Plan Review Details - Permit 19101346
Plan Review Stops For Permit 19101346
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-12-11 Cont ID  
Sent By jleahy Date 2019-12-11 Time 15:45 Rev Time 0.00
Received By jleahy Date 2019-12-11 Time 15:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-11-12 Cont ID  
Sent By jleahy Date 2019-11-12 Time 15:50 Rev Time 0.00
Received By jleahy Date 2019-11-12 Time 15:50 Sent To  
Notes
2019-11-12 15:52:06NEED TO SATISFY MECHANICAL COMMENTS FOR AN ELECTRICAL
 PASS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-12-13 Time   Rev Time 0.00
Received By lmarchan Date 2019-12-03 Time 15:21 Sent To  
Notes
2019-12-04 15:21:47RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-11-12 Cont ID  
Sent By jleahy Date 2019-11-12 Time 15:52 Rev Time 0.00
Received By jleahy Date 2019-10-25 Time 13:41 Sent To  
Notes
2019-10-28 13:41:22MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-12-13 Cont ID  
Sent By ccole Date 2019-12-13 Time 07:53 Rev Time 0.00
Received By ccole Date 2019-12-13 Time 07:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2019-11-07 Time   Rev Time 0.00
Received By ccole Date 2019-11-07 Time 13:41 Sent To E
Notes
2019-11-07 14:31:381ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19101346
 11/7/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SIGNATURE OF THE CONTRACTOR SHALL BE ON THE
 A/C-1 PLAN- SECTION 107.2.1 WPB: ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS AND ACCOMPANYING DATA SHALL
 BEAR THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN.
  
 2) THE SUBMITTAL DOCUMENT FOR THE MIAMI TECH INC.
 BRACKET HAS GENERIC ENGINEERING AND LIMITATIONS OF USE
 BASED ON PRESSURES AND LOCATION. THE DOCUMENT IS NOT A
 FLORIDA PRODUCT APPROVAL OR MIAM-DADE NOA AND MUST BEAR
 THE ORIGINAL SIGNATURE AND SEAL OF THE ENGINEER OF
 RECORD- SECTION 61G15-23.002 FAC. PLEASE SHOW THE
 LOCATION OF THE CU AND BRACKET INSTALLATION AND PROVIDE
 DESIGN PRESSURES AND INSTALLATION DETAILS PREPARED BY A
 FLORIDA REGISTERED ENGINEER- SECTION 1609 FBC B AND
 SECTION 107.1 WPB. PLEASE SEE GENERAL NOTE #1 ON THJE
 SUBMITTAL WHICH INDICATES SITE-SPECIFIC ENGINEERING MAY
 BE REQUIRED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  