Plan Review Details - Permit 19101209
Plan Review Stops For Permit 19101209
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2019-11-04 Cont ID  
Sent By jwitmer Date 2019-11-04 Time 08:49 Rev Time 0.00
Received By jwitmer Date 2019-11-04 Time 06:20 Sent To  
Notes
2019-11-04 08:48:56YEAR BUILT: 2018.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-11-26 Cont ID  
Sent By dbattles Date 2019-11-26 Time 09:07 Rev Time 0.00
Received By dbattles Date 2019-11-26 Time 08:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-11-04 Cont ID  
Sent By jwitmer Date 2019-11-04 Time 08:46 Rev Time 0.00
Received By jwitmer Date 2019-11-04 Time 05:45 Sent To  
Notes
2019-11-04 08:46:302017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19101209
 ADD: 2602 S. DIXIE HWY.
 CONT: RMS CONSTRUCTION
 TEL: 561-290-9920
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. NOV. 04TH/ 2019
 ACTION: DENIED
  
 1) THE ARCHITECTURAL SHEET A-1 SHOWS THE MEN?S AND
 LADIES RESTROOMS. THE PLUMBING SHEET P-1 SHOWS A CODE
 COMPLIANT DETAIL OF A RESTROOM BUT NOT A DETAIL OF THE
 EXACT LAYOUT, DOOR LOCATION NOR SIZE OF THE RESTROOM
 FROM ON SHEET A-1. AN OVER RESTROOM LAYOUT WITH
 DIMENSIONS AND DOOR LOCATION ARE REQUIRED TO DETERMINE
 COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY CODE
 SECTIONS:
  
 604.3.1 SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE
 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM
 THE REAR WALL.
  
 604.3.2 OVERLAP. THE REQUIRED CLEARANCE AROUND THE
 WATER CLOSET SHALL BE PERMITTED TO OVERLAP THE WATER
 CLOSET, ASSOCIATED GRAB BARS, DISPENSERS, SANITARY
 NAPKIN DISPOSAL UNITS, COAT HOOKS, SHELVES, ACCESSIBLE
 ROUTES, CLEAR FLOOR SPACE AND CLEARANCES REQUIRED AT
 OTHER FIXTURES, AND THE TURNING SPACE. NO OTHER
 FIXTURES OR OBSTRUCTIONS SHALL BE LOCATED WITHIN THE
 REQUIRED WATER CLOSET CLEARANCE.
  
 2) SHEET A-1 DOES NOT INDICATE A NEW RTU UNIT TO BE
 INSTALLED BUT M-1 NOTE # 2 DOES INDICATE THE
 INSTALLATION OF A NEW 7.5 TON RTU. PLEASE SHOW ON
 EITHER THE ARCHITECTURAL SHEETS OR STRUCTURAL SHEET THE
 PENETRATION OF THE ROOF DECK (PROVIDE SIZE AND
 LOCATION), THE REINFORCEMENT OF THE ROOF FRAMING FOR
 THE POINT LOADING OF THE FRAMING MEMBERS, AND THE
 ANCHORING DETAIL FOR THE ROOF TOP CURB AS WELL AS THE
 RTU TO THE CURB. PLEASE ALSO PROVIDE THE WIND DESIGN
 CRITERIA AND LATERAL PRESSURES TO BE RESISTED.
  
 2A) 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1 OF THE ADMINISTRATIVE CODE
 SECTION 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
 2B) 2017 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND
 SPEED, VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 2. RISK CATEGORY.
  
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE
 1609.7.2. HEIGHT AND EXPOSURE.
  
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
  
 6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 7. FBC-B 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 2C) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(D) ROOFING PRODUCTS AND OR ROOF TOP CURB UNITS.
  
 2D) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 2E) WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION. IN ACCORDANCE WITH THE AMERICAN WELDING
 SOCIETY.
 2017 FBC-B 2204.1 WELDING (ADDITIONAL ROOF FRAMING
 MEMBERS TO BAR JOIST)
 2017 FBC-B 2204.2 BOLTING.
 IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS
 FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING
 INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU.
  
 2F) LATERAL FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP
 EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 3) BUILDING PROVISO: PLEASE NOTE THE WALK IN COOLER AND
 HOOD AND SUPPRESSION SYSTEM ARE TO UNDER SEPARATE
 PERMIT, FEES AND REVIEW. NOT KNOWN AT THIS TIME IF THE
 WALK IN COOLER WILL REQUIRE A ROOF TOP CONDENSER THAT
 WOULD ALSO NEED TO SHOW COMPLIANCE WITH
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(G) PRE-ENGINEERED A/C STANDS
  
 ROOF TOP A/C STAND PRODUCT APPROVAL WILL NEED TO BE
 REVIEWED BY THE DESIGNER OF RECORD. PLEASE IDENTIFY THE
 FOLLOWING REQUIREMENTS CALCULATING THE AREA (SIDE VIEW)
 OF THE ROOF TOP COMPRESSORS, CONFIGURATION ON STAND,
 THE MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS,
 WEIGHT, CIRCLED THE DESIGN PARAMETERS IN THE TABLES,
 ANCHORS AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE
 STAND AND THE STAND TO THE ROOF. THE PRODUCT APPROVAL
 IS TO BE REVIEWED BY THE DESIGNER OF RECORD, APPROVED
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-11-06 Cont ID  
Sent By jpearson Date 2019-11-06 Time 14:30 Rev Time 0.00
Received By jpearson Date 2019-11-05 Time 11:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-10-31 Cont ID  
Sent By pleduc Date 2019-10-31 Time   Rev Time 0.00
Received By pleduc Date 2019-10-31 Time 14:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-12-11 Time   Rev Time 0.00
Received By lmarchan Date 2019-12-05 Time 15:26 Sent To  
Notes
2019-12-06 15:26:48RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-11-26 Cont ID  
Sent By dbattles Date 2019-11-26 Time 09:08 Rev Time 0.00
Received By dbattles Date 2019-11-18 Time 14:44 Sent To  
Notes
2019-11-19 14:44:35B11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-11-07 Cont ID  
Sent By jesmith Date 2019-11-07 Time 13:32 Rev Time 0.00
Received By jesmith Date 2019-11-07 Time 13:32 Sent To  
Notes
2019-10-24 16:21:05B11

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2019-12-16 Cont ID  
Sent By jwitmer Date 2019-12-16 Time 10:57 Rev Time 0.00
Received By jwitmer Date 2019-12-16 Time 10:57 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-11-04 Cont ID  
Sent By jwitmer Date 2019-11-04 Time 08:47 Rev Time  
Received By jwitmer Date 2019-11-04 Time 05:45 Sent To  
Notes
2019-11-04 08:47:11IMPACT FEES- PAPER SUBMITTALS. PLANS REQUIRE REVIEW BY
 THE PBC IMPACT FEE OFFICE. CALL (561) 233-5025. UPON
 APPROVAL, YOU MAY CHECK OUT ONE PLAN SET AND TAKE TO
 THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED AND
 WITH A COPY OF THE RECEIPT AS APPLICABLE. PLEASE
 PROVIDE THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 THE PBC IMPACT FEE OFFICE. THE FORM CAN BE FOUND AT:
 HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPAC
 TFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-12-11 Cont ID  
Sent By ccole Date 2019-12-11 Time 08:21 Rev Time 0.00
Received By ccole Date 2019-12-11 Time 07:31 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-11-20 Cont ID  
Sent By ccole Date 2019-11-20 Time 14:06 Rev Time 0.00
Received By ccole Date 2019-11-20 Time 11:58 Sent To  
Notes
2019-11-20 14:23:091ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19101209
 11/20/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) M-1: PLEASE REFER TO TABLE 403.3.1.1: THE O/A
 VENTILATION RATE FOR DINING ROOMS IS CALCULATED AT 70
 PERSONS PER 1000 SF AT 7.5 CFMS PER PERSON + 0.18 CFMS
 PER SF. PLEASE CORRECT THE CALCULATION.
  
 2) THE REVISED AC CALULATIONS ARE INCORRECTLY LISTING
 THE PROJECT LOCATION AS ST. LUCIE WEST- PLEASE CORRECT.
  
 3) THE REVISED AC CALCULATIONS SHOW LIGHTING WATTAGE AT
 1413 (SEE ROOM INPUT ON PAGE 4), HOWEVER THE REVISED
 COMCHECK INTERIOR LIGHTING COMPLIANCE INDICATES 977
 WATTS. PLEASE NOTE THAT THE LIGHTING POWER DENSITIES
 ARE INDICATED AT 1253 WATTS ON E-1.
  
 4) THE ARCHITECT OF RECORD SHALL PROVIDE AN APPROVAL
 STAMP ON THE CORRECTED COMCHECK COMPLIANCE REPORT-
 SECTION 107.2.1 WPB. PLEASE INFORM ALTMAN BROTHERS LLC.
 THAT THEIR CONTRACTOR REGISTRATION WITH THE CITY OF WPB
 HAS EXPIRED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-10-25 Cont ID  
Sent By ccole Date 2019-10-25 Time 14:17 Rev Time 0.00
Received By ccole Date 2019-10-25 Time 11:17 Sent To  
Notes
2019-10-25 14:48:471ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19101209
 10/25/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) M-1: AN EXHAUST VENTILATION SYSTEM SIZED AT A RATE
 OF .7 CFMS PER SQ. FT. IS REQUIRED FOR THE KITCHEN, AND
 RECIRCULATION OF AIR FROM THE KITCHEN INTO THE DINING
 ROOM IS PROHIBITED- TABLE 403.3.1.1 FBC M.
  
 2) THE AC CALCULATIONS DO NOT SHOW ANY BTUH LOADS FOR
 PEOPLE- SECTION C403.2.1 FBC EC.
  
 3) SHOW THE LOCATION OF THE NEW RTU ON THE ROOF AND
 REQUIRED CLEARANCE DISTANCES TO EXHAUST OUTLETS, VENTS
 ETC- SECTION 401.4 FBC M.
  
 4) PROVIDE STRUCTURAL ENGINEERING FOR THE ROOF OPENING,
 INSTALLATION OF THE CURB, AND MOUNTING OF THE RTU-
 SECTION 301.15 FBC M.
  
 5) PLEASE NOTE THAT A SEPARATE PERMIT IS REQUIRED FOR
 THE WALK IN COOLER- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-11-22 Cont ID  
Sent By gjohnson Date 2019-11-22 Time 11:57 Rev Time 0.00
Received By gjohnson Date 2019-11-22 Time 09:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-11-07 Cont ID  
Sent By jesmith Date 2019-11-07 Time 13:22 Rev Time 0.00
Received By jesmith Date 2019-11-07 Time 07:47 Sent To  
Notes
2019-11-07 13:22:47CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
  
 NOTE: A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS
 AS REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1. PER WPB FBC 107.2.1, ARCHITECT SHALL PROVIDE FOR
 RESTROOMS, RESTROOM LAYOUT WITH DIMENSIONS AND DOOR
 LOCATION ARE REQUIRED TO DETERMINE COMPLIANCE WITH THE
 2017 FBC-ACCESSIBILITY CODE SECTIONS.
 2. RE: A-1; ADA RESTROOM ELEVATIONS. PER FBC ACC 604.2,
 THE CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES
 (405 MM) MINIMUM TO 18 INCHES (455 MM) MAXIMUM FROM THE
 SIDE WALL OR PARTITION. PER WPB FBC 107.2.1, SHOW THE
 SAME.
 3. RE: A-1; ADA RESTROOM ELEVATIONS. PER FBC ACC 604.7,
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. PER WPB FBC 107.2.1,
 SHOW THE SAME.
 4. RE: PLAN SHEET P-1: PLUMBING NOTE 5: PER WPB FBC
 107.2.1 AND 107.3.5.1.3, CLEARLY SPECIFY THE TYPE
 POLYETHYLENE PIPING AND FITTINGS USED FOR WATER
 DISTRIBUTION CITING FBC PL TABLES 605.4 AND 605.5; LIST
 THE APPLICABLE STANDARD(S) OR CHANGE NOTE TO REQUIRE
 WATER DISTRIBUTION MATERIALS TO COMPLY WITH FBC PL
 TABLES 605.4 AND 605.5.
 5. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE GREASE
 INTERCEPTOR SPECIFICATION/CUT SHEETS. ELIMINATE DRY
 HORIZONTAL VENTS FROM 3 COMPARTMENT SINK DETAIL. THE GC
 HAS STATED THAT THE INTERCEPTOR WILL BE SET ON TOP OF
 THE SLAB, NOT IN IT. IF THIS IS THE CASE, PLEASE REVISE
 THE 3 COMPARTMENT SINK DETAIL TO REFLECT.
 6. PLEASE REFER TO UNDERGROUND PLUMBING REVIEW PERMIT
 #19090446, ISSUED 10/29/19. PLAN SHEET P-1;
 A) PLUMBING PROVISO FOR FUTURE VENT. PROVISO STATES
 HORIZONTAL DRY VENT NOT PERMITTED PER FBC PL
 903.3-903.4. P-1 THIS PERMIT IS STILL SHOWING THE
 PROHIBITED HORIZONTAL DRY VENT. REMOVE TO COMPLY.
 B) FLOOR SINKS FOR EQUIPMENT 8 AND 26 HAVE ADDED
 UNDERGROUND PIPING ON P-1 THIS PERMIT, WHICH APPEARS TO
 BE HORIZONTAL DRY VENTS. COMPLY WITH FBC PL
 903.3-903.4.
 C) IT IS NOTED THAT THE USE OF A POINT OF USE GREASE
 INTERCEPTOR AT THE FUTURE THREE COMPARTMENT SINK WAS
 APPROVED AND A WHOLE HOUSE INTERCEPTOR IS NOT REQUIRED.
 7. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE PLAN
 VIEW LAYOUT FOR COLD AND HOT WATER DISTRIBUTION; PLEASE
 NOTE THAT PER FBC PL 607.2, DEVELOPED LENGTH OF HOT
 WATER PIPING THAT EXCEEDS 50 FEET SHALL REQUIRE A
 RECIRCULATING SYSTEM OR HEAT TRACE SYSTEM WHICH
 COMPLIES WITH FBC PL 607.2.1 THROUGH 607.2.2.2.
 8. PER WPB FBC 107.2.1 AND 107.3.5.1.3, SHOW
 CALCULATIONS FOR AND CLEARLY SIZE THE COLD AND HOT
 WATER DISTRIBUTION.
 9. PER WPB FBC 107.2.1 AND 107.3.5.1.3, CLEARLY
 INDICATE THE DELIVERY TEMPERATURE OF THE HOT WATER
 DISTRIBUTION.
 10. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE AND
 SPECIFY AND LOCATE BACKFLOW PREVENTERS TO COMPLY WITH
 FBC PL 608.1, FOR THE WATER SERVICE, ICE MAKER(S),
 COFFEE MAKER(S) AND EXPRESSO MACHINES(S).
 11. PER WPB FBC 107.2.1, PROVIDE WATER HEATER SCHEDULE
 NOTING MANUFACTURER, MODEL NUMBER, ELECTRICAL
 CHARACTERISTICS, NOTE WHETHER OR NOT, IT COMES WITH
 INTEGRAL HEAT TRAPS AND ENERGY PERFORMANCE EFFICIENCY
 AS REQUIRED BY FBC EC C404.2.
 12. PLAN SHEETS A-1, E-1 AND P-1 SHOWS A 50 GALLON
 WATER HEATER. P-2 SHOWS A 30 GALLON WATER HEATER.
 PLEASE CLARIFY. PER WPB FBC 107.2.1 AND 107.3.5.1.3,
 PROVIDE DETAIL FOR WATER HEATER MOUNTED ON SHELF ABOVE
 THE MOP SINK; IN ACCORDANCE WITH THE REQUIREMENTS OF
 FBC PL SECTIONS 503, 504 AND FBC PL 607.3, SHOW
 REQUIRED SHUT OFF AND RELIEF VALVES, EXPANSION TANK
 SHALL BE SIZED, HEAT TRAPS IF NOT INTEGRAL TO THE WATER
 HEATER, SIZED T & P DISCHARGE TO HUB DRAIN WITH
 REQUIRED AIR GAP (OR TO PAN WITH REQUIRED AIR GAP), PAN
 (SPECIFY MATERIAL TO COMPLY WITH FBC PL 504.7), SIZED
 PAN DRAIN TO IT?S POINT OF TERMINATION. RELIEF PIPING
 AND PAN DRAIN PIPING TO BE OF MATERIALS ALLOWED BY FBC
 PL TABLES 605.4 AND 605.5.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 AS THE PLANS ARE NOT SIGNED AND SEALED BY A
 PROFESSIONAL ENGINEER OR ARCHITECT, THE PLUMBING PLAN
 SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE
 DESIGNER PER WPB FBC 107.2.1.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19101209 2602 S DIXIE HWY