Plan Review Details - Permit 19101343
Plan Review Stops For Permit 19101343
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-11-18 Cont ID  
Sent By pvalenti Date 2019-11-18 Time 13:49 Rev Time 0.00
Received By pvalenti Date 2019-11-18 Time 13:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-11-21 Cont ID  
Sent By jleahy Date 2019-11-21 Time 12:21 Rev Time 0.00
Received By jleahy Date 2019-11-21 Time 12:21 Sent To  
Notes
2019-11-21 12:25:50FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) PAGE E-101
  
 RISER SHOWS A TAP IN THE PANEL LOCATED IN THE KITCHEN
 WHICH STATES NO MAIN. TAP IS 10' OR LESS ACCORDING TO
 THE NOTE ON THE PAGE.
 WITH NO MAIN THESE CONDUCTORS WILL BE SERVICE
 CONDUCTORS AND CODE DOES NOT ALLOW SERVICE ENTRANCE
 CONDUCTORS TO BE RUN INSIDE OF THE BUILDING.
 PLEASE EXPLAIN HOW CONDUCTORS AR TO BE PROTECTED INSIDE
 BUILDING WITH OUT OCP PROTECTION.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-11-21 Cont ID  
Sent By jleahy Date 2019-11-21 Time 12:25 Rev Time 0.00
Received By jleahy Date 2019-10-25 Time 13:42 Sent To  
Notes
2019-10-28 13:42:58ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status F Date 2019-10-30 Cont ID  
Sent By hmtribou Date 2019-10-30 Time 12:09 Rev Time 0.00
Received By hmtribou Date 2019-10-30 Time 12:09 Sent To B
Notes
2019-10-30 12:10:50ACCOUNT HAS A HOUSING AND COMMUNITY DEVELOPMENT HOLD
 AND CODE COMPLIANCE HOLD ON IT.