHECK IN THE FIELD. SEE THE 2017 ACCESS. CODE:
 CHECK WRITING SURFACES. 904.3.3. CHECK WRITING
 SURFACES. WHERE PROVIDED, CHECK WRITING SURFACES SHALL
 COMPLY WITH 902.3.
 WORK SURFACES. 902.3 HEIGHT. THE TOPS OF WORK SURFACES
 SHALL BE 28 INCHES MINIMUM AND 34 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND. DISPROPORTIONATE COST WAS
 NOT PROVIDED.
  
 3A) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
 3B) THE DETAIL 03 THE PROPOSED ROOFING PLAN DOES
 PROVIDE A MIAMI-DADE NOTICE OF ACCEPTANCE (NOA) NUMBER
 15-1008.01 WHICH IS EXPIRED. THERE IS A NEWER NOA FOR A
 REPLACEMENT, NOA: 15-1020.06 WHICH EXPIRES ON
 11/06/2023. THIS NOA IS COMPRISED OF 112 PAGES.
  
 3C) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 3D) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER OR REGISTERED
 ARCHITECT. 1609.6.4.4.1 COMPONENTS & CLADDING.
  
 JAMES A. WITMER BN, PX, CBO
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6717 / E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-02-03 Cont ID  
Sent By rmcphers Date 2020-02-03 Time 15:46 Rev Time 0.00
Received By rmcphers Date 2020-02-03 Time 15:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-11-05 Cont ID  
Sent By jwitmer Date 2019-11-05 Time 08:13 Rev Time 0.00
Received By jwitmer Date 2019-11-04 Time 14:43 Sent To  
Notes
2019-11-05 08:13:072017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19101431
 ADD: 3515 S DIXIE HWY
 CONT: POWER ENTERPRISE CORP
 TEL: 305-216-9782
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. NOV. 5TH/ 2019
 ACTION: DENIED
  
 1) WHEN CHECKING THE STATUS OF THE CONTRACTORS LISTED
 FOR THIS PROJECT THE (EC) CONTRACTOR POWER ENTERPRISE
 CORP, QUALIFIER LAZARO FERNANDEZ, THE LICENSE IS NULL &
 VOID.
  
 2) THE COVERSHEET C1.0:
  
 2A) DETAILS A & B BOTH SHOW A NEW ACCESSIBLE RAMP WITH
 A NEW 6 INCH STEP. A RAMP MUST BE USED, NOT A 6 INCH
 STEP. PLEASE SHOW COMPLIANCE WITH THE 2017 FBC:
 1003.5 ELEVATION CHANGE. WHERE CHANGES IN ELEVATION OF
 LESS THAN 12 INCHES EXIST IN THE MEANS OF EGRESS,
 SLOPED SURFACES SHALL BE USED. WHERE THE SLOPE IS
 GREATER THAN ONE UNIT VERTICAL IN 20 UNITS HORIZONTAL
 (5-PERCENT SLOPE), RAMPS COMPLYING WITH SECTION 1012
 SHALL BE USED. WHERE THE DIFFERENCE IN ELEVATION IS 6
 INCHES OR LESS, THE RAMP SHALL BE EQUIPPED WITH EITHER
 HANDRAILS OR FLOOR FINISH MATERIALS THAT CONTRAST WITH
 ADJACENT FLOOR FINISH MATERIALS.
  
 ACCESSIBILITY CODE SECTION 303.2 VERTICAL. CHANGES IN
 LEVEL OF 1/4 INCH HIGH MAXIMUM SHALL BE PERMITTED TO BE
 VERTICAL. WHERE CHANGES IN LEVEL ARE PERMITTED IN FLOOR
 OR GROUND SURFACES, THEY SHALL COMPLY WITH 303.
  
 303.2 VERTICAL. CHANGES IN LEVEL OF 1/4 INCH (6.4 MM)
 HIGH MAXIMUM SHALL BE PERMITTED TO BE VERTICAL.
  
 2B) THE COVERSHEET SHOWS 4 INCH OUTSIDE DIAMETER
 BOLLARDS FOR PROTECTION OF THE PEDESTRIAN WALKWAY AND
 RAMPED SECTIONS OF THE WALKWAY. WHAT THE PLAN DOES NOT
 SHOW IS COMPLIANCE FOR HANDRAILS UNDER THE
 ACCESSIBILITY CODE SECTION:
 1014.3 HANDRAIL GRASPABILITY. REQUIRED HANDRAILS SHALL
 COMPLY WITH SECTION 1014.3.1 OR SHALL PROVIDE
 EQUIVALENT GRASPABILITY.
  
 1014.3.1 TYPE I. HANDRAILS WITH A CIRCULAR CROSS
 SECTION SHALL HAVE AN OUTSIDE DIAMETER OF NOT LESS THAN
 11/4 INCHES (32 MM) AND NOT GREATER THAN 2 INCHES (51
 MM). WHERE THE HANDRAIL IS NOT CIRCULAR, IT SHALL HAVE
 A PERIMETER DIMENSION OF NOT LESS THAN 4 INCHES (102
 MM) AND NOT GREATER THAN 61/4 INCHES (160 MM) WITH A
 MAXIMUM CROSS-SECTIONAL DIMENSION OF 21/4 INCHES (57
 MM) AND MINIMUM CROSS-SECTIONAL DIMENSION OF 1 INCH (25
 MM). EDGES SHALL HAVE A MINIMUM RADIUS OF 0.01 INCH
 (0.25 MM).
  
 1014.2 HEIGHT. HANDRAIL HEIGHT, MEASURED ABOVE STAIR
 TREAD NOSING, OR FINISH SURFACE OF RAMP SLOPE, SHALL BE
 UNIFORM, NOT LESS THAN 34 INCHES AND NOT MORE THAN 38
 INCHES.
  
 3) SHEET A-1.01:
  
 3A) THE BUILDING CODE ANALYSIS DOES NOT PROVIDE THE
 MINIMUM BUILDING TYPE FOR THIS BUILDING. PLEASE REVIEW
 THE 2017 FBC-B TABLES 504.3, 504.4 & 506.2.
  
 3B)(1) THE BUILDING CODE ANALYSIS DOES NOT PROVIDE THE
 TRAVEL DISTANCE FOR BUILDINGS/ STORIES WITH ONE EXIT OR
 ACCESS TO ONE EXIT. PLEASE REVIEW THE 2017 FBC-B TABLE
 1006.3.2(2). FOR BOTH MERCANTILE AND STORAGE OCCUPANCY
 THE TRAVEL DISTANCE FOR BUILDINGS WITH ONE EXIT IS 75
 FEET. WHEN YOU TAKE THE TRAVEL DISTANCE FROM THE
 FURTHEST POINT IN THE WALK IN COOLER TO THE FRONT DOOR
 THE TRAVEL DISTANCE IS 100 FEET. PLEASE SHOW CODE
 COMPLIANCE WILL BE ACHIEVED.
  
 3B)(2) PLEASE NOTE ON THE PROPOSED FLOOR PLAN IN THE
 UNISEX RESTROOM THE PLAN SHOWS AN EXTERIOR DOOR TO BE
 BLOCKED UP, THE INFILL IS TO MATCH THE EXISTING
 STOREFRONT. PLEASE NOTE WITHIN THIS SET OF PLANS THERE
 ARE NO DETAILS HOW THE INFILL IS TO OCCUR, AND BOND TO
 THE EXISTING CBS BLOCK WORK. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED. PLEASE SHOW COMPLIANCE WITH
 SECTION 2103.4 METAL REINFORCEMENT AND ACCESSORIES OF
 THE 2017 FBC-B, ALSO REVIEW NCMA TEK 12-2B BULLETIN ON
 JOINT REINFORCEMENT FOR CONCRETE MASONRY.
  
 3C) PLEASE PROVIDE THE OVERALL DIAGONAL DISTANCE OF THE
 BUILDING AND ONE-HALF THAT DISTANCE WOULD BE THE
 MINIMUM THE 2 REQUIRED EGRESS DOORS CAN BE APART AS PER
 SECTION 1007.1.1 OF THE 2017 FBC-B.
  
 3D) THE BUILDING CODE ANALYSIS DOES NOT PROVIDE A BREAK
 DOWN BY OCCUPANCY THE OCCUPANT LOAD FOR MERCANTILE AND
 FOR STORAGE OR THE TOTAL OCCUPANT LOAD FOR THE
 BUILDING. 2017 FBC-B TABLE 1004.1.2
  
 3E) THE BUILDING CODE ANALYSIS DOES NOT PROVIDE THE
 REQUIRED PLUMBING FIXTURE COUNT AS PER THE 2017 FBC-B
 TABLE 2902.1.
  
 3F) WALK IN COOLERS ARE UNDER A SEPARATE PERMIT, WITH
 ASSOCIATED FEES AND REVIEWS. 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE CHAPTER 1OF THE
 ADMINISTRATIVE CODE SECTION 105.1 PERMITS.
  
 3G) THE PROPOSED PLAN DOES NOT INDICATE IF THE ATM
 MACHINE IS NEW OR EXISTING, IS THIS MACHINE GO THROUGH
 THE WALL TO THE EXTERIOR? WILL A NEW OPENING IN THE
 WALL BE REQUIRED? 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 3H) THE PROPOSED FLOOR PLAN DOES INDICATE THE SERVICE/
 CASHIERS COUNTER IS EXISTING, NO INFORMATION IS GIVEN.
 COMPLIANCE WITH SERVICE COUNTERS CANNOT BE ESTABLISHED
 AT THIS TIME. SEE THE 2017 ACCESS. CODE:
  
 CHECK WRITING SURFACES. 904.3.3. CHECK WRITING
 SURFACES. WHERE PROVIDED, CHECK WRITING SURFACES SHALL
 COMPLY WITH 902.3.
  
 WORK SURFACES. 902.3 HEIGHT. THE TOPS OF WORK SURFACES
 SHALL BE 28 INCHES MINIMUM AND 34 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND.
  
 DISPROPORTIONATE COST. PLEASE PROVIDE A LETTER EITHER
 FROM THE CONTRACTOR OR DESIGNER OF RECORD ON THEIR
 LETTERHEAD WHERE UP TO 20 % OF THE CONTRACT VALUE IS
 GOING TO BE SPENT IN ACCESSIBLE UPGRADES TO THE
 PROJECT. IF ALL EXISTING CONDITIONS ARE COMPLETED
 (COMPLIED) BEFORE DISPROPORTIONATION COST IS MET A
 LETTER IS NOT REQUIRED. SHOW COMPLIANCE WITH THE:
 2017 FBC-ACCESSIBILITY CODE SECTION 202.4.1
 DISPROPORTIONATE COST. ALTERATIONS MADE TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO THE ALTERED AREA WILL BE
 DEEMED DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN
 THE COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO
 THE PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE
  
 4) SHEET A-1.03:
  
 4A) PLEASE NOTE THE CGC WILL NEED TO SUB-CONTRACT THE
 ROOFING TO A ROOFING CONTRACTOR. UNDER FLORIDA STATUTE
 489.113 (3)(G) NO GENERAL, BUILDING OR RESIDENTIAL
 CONTRACTOR CERTIFIED AFTER 1973 SHALL ACT AS, HOLD
 HIMSELF OR HERSELF OUT TO BE OR ADVERTISE HIMSELF OR
 HERSELF TO BE A ROOFING CONTRACTOR UNLESS HE OR SHE IS
 CERTIFIED OR REGISTERED AS A ROOFING CONTRACTOR.
  
 4B) THE DETAIL 03 THE PROPOSED ROOFING PLAN DOES
 PROVIDE A MIAMI-DADE NOTICE OF ACCEPTANCE (NOA) NUMBER
 15-1008.01 WHICH IS EXPIRED. THERE IS A NEWER NOA FOR A
 REPLACEMENT, NOA: 15-1020.06 WHICH EXPIRES ON
 11/06/2023. THIS NOA IS COMPRISED OF 112 PAGES.
  
 4C) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 4D) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-02-25 Cont ID  
Sent By jpearson Date 2020-02-25 Time 11:13 Rev Time 0.00
Received By jpearson Date 2020-02-25 Time 11:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-01-31 Cont ID  
Sent By jpearson Date 2020-01-31 Time 09:12 Rev Time 0.00
Received By jpearson Date 2020-01-31 Time 06:55 Sent To  
Notes
2020-01-31 07:42:15CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3 (NOT PROVIDED.)
 2. FIRE ALARM, LOW VOLTAGE SYSTEMS, DAS, LIGHTNING
 PROTECTION, GENERATORS, COMMERCIAL HOOD SYSTEMS, WALK
 IN COOLERS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND PLAN SUBMITTALS FOR ANY
 OF THESE SYSTEMS PRESENT. WPB FBC 105.1, 107.2.1 (NOT
 PROVIDED.)
 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10 (NOT
 PROVIDED.)
 4. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 (NOT PROVIDED.)
 5. CORRECTED.
 6. PROVIDE COMPLIANCE WITH NEC 514.11 AND 514.13. (NOT
 PROVIDED.)
 7. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94 (NOT PROVIDED.)
  
 NEW COMMENT:
  
 8. PROVIDE GFCI PROTECTION FOR DRINKING FOUNTAIN. THE
 GFCI DEVICE MUST BE READILY ACCESSIBLE. NEC 422.5,
 422.52
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-11-14 Cont ID  
Sent By jpearson Date 2019-11-14 Time 12:39 Rev Time 0.00
Received By jpearson Date 2019-11-14 Time 10:36 Sent To  
Notes
2019-11-14 11:22:35CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
 2. FIRE ALARM, LOW VOLTAGE SYSTEMS, DAS, LIGHTNING
 PROTECTION, GENERATORS, COMMERCIAL HOOD SYSTEMS, WALK
 IN COOLERS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND PLAN SUBMITTALS FOR ANY
 OF THESE SYSTEMS PRESENT. WPB FBC 105.1, 107.2.1
 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10
 4. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 5. ALL RECEPTACLE OUTLETS WITHIN 6 FEET OF A SINK
 REQUIRE GFCI PROTECTION. PROVIDE CORRECTION. NEC 210.8
 6. PROVIDE COMPLIANCE WITH NEC 514.11 AND 514.13.
 7. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-02-12 Cont ID  
Sent By pleduc Date 2020-02-12 Time   Rev Time 0.00
Received By pleduc Date 2020-02-12 Time 15:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-01-28 Cont ID  
Sent By pleduc Date 2020-01-28 Time   Rev Time 0.00
Received By pleduc Date 2020-01-28 Time 10:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-10-31 Cont ID  
Sent By pleduc Date 2019-10-31 Time   Rev Time 0.00
Received By pleduc Date 2019-10-31 Time 15:30 Sent To  
Notes
2019-10-31 15:45:12THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 1.01 - THERE IS AN INCOREECT EDITION OF THE
 CURRENT FLORIDA FIRE PREVENTION CODE; 5TH.
  
 THE CURRENT EDTION IS THE 6TH.
  
 PLEASE REVIEW AND CORRECT AND ENSURE COMPLAINCE.
  
  
 2) SHEET A 1.01 - THERE IS ONLY ONE EXIT INDICATED FROM
 THIS PROPOSED MERCANTILE OCCUPANCY.
  
 PER NFPA 101, CH 36, NEW MERCANTILE OCCUPANCIES
  
 36.2.4 NUMBER OF MEANS OF EGRESS.
 36.2.4.1 MEANS OF EGRESS SHALL COMPLY WITH ALL OF THE
 FOLLOWING,
 EXCEPT AS OTHERWISE PERMITTED BY 36.2.4.2 THROUGH
 36.2.4.5:
 (1) THE NUMBER OF MEANS OF EGRESS SHALL BE IN
 ACCORDANCE WITH
 SECTION 7.4.
 (2) NOT LESS THAN TWO SEPARATE EXITS SHALL BE PROVIDED
 ON EVERY
 STORY.
 (3) NOT LESS THAN TWO SEPARATE EXITS SHALL BE
 ACCESSIBLE FROM
 EVERY PART OF EVERY STORY.
 36.2.4.2 EXIT ACCESS, AS REQUIRED BY 36.2.4.1(3), SHALL
 BE PERMITTED
 TO INCLUDE A SINGLE EXIT ACCESS PATH FOR THE DISTANCES
 PERMITTED AS
 COMMON PATHS OF TRAVEL BY 36.2.5.3.
 36.2.4.3 A SINGLE MEANS OF EGRESS SHALL BE PERMITTED IN
 A CLASS C
 MERCANTILE OCCUPANCY, PROVIDED THAT THE TRAVEL DISTANCE
 TO THE EXIT
 OR TO A MALL PEDESTRIAN WAY (SEE 36.4.4.2) DOES NOT
 EXCEED 75 FT
 (23 M).
  
 THE DISTANCE IS NOT PROVIDED, PLEASE PROVIDE THE TRAVLE
 DISTANCE FROM THE REMOTE AREA WITHIN COMPLIANCE OR
 CORRECT WITH A 2ND EXIT.
  
  
  
 3) SHEET A 1.01 OR OTHERS - THERE IS NO INDICATIONS OF
 A DOOR SCHEDULE INCLUDING ALL HARDWARE AND
 LOCKS/LATCHES.
  
 PER NFPA 101, CH 7, MEANS OF EGRESS
  
 7.2 MEANS OF EGRESS COMPONENTS.
 7.2.1 DOOR OPENINGS.
 7.2.1.1 GENERAL.
 7.2.1.1.1 A DOOR ASSEMBLY IN A MEANS OF EGRESS SHALL
 CONFORM TO
 THE GENERAL REQUIREMENTS OF SECTION 7.1 AND TO THE
 SPECIAL
 REQUIREMENTS OF 7.2.1.
 7.2.1.1.2 EVERY DOOR OPENING AND EVERY PRINCIPAL
 ENTRANCE THAT IS
 REQUIRED TO SERVE AS AN EXIT SHALL BE DESIGNED AND
 CONSTRUCTED SO
 THAT THE PATH OF EGRESS TRAVEL IS OBVIOUS AND DIRECT.
 WINDOWS THAT,
 BECAUSE OF THEIR PHYSICAL CONFIGURATION OR DESIGN AND
 THE MATERIALS
 USED IN THEIR CONSTRUCTION, HAVE THE POTENTIAL TO BE
 MISTAKEN FOR
 DOOR OPENINGS SHALL BE MADE INACCESSIBLE TO THE
 OCCUPANTS BY
 BARRIERS OR RAILINGS.
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR
 LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO
 ELEVATED
 TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON
 LABORATORY
 FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A
 TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM
 THE EGRESS
 SIDE.
 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3
 SHALL NOT
 APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH
 23.
 7.2.1.5.5 KEY-OPERATED LOCKS.
 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE
 PERMITTED TO HAVE
 KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED THAT
 ALL OF THE
 FOLLOWING CRITERIA ARE MET:
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43 FOR
 THE SPECIFIC OCCUPANCY.
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN.
 (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS
 FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF:
 THIS
 DOOR TO REMAIN UNLOCKED WHEN THE
 BUILDING IS OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE
 AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE
 BUILDING WHEN IT IS LOCKED.
  
 PLEASE PROVIDE IN COMPLIANCE WITH THE APPLICABLE CODE.
  
  
  
 4) SHEET C 1.0 - THERE IS AN INDICATIONS OF A RAILING
 WITH NO HANDRAIL ON THE OPPISITE SIDE.
  
 PER NFPA 101, CH 7
  
 7.2.2.4.1 HANDRAILS.
 7.2.2.4.1.1 STAIRS AND RAMPS SHALL HAVE HANDRAILS ON
 BOTH SIDES,
 UNLESS OTHERWISE PERMITTED IN 7.2.2.4.1.5 OR
 7.2.2.4.1.6.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2020-02-25 Time   Rev Time 0.00
Received By lmarchan Date 2020-02-10 Time 14:22 Sent To  
Notes
2020-02-11 14:23:06B21

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-02-03 Cont ID  
Sent By rmcphers Date 2020-02-03 Time 16:01 Rev Time 0.00
Received By rmcphers Date 2020-01-24 Time 13:57 Sent To  
Notes
2020-02-04 10:16:11TO JESMITH
2020-02-03 08:28:35B10
2020-01-27 13:57:48B10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-11-18 Cont ID  
Sent By cpuell Date 2019-11-18 Time 12:47 Rev Time 0.00
Received By cpuell Date 2019-10-28 Time 14:44 Sent To  
Notes
2019-10-29 14:44:46B02

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-11-04 Cont ID  
Sent By jwitmer Date 2019-11-04 Time 15:13 Rev Time 0.00
Received By jwitmer Date 2019-11-04 Time 14:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-02-12 Cont ID  
Sent By ccole Date 2020-02-12 Time 13:28 Rev Time 0.00
Received By ccole Date 2020-02-12 Time 11:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-01-28 Cont ID  
Sent By ccole Date 2020-01-28 Time 14:06 Rev Time 0.00
Received By ccole Date 2020-01-28 Time 12:37 Sent To  
Notes
2020-01-28 14:22:031ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19101431
 1/28/2020
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) A MECHANICAL SUB-PERMIT APPLICATION HAS BEEN
 SUBMITTED FOR INSTALLATION OF A WALK-IN COOLER AND
 REFRIGERATION SYSTEM, HOWEVER A SEPARATE PRIMARY PERMIT
 IS REQUIRED FOR THAT PORTION OF THE PROJECT. CONCERNING
 THE MASTER PERMIT FOR THE PROJECT, A MECHANICAL
 SUB-PERMIT IS REQUIRED FOR THE NEW AC SYSTEM AND BATH
 EXHAUST FAN- SECTION 107.1 WPB.
  
 2) THE $8700.00 JOB VALUE ON THE MASTER PERMIT MUST BE
 INCREASED TO REFLECT THE COSTS OF THE NEW HVAC SYSTEMS-
 SECTION 109.3 WPB.
  
 3) SHOW THE O/A DUCT AND DAMPER LOCATIONS ON THE PLAN
 AND PROVIDE DETAILS- SECTION C403.2.4.3 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-10-31 Cont ID  
Sent By ccole Date 2019-10-31 Time 11:02 Rev Time 0.00
Received By ccole Date 2019-10-31 Time 10:57 Sent To  
Notes
2019-10-31 11:23:361ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19101431
 10/31/2019
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A-1.01: PROVIDE A DUCT LAYOUT PLAN SHOWING ALL
 REQUIRED AC DUCT ALTERATIONS TO ACCOMODATE THE NEW ROOM
 CONFIGURATIONS AND RELOCATION OF THE AC CLOSET- SECTION
 603 FBC M.
  
 2) A-101: CLARIFY IF THE NEW AC CLOSET WILL HAVE AN
 OPEN RETURN THROUGH A LOUVERED DOOR AND INDICATE THE
 TYPE OF DOOR. PLEASENOTE A NON-COMBUSTIBLE DOOR IS
 REQUIRED SEE SECTION 602 FBC M.
  
 3) A-101: PROVIDE AN EXHAUST VENTILATION SYSTEM FOR THE
 NEW TOILET RIOOM- TABLE 403.3.1.1 FBC M.
  
 4) THE $13,500 JOB VALUE APPEARS LOW FOR THE SCOPE OF
 THE MECHANICAL WORK. PLEASE PROVIDE A COPIES OF THE
 SIGNED CONTRACT, AND/OR ESTIMATES, INVOICES ETC. TO
 VERIFY THE TOTAL COST OF LABOR, MATERIAL, AND
 EQUIPMENT- SECTION 109.3 WPB.
  
 5) A-104: CLARIFY HOW THE CONDENSER IS BEING BOLTTED TO
 THE SLAB IN THE DETAIL. IT APPEARS THERE ARE NO
 ANCHORING CLIPS- SECTION 301.15 FBC M.
  
 6) A-104: THE NEW WALKIN COOLER SHALL BE IN COMPLIANCE
 WITH SECTION C403.2.16 FBC EC ITEMS 1, 2, 3, 6-11
 LISTED BELOW. PLEASE PROVIDE DRAWINGS, DETAILS, AND
 SPECIFICATIONS TO VERIFY COMPLIANCE.
  
 C403.2.16 WALK-IN COOLERS AND WALK-IN FREEZERS.
  
 SITE-ASSEMBLED OR SITE-CONSTRUCTED WALK-IN COOLERS AND
 WALK-IN FREEZERS SHALL COMPLY WITH THE FOLLOWING:
  
 1.AUTOMATIC DOOR CLOSERS SHALL BE PROVIDED THAT FULLY
 CLOSE WALK-IN DOORS THAT HAVE BEEN CLOSED TO WITHIN 1
 INCH (25 MM) OF FULL CLOSURE.
  
 EXCEPTION: CLOSERS ARE NOT REQUIRED FOR DOORS MORE THAN
 45 INCHES (1143 MM) IN WIDTH OR MORE THAN 7 FEET (2134
 MM) IN HEIGHT.
  
 2.DOORWAYS SHALL BE PROVIDED WITH STRIP DOORS,
 CURTAINS, SPRING-HINGED DOORS OR OTHER METHOD OF
 MINIMIZING INFILTRATION WHEN THE DOORS ARE OPEN.
  
 3.WALLS SHALL BE PROVIDED WITH INSULATION HAVING A
 THERMAL RESISTANCE OF NOT LESS THAN R-25, CEILINGS
 SHALL BE PROVIDED WITH INSULATION HAVING A THERMAL
 RESISTANCE OF NOT LESS THAN R-25 AND DOORS OF WALK-IN
 COOLERS AND WALK-IN FREEZERS SHALL BE PROVIDED WITH
 INSULATION HAVING A THERMAL RESISTANCE OF NOT LESS THAN
 R-32.
  
 EXCEPTION: INSULATION IS NOT REQUIRED FOR GLAZED
 PORTIONS OF DOORS OR AT STRUCTURAL MEMBERS ASSOCIATED
 WITH THE WALLS, CEILING OR DOOR FRAME.
  
 6.TRANSPARENT REACH-IN DOORS FOR AND WINDOWS IN OPAQUE
 WALK-IN COOLER DOORS SHALL BE DOUBLE-PANE
 HEAT-REFLECTIVE TREATED GLASS HAVING THE INTERSTITIAL
 SPACE GAS FILLED.
  
 7.EVAPORATOR FAN MOTORS THAT ARE LESS THAN 1 HP (0.746
 KW) AND LESS THAN 460 VOLTS SHALL BE ELECTRONICALLY
 COMMUTATED MOTORS OR 3-PHASE MOTORS.
  
 8.CONDENSER FAN MOTORS THAT ARE LESS THAN 1 HP (0.746
 KW) IN CAPACITY SHALL BE OF THE ELECTRONICALLY
 COMMUTATED OR PERMANENT SPLIT CAPACITOR-TYPE OR SHALL
 BE 3-PHASE MOTORS.
  
 EXCEPTION: FAN MOTORS IN WALK-IN COOLERS AND WALK-IN
 FREEZERS COMBINED IN A SINGLE ENCLOSURE GREATER THAN
 3,000 SQUARE FEET (279 M2) IN FLOOR AREA ARE EXEMPT.
  
 9.ANTISWEAT HEATERS THAT ARE NOT PROVIDED WITH
 ANTISWEAT HEATER CONTROLS SHALL HAVE A TOTAL DOOR RAIL,
 GLASS AND FRAME HEATER POWER DRAW NOT GREATER THAN 7.1
 W/FT2(76 W/M2) OF DOOR OPENING FOR WALK-IN FREEZERS,
 AND NOT GREATER THAN 3.0 W/FT2(32 W/M2) OF DOOR OPENING
 FOR WALK-IN COOLERS.
  
 10.ANTISWEAT HEATER CONTROLS SHALL BE CAPABLE OF
 REDUCING THE ENERGY USE OF THE ANTISWEAT HEATER AS A
 FUNCTION OF THE RELATIVE HUMIDITY IN THE AIR OUTSIDE
 THE DOOR OR TO THE CONDENSATION ON THE INNER GLASS
 PANE.
  
 11.LIGHT SOURCES SHALL HAVE AN EFFICACY OF NOT LESS
 THAN 40 LUMENS PER WATT, INCLUDING ANY BALLAST LOSSES,
 OR SHALL BE PROVIDED WITH A DEVICE THAT AUTOMATICALLY
 TURNS OFF THE LIGHTS WITHIN 15 MINUTES OF WHEN THE
 WALK-IN COOLER OR WALK-IN FREEZER WAS LAST OCCUPIED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-02-19 Cont ID  
Sent By gjohnson Date 2020-02-19 Time 13:06 Rev Time 0.00
Received By gjohnson Date 2020-02-19 Time 13:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-02-04 Cont ID  
Sent By jesmith Date 2020-02-04 Time 14:21 Rev Time 0.00
Received By jesmith Date 2020-02-04 Time 14:20 Sent To  
Notes
2020-01-28 15:19:20PLUMBING COMMENTS: APPROVED
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-11-08 Cont ID  
Sent By gjohnson Date 2019-11-08 Time 11:21 Rev Time 0.00
Received By gjohnson Date 2019-11-08 Time 11:21 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2020-02-14 Cont ID  
Sent By awooten Date 2020-02-14 Time   Rev Time 0.00
Received By awooten Date 2020-02-14 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-01-31 Cont ID  
Sent By awooten Date 2020-01-31 Time   Rev Time 0.00
Received By awooten Date 2020-01-31 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-11-18 Cont ID  
Sent By awooten Date 2019-11-18 Time   Rev Time  
Received By awooten Date 2019-11-18 Time   Sent To  
Notes
***NONE***