Plan Review Details - Permit 19101246
Plan Review Stops For Permit 19101246
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2019-10-30 Cont ID  
Sent By pvalenti Date 2019-10-30 Time 11:40 Rev Time 0.00
Received By pvalenti Date 2019-10-30 Time 11:40 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2019-10-29 Cont ID  
Sent By jwitmer Date 2019-10-29 Time 07:48 Rev Time 0.00
Received By jwitmer Date 2019-10-29 Time 06:04 Sent To  
Notes
2019-10-29 07:46:38HIGH RISE BUILT IN 1985.
 , ASBESTOS COMMERCIAL: PLEASE PROVIDE A SIGNED
 ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD,
 STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF
 ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF
 HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT
 NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL
 INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE
 FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/_DOCUMENTS/ASBESTOS-
 NOTIFICATION-FORM-PBC-FILLABLE-UPDATE-07-30-2015.PDF
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-11-12 Cont ID  
Sent By rmcdouga Date 2019-11-12 Time 09:23 Rev Time 0.00
Received By rmcdouga Date 2019-11-08 Time 17:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-10-29 Cont ID  
Sent By jwitmer Date 2019-10-29 Time 07:45 Rev Time 0.00
Received By jwitmer Date 2019-10-29 Time 06:05 Sent To  
Notes
2019-10-29 07:45:022017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19101246
 ADD: 1555 PALM BEACH LAKES BLVD. SUITE # 1400
 CONT: VERDEX CONSTRUCTION, INC.
 TEL: 561-756-6409
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. OCT. 29TH/ 2019
 ACTION: DENIED
  
 1A) THE LIFE SAFETY PLAN 002_ALS1.1 AND SHEET
 003_A1.1.1 THE NUMBERING SYSTEM FOR ALL ROOMS DOES NOT
 CORRELATE FROM PAGE TO PAGE. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED, DISCREPANCY IN THE PLANS.
  
 1B) THE LIFE SAFETY PLAN 002_ALS1.1 SHOWS TRAVEL
 DISTANCES TO (2) EXITS. THE PLAN DOES SHOW THE OVERALL
 DIAGONAL DISTANCE OF THE OFFICE SPACE, ALSO THE
 REQUIRED 1/3RD DIAGONAL DISTANCE APART OF 31 FEET 1
 INCH AND THE ACTUAL DIAGONAL DISTANCE THE 2 EXITS ARE
 APART 47 FEET 7 INCHES.
  
 THE ISSUE IS THE DESIGNER OF RECORD HAS SHOWN 2 MEANS
 OF EGRESS. THE SECOND MEANS OF EGRESS THAT GOES THROUGH
 ROOM 1400.9 IS A FILE STORAGE ROOM. PLEASE REVIEW
 SECTION 1016.2 EGRESS THROUGH INTERVENING ROOMS (5)
 EGRESS SHALL NOT PASS THROUGH STORAGE ROOMS, CLOSETS OR
 SPACES USED FOR SIMILAR PURPOSES.
  
 PLEASE MEASURE YOUR COMMON PATH OF TRAVEL FROM THE MOST
 REMOTE POINT OF THE FILE STORAGE ROOM 1400.12 FOR
 TRAVEL DISTANCE TO THE FRONT EGRESS DOORS OF THE OFFICE
 SPACE. I MEASURED THE DISTANCE TO APPROXIMATELY 85
 FEET.
 REVIEW TABLE 1006.2.1 SPACES WITH ONE EXIT OR EXIT
 ACCESS DOORWAY. THE MAXIMUM COMMON PATH OF TRAVEL FOR A
 FIRE SPRINKLERED BUILDING WITH AN OCCUPANT LOAD OF LESS
 THAN 30 FOR A BUSINESS OCCUPANCY WILL ALLOW YOU 100
 FEET OF COMMON PATH OF TRAVEL. PLEASE ADJUST PLANS
 ACCORDINGLY. IF QUESTIONS PLEASE GIVE ME A CALL.
  
 1C) SHEET 003_A.1.1. AS LABELED ON THE FLOOR PLAN,
 ENTRY DOOR TO THE STORAGE ROOM 1400.9 (LIFE SAFETY
 SHEET ROOM 1400.1.2.). THERE IS NO DEMO PLAN PROVIDED
 IN THIS SET OF PLANS TO KNOW IF THIS DOOR IS EXITING
 AND OR IF NEW. PLEASE NOTE THIS ISSUE HAS COME UP
 BEFORE IN PLAN REVIEW WITH THIS DESIGNER. WHOSE DOOR IS
 THIS, UNDER MANAGEMENT OR THE TENANT? WHAT IS THE
 STANDARD FOR THIS BUILDING? THIS DOOR DOES NOT COMPLY
 WITH THE:
  
 2017 FBC-ACCESSIBILITY CODE MANEUVERING CLEARANCES.
 DOORS. MINIMUM MANEUVERING CLEARANCES AT DOORS AND
 GATES SHALL COMPLY WITH 404.2.4 (A). MANEUVERING
 CLEARANCES SHALL EXTEND THE FULL WIDTH OF THE DOORWAY
 AND THE REQUIRED LATCH SIDE FOR SIDE CLEARANCE. THIS
 DOOR AS SHOWN DOES NOT HAVE 18 INCHES ON THE LATCH
 SIDE.
  
 1D) UNDER COMMENT 1C) IF THE DOOR TO THE STORAGE ROOM
 1400.9 (FLOOR PLAN) 1004.1.2(LIFE SAFETY PLAN) IS UNDER
 THE CONTROL OF THE TENANT AND IS EXISTING THEN
 DISPROPORTIONATE COST CAN KICK IN, UP TO 20 % OF THE
 VALUE OF WORK PERFORMED UNDER THIS PERMIT CAN GO TO
 ACCESSIBLE UPGRADES OR $16,000.00 OF VALUE IN MAKING
 THIS TENANT SPACE 100% ACCESSIBLE.
  
 2017 ACCESSIBILITY CODE SECTION 202.4.1
 DISPROPORTIONATE COST. ALTERATIONS MADE TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO THE ALTERED AREA WILL BE
 DEEMED DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN
 THE COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO
 THE PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 2) THE SECOND ISSUE CAN BE FOUND ON SHEET 008_A3.1.1.
 THE HEIGHT OF THE RECEPTION DESK THE OVERALL HEIGHT OF
 THE RECEPTION DESK IS GIVEN AT 3 FEET 6 INCHES TALL.
 PLEASE REVIEW SECTION 904.3.3 OF THE 2017 ACCESSIBILITY
 CODE. WHERE PROVIDED, CHECK WRITING SURFACES SHALL
 COMPLY WITH 902.3. 404.2.4 902.3 HEIGHT. THE TOPS OF
 AND WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-10-29 Cont ID  
Sent By jpearson Date 2019-10-29 Time 09:32 Rev Time 0.00
Received By jpearson Date 2019-10-29 Time 06:42 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2019-10-29 Cont ID  
Sent By jpearson Date 2019-10-29 Time 09:56 Rev Time 0.00
Received By jpearson Date 2019-10-29 Time 09:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-11-12 Cont ID  
Sent By pleduc Date 2019-11-12 Time   Rev Time 0.00
Received By pleduc Date 2019-11-12 Time 12:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-11-07 Cont ID  
Sent By pleduc Date 2019-11-07 Time   Rev Time 0.00
Received By pleduc Date 2019-11-07 Time 09:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-11-12 Cont ID  
Sent By shill Date 2019-11-12 Time 13:42 Rev Time 0.00
Received By shill Date 2019-11-07 Time 06:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-11-07 Cont ID  
Sent By cpuell Date 2019-11-07 Time 10:00 Rev Time 0.00
Received By cpuell Date 2019-10-29 Time 06:04 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-10-29 Cont ID  
Sent By jwitmer Date 2019-10-29 Time 07:42 Rev Time 0.00
Received By jwitmer Date 2019-10-29 Time 06:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-10-29 Cont ID  
Sent By ccole Date 2019-10-29 Time 11:21 Rev Time 0.00
Received By ccole Date 2019-10-29 Time 10:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-11-07 Cont ID  
Sent By shill Date 2019-11-07 Time 07:22 Rev Time 0.00
Received By shill Date 2019-10-29 Time 11:26 Sent To  
Notes
2019-11-07 07:24:19REVIEWED REMOTELY BY TIM HUNT
 APPROVED WITH THE FOLLOWING REDLINES/PROVISO:
  
 INSTANTANEOUS WATER HEATER CONNECTIONS FOR PUBLIC
 LAVATORIES, P0.1, CROSSED OFF.
  
 BREAKROOM SINK SHALL NOT BE TEMPERED BELOW 110F,
 FBC-PLB 607.1
  
 TANKLESS SHALL BE SIZED TO PRODUCE HOT WATER @ THE
 DESIGN GPM OF THE FAUCET MANUFACTURE. SLOWING THE WATER
 FLOW DOWN WILL NOT BE ALLOWED.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-11-12 Cont ID  
Sent By rmcdouga Date 2019-11-12 Time 08:45 Rev Time 0.00
Received By rmcdouga Date 2019-11-12 Time 08:44 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2019-10-31 Cont ID  
Sent By pvalenti Date 2019-10-31 Time 06:45 Rev Time 0.00
Received By pvalenti Date 2019-10-31 Time 06:45 Sent To  
Notes
2019-10-29 11:22:10MECH SHEETS OK.
2019-10-29 07:52:25ARCHITECTURAL SHEETS CHECKED FOR ELECTRONIC SIGNATURE
 AND SEAL, GOOD. J. W.
2019-10-29 06:56:22ELECTRICAL SHEETS GOOD.

Review Stop Z ZONING
Rev No 1 Status P Date 2019-11-01 Cont ID  
Sent By rfalcone Date 2019-11-01 Time 14:37 Rev Time 0.00
Received By rfalcone Date 2019-11-01 Time 14:37 Sent To I
Notes
2019-11-01 14:37:3111/1/19 PASSED. RF
  
 NO EXTERIOR MODIFICATIONS BEING MADE.