Plan Review Details - Permit 19101216
Plan Review Stops For Permit 19101216
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2019-12-18 Cont ID  
Sent By lcrespo Date 2019-12-18 Time 18:13 Rev Time 0.00
Received By lcrespo Date 2019-12-18 Time 18:13 Sent To  
Notes
2019-12-18 18:13:3612/18/19 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 2:00 PM TO 5:00 PM
 [email protected]
 561-701-6437
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-10-25 Cont ID  
Sent By lcrespo Date 2019-10-25 Time 07:11 Rev Time 0.00
Received By lcrespo Date 2019-10-25 Time 07:11 Sent To  
Notes
2019-10-25 07:12:1010/25/19 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON
 PLANS IN FULL, NUMBER, STREET, CITY, STATE AND ZIP CODE
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 2. GAS RISER DIAGRAM REQUIRED WPB AMENDMENTS TO THE FBC
 SEC. 107.3.5.3 (12) RESIDENTIAL GAS
 3. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1' OF
 EITHER SIDE (IF APPICABLE) SHUTOFF VALVES AND DRIP LEGS
 PER THE 2017 FBC RES. SEC G2421.2 OR 2017 FBC FG SEC
 410.2.
 4. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS-STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 (CLOTHES DRYERS) OR 2017 FBC RES. SEC. G2407.1 AND
 G2439.4 (CLOTHES DRYERS).
 6. THE DELIVERY PRESSURE IS NOT 7" W.C. PLEASE INDICATE
 THE DELIVERY PRESSURE (PSI) OF THE SYSTEM ON THE PLAN
 PER 2017 FBC RES. SEC. G2413.2.
 7. SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2017 FBC RES. SEC. G2408.1.
 PLEASE NOTE THAT GENERATOR MAY HAVE THE WRONG BTU'S ,
 IF USING A GENERAC THE TOTAL IS 327 BTU'S AS NEW SPECS
 FOR 2018 ARE AVAILABLE ONLINE AND THE TOTAL IS
 INCORRECT.
 8. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2017
 FBC FG SECS. 402.2 AND 301.3 OR 2017 FBC RES. SEC.
 G2413.2 AND G2404.3.
 9. THE GENERATOR SHALL BE ONE FOOT SIX INCHES (1'-6")
 FROM THE HOUSE, FIVE (5'-0") FROM THE PROPERTY LINE,
 EXHAUST SHALL BE TEN (10?-0?) FROM ANY OPENING UNLESS
 OTHERWISE STATED IN THE MANUFACTURES SPECIFICATION
 INSTRUCTIONS. PLEASE SHOW LOCATION DISTANCE ON YOUR
 FLAT DRAWING.
 10. THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON
 THE APPLICATION, PLEASE PROVIDE A BONA FIDE SIGNED
 CONTRACT. WPB AMENDMENTS TO THE FBC 109.3. BUILDING
 PERMITS VALUATIONS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-12-18 Cont ID  
Sent By lcrespo Date 2019-12-18 Time 18:13 Rev Time 0.00
Received By lcrespo Date 2019-12-17 Time 14:05 Sent To  
Notes
2019-12-18 14:05:58RESUB ROUTED TO LCRESPO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-10-25 Cont ID  
Sent By lcrespo Date 2019-10-25 Time 07:13 Rev Time 0.00
Received By lcrespo Date 2019-10-23 Time 15:43 Sent To  
Notes
2019-10-24 15:44:03PLUMB<5K