Plan Review Details - Permit 19101052
Plan Review Stops For Permit 19101052
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-10-25 Cont ID  
Sent By rmcdouga Date 2019-10-25 Time 14:48 Rev Time 0.00
Received By rmcdouga Date 2019-10-25 Time 14:48 Sent To  
Notes
2019-10-25 13:55:59CONDITIONAL APPROVAL
  
 RICHARD GATHRIGHT AND MYSELF CONDUCTED A SITE VISIT ON
 10/25/19 AND FOUND THAT MOST OF THE ITEMS HAD BEEN
 CORRECTED. IN LIEU OF THE FIRE SPRINKLER SYSTEM AND
 FIRE ALARM REQUIREMENTS, THE OWNER/OPERATOR OF THE
 TEMPORARY (ONE WEEK) HAUNTED HOUSE ATTRACTION HAS
 AGREED TO LIMIT THE NUMBER OF PERSONS THAT WILL BE IN
 THE BUILDING AT ONE TIME AS SET BY THE CITY FIRE
 DEPARTMENT, HAVE TWO SECURITY GUARDS POSTED AT THE
 FRONT AND TWO AT THE REAR EXISTS, HAVE THE EIGHT STAFF
 MEMBERS TRAINED IN SAFETY PROCEDURES WITH CITY FIRE
 DEPARTMENT STAFF PRESENT AND AGREED TO HAVE THE CITY
 FIRE DEPARTMENT PERIODICALLY MONITOR THE OPERATIONS.
  
 THE FOLLOWING ITEMS SHALL BE ADDRESSED PRIOR TO
 OPENING.
 1) THE FIRE DEPARTMENT'S REQUIREMENTS.
 2) THE EAST EXIT FROM THE NORTH ROOM OF THE BUILDING TO
 THE SOUTH ROOM IS REQUIRED TO HAVE AN ACCESSIBLE RAMP.
 3) PLACE A DIRECTIONAL EXIT SIGN ON THE EAST WALL NEAR
 THE CENTER OF THE FRONT ROOM TO DIRECT OCCUPANTS TO THE
 REAR EXITS. THE REAR EXIT SIGNS ARE NOT VISIBLE IN THIS
 AREA.
 4) NO SMOKING IS TO BE ALLOWED IN THE ATTRACTION. PLACE
 SIGN AT ENTRANCE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-10-24 Cont ID  
Sent By rmcdouga Date 2019-10-24 Time 15:49 Rev Time 0.00
Received By rmcdouga Date 2019-10-24 Time 14:36 Sent To  
Notes
2019-10-24 14:53:15PLAN REVIEW COMMENTS
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 THE FOLLOWING ARE THE 2017 FLORIDA BUILDING CODE
 REQUIREMENTS FOR A HAUNTED HOUSE ATTRACTION.
 FBC SECTION 202 DEFINITIONS. SPECIAL AMUSEMENT
 BUILDING. A SPECIAL AMUSEMENT BUILDING IS ANY TEMPORARY
 OR PERMANENT BUILDING OR PORTION THEREOF THAT IS
 OCCUPIED FOR AMUSEMENT, ENTERTAINMENT OR EDUCATIONAL
 PURPOSES AND THAT CONTAINS A DEVICE OR SYSTEM THAT
 CONVEYS PASSENGERS OR PROVIDES A WALKWAY ALONG, AROUND
 OR OVER A COURSE IN ANY DIRECTION SO ARRANGED THAT THE
 MEANS OF EGRESS PATH IS NOT READILY APPARENT DUE TO
 VISUAL OR AUDIO DISTRACTIONS OR IS INTENTIONALLY
 CONFOUNDED OR IS NOT READILY AVAILABLE BECAUSE OF THE
 NATURE OF THE ATTRACTION OR MODE OF CONVEYANCE THROUGH
 THE BUILDING OR STRUCTURE.
  
 FBC CHAPTER 4 SPECIAL DETAILED REQUIREMENTS BASED ON
 USE AND OCCUPANCY SPECIAL AMUSEMENT BUILDINGS
 1) 411.1 GENERAL.
 SPECIAL AMUSEMENT BUILDINGS HAVING AN OCCUPANT LOAD OF
 50 OR MORE SHALL COMPLY WITH THE REQUIREMENTS FOR THE
 APPROPRIATE GROUP A OCCUPANCY AND SECTIONS 411.1
 THROUGH 411.8. SPECIAL AMUSEMENT BUILDINGS HAVING AN
 OCCUPANT LOAD OF LESS THAN 50 SHALL COMPLY WITH THE
 REQUIREMENTS FOR A GROUP B OCCUPANCY AND SECTIONS 411.1
 THROUGH 411.8.
 EXCEPTION: SPECIAL AMUSEMENT BUILDINGS OR PORTIONS
 THEREOF THAT ARE WITHOUT WALLS OR A ROOF AND
 CONSTRUCTED TO PREVENT THE ACCUMULATION OF SMOKE NEED
 NOT COMPLY WITH THIS SECTION.
 FOR FLAMMABLE DECORATIVE MATERIALS, SEE THE FLORIDA
 FIRE PREVENTION CODE.
  
 411.2 DEFINITION. THE FOLLOWING TERM IS DEFINED IN
 CHAPTER 2: SPECIAL AMUSEMENT BUILDING.
  
 2) NOT ADDRESSED. [F]411.3 AUTOMATIC FIRE DETECTION.
 SPECIAL AMUSEMENT BUILDINGS SHALL BE EQUIPPED WITH AN
 AUTOMATIC FIRE DETECTION SYSTEM IN ACCORDANCE WITH
 SECTION 907.
  
 3) NOT ADDRESSED. [F]411.4 AUTOMATIC SPRINKLER SYSTEM.
 SPECIAL AMUSEMENT BUILDINGS SHALL BE EQUIPPED
 THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 903.3.1.1. WHERE THE SPECIAL
 AMUSEMENT BUILDING IS TEMPORARY, THE SPRINKLER WATER
 SUPPLY SHALL BE OF AN APPROVED TEMPORARY MEANS.
 EXCEPTION: AUTOMATIC SPRINKLERS ARE NOT REQUIRED WHERE
 THE TOTAL FLOOR AREA OF A TEMPORARY SPECIAL AMUSEMENT
 BUILDING IS LESS THAN 1,000 SQUARE FEET (93 M2) AND THE
 EXIT ACCESS TRAVEL DISTANCE FROM ANY POINT TO AN EXIT
 IS LESS THAN 50 FEET (15 240 MM).
  
 4) NOT ADDRESSED. [F]411.5 ALARM.
 ACTUATION OF A SINGLE SMOKE DETECTOR, THE AUTOMATIC
 SPRINKLER SYSTEM OR OTHER AUTOMATIC FIRE DETECTION
 DEVICE SHALL IMMEDIATELY SOUND AN ALARM AT THE BUILDING
 AT A CONSTANTLY ATTENDED LOCATION FROM WHICH EMERGENCY
 ACTION CAN BE INITIATED INCLUDING THE CAPABILITY OF
 MANUAL INITIATION OF REQUIREMENTS IN SECTION
 907.2.12.2.
  
 5) NOT ADDRESSED. [F]411.6 EMERGENCY VOICE/ALARM
 COMMUNICATIONS SYSTEM.
 AN EMERGENCY VOICE/ALARM COMMUNICATIONS SYSTEM SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTIONS 907.2.12 AND
 907.5.2.2, WHICH IS ALSO PERMITTED TO SERVE AS A PUBLIC
 ADDRESS SYSTEM AND SHALL BE AUDIBLE THROUGHOUT THE
 ENTIRE SPECIAL AMUSEMENT BUILDING.
  
 6) TO BE ADDRESSED. VERIFY IN FIELD. 411.7 EXIT
 MARKING.
 EXIT SIGNS SHALL BE INSTALLED AT THE REQUIRED EXIT OR
 EXIT ACCESS DOORWAYS OF AMUSEMENT BUILDINGS IN
 ACCORDANCE WITH THIS SECTION AND SECTION 1013. APPROVED
 DIRECTIONAL EXIT MARKINGS SHALL ALSO BE PROVIDED. WHERE
 MIRRORS, MAZES OR OTHER DESIGNS ARE UTILIZED THAT
 DISGUISE THE PATH OF EGRESS TRAVEL SUCH THAT THEY ARE
 NOT APPARENT, APPROVED AND LISTED LOW-LEVEL EXIT SIGNS
 THAT COMPLY WITH SECTION 1013.5, AND DIRECTIONAL PATH
 MARKINGS LISTED IN ACCORDANCE WITH UL 1994, SHALL BE
 PROVIDED AND LOCATED NOT MORE THAN 8 INCHES (203 MM)
 ABOVE THE WALKING SURFACE AND ON OR NEAR THE PATH OF
 EGRESS TRAVEL. SUCH MARKINGS SHALL BECOME VISIBLE IN AN
 EMERGENCY. THE DIRECTIONAL EXIT MARKING SHALL BE
 ACTIVATED BY THE AUTOMATIC FIRE DETECTION SYSTEM AND
 THE AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH
 SECTION 907.2.12.2.
  
 7) NOT APPLICABLE. 411.7.1 PHOTOLUMINESCENT EXIT SIGNS.
 WHERE PHOTOLUMINESCENT EXIT SIGNS ARE INSTALLED,
 ACTIVATING LIGHT SOURCE AND VIEWING DISTANCE SHALL BE
 IN ACCORDANCE WITH THE LISTING AND MARKINGS OF THE
 SIGNS.
  
 8) VERIFY IN FIELD. 411.8 INTERIOR FINISH. THE INTERIOR
 FINISH SHALL BE CLASS A IN ACCORDANCE WITH SECTION
 803.1.
  
 IN ADDITION TO THE ABOVE REQUIREMENTS PLEASE PROVIDE
 THE FOLLOWING INFORMATION.
  
 9) COMPLIED. SPECIFY THE SIZE OF THE AREA THAT WILL BE
 USED FOR THE HAUNTED HOUSE.
  
 10) COMPLIED. THE LOCATIONS AND NUMBER OF EXITS.
 SPECIFY THE CLEAR OPENING SIZES OF EACH OF THEM.
  
 11) COMPLIED. VERIFY THAT PANEL ARE STRUCTURALLY
 SECURED IN PLACE IN THE FIELD AT INSPECTION. (SPECIFY
 THE NUMBER, SIZE, LENGTH AND TYPE OF FASTENERS THAT
 WILL BE USED TO ATTACH THE PLYWOOD TO THE 2X4S AND TO
 ATTACH THE 2X4S TO THE CEILING JOISTS/RAFTERS.) PROVIDE
 DETAILS/DRAWINGS SHOWING HOW THE PLYWOOD WITH WOOD BEAM
 SUPPORTS WILL BE CONSTRUCTED AND ATTACHED TO THE
 STRUCTURE.
  
 12) COMPLIED. VERIFY IN FIELD. NOTE: THE RAMPS SHALL
 HAVE A RUNNING SLOPE NOT STEEPER THAN 1:12 PER FBC
 ACCESSIBILITY 405.2. PER FBC ACCESSIBILITY 303.3
 CHANGES IN LEVEL BETWEEN 1/4" HIGH MINIMUM AND 1/2"
 HIGH MAXIMUM SHALL BE BEVELED WITH A SLOPE NOT STEEPER
 THAN 1:2. THE RAMP CAN NOT HAVE A 3/4" LIP. FBC(CONFIRM
 THAT THE ENTRANCE AND ROUTE THROUGH THE ATTRACTION IS
 STABLE, FIRM, SLIP RESISTANT AND LEVEL, RUNNING SLOPE
 NOT STEEPER THAN 1:20. THE CLEAR WIDTH OF WALKING
 SURFACES SHALL BE 36 INCHES MINIMUM. WHERE THE
 ACCESSIBLE ROUTE MAKES A 180 DEGREE TURN THE CLEAR
 WIDTH SHALL BE 42 INCHES MINIMUM APPROACHING THE TURN,
 48 INCHES MINIMUM AT THE TURN AND 42 INCHES MINIMUM
 LEAVING THE TURN.) FBC ACCESSIBILITY CHAPTER 4 REQUIRES
 AN ACCESSIBLE ENTRANCE, ROUTE THROUGH AND EXIT FROM THE
 ATTRACTION.
  
 13) NOT ADDRESSED. (EXPLAIN HOW THE CURTAIN WILL BE
 OPENED IN AN EMERGENCY. WILL THEY BE OPENED
 AUTOMATICALLY BY SOME TYPE OF MOTOR OR WILL THEY DEPEND
 ON SOMEONE TO PHYSICALLY OPEN THEM. INDICATE HOW THE
 CURTAINS WILL BE HUNG. WILL THEY BE HUNG FROM SOME TYPE
 OF CURTAIN ROD OR A TRACK? WILL THE EXIT SIGNS BE
 VISIBLE OVER THE TOP OF THEM? PLEASE PROVIDE SPECIFIC
 DETAILS.) HOW PROVIDE DETAILS/DRAWINGS TO SHOW HOW THE
 FIREPROOF CURTAINS WILL BE HUNG AND HOW THEY WILL BE
 OPENED IN AN EMERGENCY.
  
 14) COMPLIED. INDICATE THE LOCATIONS OF THE BATHROOMS
 FOR STAFF.
  
 15) TO BE ADDRESSED. VERIFY IN FIELD. (THE DRAWINGS
 SHOW THE EXIT SIGNS ON THE WRONG SIDE OF THE WALL
 BETWEEN THE NORTH AND SOUTH ROOMS. CLARIFY HOW THE
 SIGNS WILL REMAIN VISIBLE WHEN THE CURTAINS, WOOD
 PANELS AND DECORATIONS ARE IN PLACE.) THE EXIT SIGNS
 NEED TO BE VISIBLE AND CAN NOT BE BLOCKED FROM VIEW.
  
 16) NOT ADDRESSED. NOT SPECIFIED ON DRAWINGS. (SHOW THE
 LOCATIONS OF EMERGENCY LIGHTS ON THE DRAWINGS.)
 EMERGENCY LIGHTING WITH BATTERY BACKUP SHALL BE
 PROVIDED IN ALL ROOMS, AREAS AND EXIT PATHWAYS.
  
 17) NEED FIRE DEPARTMENT TO APPROVE THE TEST REPORT.
 NEED SHIPPING LABEL OR FABRIC TAG TO VERIFY IN FIELD.
 (SUBMIT THE MANUFACTURER'S FIREPROOFING
 INFORMATION/TEST REPORTS FOR THE CURTAINS, FABRICS,
 DECORATIONS AND FURNISHINGS.) ALL FURNISHINGS AND
 DECORATIONS (INCLUDING ALL DRAPERIES AND CURTAINS) ARE
 REQUIRED TO BE FLAME RESISTANT.
  
 18) COMPLIED. SHOW THE LOCATION OF ELECTRICAL PANELS
 AND LIGHTING CONTROLS.
  
 19) NOT ALL ITEMS HAVE BEEN ADDRESSED. (PROVIDE THE
 EXPERIENCE AND TRAINING OF THE TWO SECURITY GUARDS THAT
 WILL BE EMPLOYED. SPECIFY WHO WILL BE RESPONSIBLE FOR
 EDUCATING THE ACTORS ON EMERGENCY PROCEDURES. SPECIFY
 HOW THE "LIGHT EFFECTS" WILL BE TURNED OFF AND WHO WILL
 DO SO. ARE THEY ALL CONNECTED TO A SINGLE SWITCH OR
 MULTIPLY SWITCHES IN THE SAME LOCATION? SPECIFY HOW THE
 EXISTING BUILDING LIGHTS WILL BE TURNED ON AND BY WHOM.
 ARE THEY ALL CONNECTED TO A SINGLE SWITCH OR MULTIPLY
 SWITCHES IN THE SAME LOCATION? HOW MANY MEGAPHONES WILL
 BE PROVIDED AND WHO WILL HAVE THEM? WHAT IS A BLOW HORN
 AND HOW WILL IT BE USED TO NOTIFY PEOPLE OF AN
 EMERGENCY SITUATION?) SUBMIT A WRITTEN EMERGENCY
 PROCEDURE PLAN.
  
 20) NOT ADDRESSED. FBC 107.2.1 - INFORMATION ON
 CONSTRUCTION DOCUMENTS. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
  
 21) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-10-22 Cont ID  
Sent By rmcdouga Date 2019-10-22 Time 08:54 Rev Time 0.00
Received By rmcdouga Date 2019-10-21 Time 17:38 Sent To  
Notes
2019-10-21 17:38:20PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 THE FOLLOWING ARE THE 2017 FLORIDA BUILDING CODE
 REQUIREMENTS FOR A HAUNTED HOUSE ATTRACTION.
 FBC SECTION 202 DEFINITIONS. SPECIAL AMUSEMENT
 BUILDING. A SPECIAL AMUSEMENT BUILDING IS ANY TEMPORARY
 OR PERMANENT BUILDING OR PORTION THEREOF THAT IS
 OCCUPIED FOR AMUSEMENT, ENTERTAINMENT OR EDUCATIONAL
 PURPOSES AND THAT CONTAINS A DEVICE OR SYSTEM THAT
 CONVEYS PASSENGERS OR PROVIDES A WALKWAY ALONG, AROUND
 OR OVER A COURSE IN ANY DIRECTION SO ARRANGED THAT THE
 MEANS OF EGRESS PATH IS NOT READILY APPARENT DUE TO
 VISUAL OR AUDIO DISTRACTIONS OR IS INTENTIONALLY
 CONFOUNDED OR IS NOT READILY AVAILABLE BECAUSE OF THE
 NATURE OF THE ATTRACTION OR MODE OF CONVEYANCE THROUGH
 THE BUILDING OR STRUCTURE.
  
 FBC CHAPTER 4 SPECIAL DETAILED REQUIREMENTS BASED ON
 USE AND OCCUPANCY SPECIAL AMUSEMENT BUILDINGS
 1) 411.1 GENERAL.
 SPECIAL AMUSEMENT BUILDINGS HAVING AN OCCUPANT LOAD OF
 50 OR MORE SHALL COMPLY WITH THE REQUIREMENTS FOR THE
 APPROPRIATE GROUP A OCCUPANCY AND SECTIONS 411.1
 THROUGH 411.8. SPECIAL AMUSEMENT BUILDINGS HAVING AN
 OCCUPANT LOAD OF LESS THAN 50 SHALL COMPLY WITH THE
 REQUIREMENTS FOR A GROUP B OCCUPANCY AND SECTIONS 411.1
 THROUGH 411.8.
 EXCEPTION: SPECIAL AMUSEMENT BUILDINGS OR PORTIONS
 THEREOF THAT ARE WITHOUT WALLS OR A ROOF AND
 CONSTRUCTED TO PREVENT THE ACCUMULATION OF SMOKE NEED
 NOT COMPLY WITH THIS SECTION.
 FOR FLAMMABLE DECORATIVE MATERIALS, SEE THE FLORIDA
 FIRE PREVENTION CODE.
 411.2 DEFINITION. THE FOLLOWING TERM IS DEFINED IN
 CHAPTER 2: SPECIAL AMUSEMENT BUILDING.
  
 2) [F]411.3 AUTOMATIC FIRE DETECTION.
 SPECIAL AMUSEMENT BUILDINGS SHALL BE EQUIPPED WITH AN
 AUTOMATIC FIRE DETECTION SYSTEM IN ACCORDANCE WITH
 SECTION 907.
  
 3) [F]411.4 AUTOMATIC SPRINKLER SYSTEM.
 SPECIAL AMUSEMENT BUILDINGS SHALL BE EQUIPPED
 THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 903.3.1.1. WHERE THE SPECIAL
 AMUSEMENT BUILDING IS TEMPORARY, THE SPRINKLER WATER
 SUPPLY SHALL BE OF AN APPROVED TEMPORARY MEANS.
 EXCEPTION: AUTOMATIC SPRINKLERS ARE NOT REQUIRED WHERE
 THE TOTAL FLOOR AREA OF A TEMPORARY SPECIAL AMUSEMENT
 BUILDING IS LESS THAN 1,000 SQUARE FEET (93 M2) AND THE
 EXIT ACCESS TRAVEL DISTANCE FROM ANY POINT TO AN EXIT
 IS LESS THAN 50 FEET (15 240 MM).
  
 4) [F]411.5 ALARM.
 ACTUATION OF A SINGLE SMOKE DETECTOR, THE AUTOMATIC
 SPRINKLER SYSTEM OR OTHER AUTOMATIC FIRE DETECTION
 DEVICE SHALL IMMEDIATELY SOUND AN ALARM AT THE BUILDING
 AT A CONSTANTLY ATTENDED LOCATION FROM WHICH EMERGENCY
 ACTION CAN BE INITIATED INCLUDING THE CAPABILITY OF
 MANUAL INITIATION OF REQUIREMENTS IN SECTION
 907.2.12.2.
  
 5) [F]411.6 EMERGENCY VOICE/ALARM COMMUNICATIONS
 SYSTEM.
 AN EMERGENCY VOICE/ALARM COMMUNICATIONS SYSTEM SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTIONS 907.2.12 AND
 907.5.2.2, WHICH IS ALSO PERMITTED TO SERVE AS A PUBLIC
 ADDRESS SYSTEM AND SHALL BE AUDIBLE THROUGHOUT THE
 ENTIRE SPECIAL AMUSEMENT BUILDING.
  
 6) 411.7 EXIT MARKING.
 EXIT SIGNS SHALL BE INSTALLED AT THE REQUIRED EXIT OR
 EXIT ACCESS DOORWAYS OF AMUSEMENT BUILDINGS IN
 ACCORDANCE WITH THIS SECTION AND SECTION 1013. APPROVED
 DIRECTIONAL EXIT MARKINGS SHALL ALSO BE PROVIDED. WHERE
 MIRRORS, MAZES OR OTHER DESIGNS ARE UTILIZED THAT
 DISGUISE THE PATH OF EGRESS TRAVEL SUCH THAT THEY ARE
 NOT APPARENT, APPROVED AND LISTED LOW-LEVEL EXIT SIGNS
 THAT COMPLY WITH SECTION 1013.5, AND DIRECTIONAL PATH
 MARKINGS LISTED IN ACCORDANCE WITH UL 1994, SHALL BE
 PROVIDED AND LOCATED NOT MORE THAN 8 INCHES (203 MM)
 ABOVE THE WALKING SURFACE AND ON OR NEAR THE PATH OF
 EGRESS TRAVEL. SUCH MARKINGS SHALL BECOME VISIBLE IN AN
 EMERGENCY. THE DIRECTIONAL EXIT MARKING SHALL BE
 ACTIVATED BY THE AUTOMATIC FIRE DETECTION SYSTEM AND
 THE AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH
 SECTION 907.2.12.2.
  
 7) 411.7.1 PHOTOLUMINESCENT EXIT SIGNS.
 WHERE PHOTOLUMINESCENT EXIT SIGNS ARE INSTALLED,
 ACTIVATING LIGHT SOURCE AND VIEWING DISTANCE SHALL BE
 IN ACCORDANCE WITH THE LISTING AND MARKINGS OF THE
 SIGNS.
  
 8) 411.8 INTERIOR FINISH. THE INTERIOR FINISH SHALL BE
 CLASS A IN ACCORDANCE WITH SECTION 803.1.
  
 IN ADDITION TO THE ABOVE REQUIREMENTS PLEASE PROVIDE
 THE FOLLOWING INFORMATION.
  
 9) COMPLIED. SPECIFY THE SIZE OF THE AREA THAT WILL BE
 USED FOR THE HAUNTED HOUSE.
  
 10) COMPLIED. THE LOCATIONS AND NUMBER OF EXITS.
 SPECIFY THE CLEAR OPENING SIZES OF EACH OF THEM.
  
 11) MORE INFORMATION IS REQUIRED. (SPECIFY THE NUMBER,
 SIZE, LENGTH AND TYPE OF FASTENERS THAT WILL BE USED TO
 ATTACH THE PLYWOOD TO THE 2X4S AND TO ATTACH THE 2X4S
 TO THE CEILING JOISTS/RAFTERS.) PROVIDE
 DETAILS/DRAWINGS SHOWING HOW THE PLYWOOD WITH WOOD BEAM
 SUPPORTS WILL BE CONSTRUCTED AND ATTACHED TO THE
 STRUCTURE.
  
 12) MORE INFORMATION IS REQUIRED. (CONFIRM THAT THE
 ENTRANCE AND ROUTE THROUGH THE ATTRACTION IS STABLE,
 FIRM, SLIP RESISTANT AND LEVEL, RUNNING SLOPE NOT
 STEEPER THAN 1:20. THE CLEAR WIDTH OF WALKING SURFACES
 SHALL BE 36 INCHES MINIMUM. WHERE THE ACCESSIBLE ROUTE
 MAKES A 180 DEGREE TURN THE CLEAR WIDTH SHALL BE 42
 INCHES MINIMUM APPROACHING THE TURN, 48 INCHES MINIMUM
 AT THE TURN AND 42 INCHES MINIMUM LEAVING THE TURN.)
 FBC ACCESSIBILITY CHAPTER 4 REQUIRES AN ACCESSIBLE
 ENTRANCE, ROUTE THROUGH AND EXIT FROM THE ATTRACTION.
  
 13) MORE INFORMATION IS REQUIRED. (EXPLAIN HOW THE
 CURTAIN WILL BE OPENED IN AN EMERGENCY. WILL THEY BE
 OPENED AUTOMATICALLY BY SOME TYPE OF MOTOR OR WILL THEY
 DEPEND ON SOMEONE TO PHYSICALLY OPEN THEM. INDICATE HOW
 THE CURTAINS WILL BE HUNG. WILL THEY BE HUNG FROM SOME
 TYPE OF CURTAIN ROD OR A TRACK? WILL THE EXIT SIGNS BE
 VISIBLE OVER THE TOP OF THEM? PLEASE PROVIDE SPECIFIC
 DETAILS.) HOW PROVIDE DETAILS/DRAWINGS TO SHOW HOW THE
 FIREPROOF CURTAINS WILL BE HUNG AND HOW THEY WILL BE
 OPENED IN AN EMERGENCY.
  
 14) COMPLIED. INDICATE THE LOCATIONS OF THE BATHROOMS
 FOR STAFF.
  
 15) MORE INFORMATION IS REQUIRED. (THE DRAWINGS SHOW
 THE EXIT SIGNS ON THE WRONG SIDE OF THE WALL BETWEEN
 THE NORTH AND SOUTH ROOMS. CLARIFY HOW THE SIGNS WILL
 REMAIN VISIBLE WHEN THE CURTAINS, WOOD PANELS AND
 DECORATIONS ARE IN PLACE.) THE EXIT SIGNS NEED TO BE
 VISIBLE AND CAN NOT BE BLOCKED FROM VIEW.
  
 16) NOT SPECIFIED ON DRAWINGS. (SHOW THE LOCATIONS OF
 EMERGENCY LIGHTS ON THE DRAWINGS.) EMERGENCY LIGHTING
 WITH BATTERY BACKUP SHALL BE PROVIDED IN ALL ROOMS,
 AREAS AND EXIT PATHWAYS.
  
 17) MORE INFORMATION IS REQUIRED. (SUBMIT THE
 MANUFACTURER'S FIREPROOFING INFORMATION/TEST REPORTS
 FOR THE CURTAINS, FABRICS, DECORATIONS AND
 FURNISHINGS.) ALL FURNISHINGS AND DECORATIONS
 (INCLUDING ALL DRAPERIES AND CURTAINS) ARE REQUIRED TO
 BE FLAME RESISTANT.
  
 18) COMPLIED. SHOW THE LOCATION OF ELECTRICAL PANELS
 AND LIGHTING CONTROLS.
  
 19) MORE INFORMATION IS REQUIRED. (PROVIDE THE
 EXPERIENCE AND TRAINING OF THE TWO SECURITY GUARDS THAT
 WILL BE EMPLOYED. SPECIFY WHO WILL BE RESPONSIBLE FOR
 EDUCATING THE ACTORS ON EMERGENCY PROCEDURES. SPECIFY
 HOW THE "LIGHT EFFECTS" WILL BE TURNED OFF AND WHO WILL
 DO SO. ARE THEY ALL CONNECTED TO A SINGLE SWITCH OR
 MULTIPLY SWITCHES IN THE SAME LOCATION? SPECIFY HOW THE
 EXISTING BUILDING LIGHTS WILL BE TURNED ON AND BY WHOM.
 ARE THEY ALL CONNECTED TO A SINGLE SWITCH OR MULTIPLY
 SWITCHES IN THE SAME LOCATION? HOW MANY MEGAPHONES WILL
 BE PROVIDED AND WHO WILL HAVE THEM? WHAT IS A BLOW HORN
 AND HOW WILL IT BE USED TO NOTIFY PEOPLE OF AN
 EMERGENCY SITUATION?) SUBMIT A WRITTEN EMERGENCY
 PROCEDURE PLAN.
  
 20) FBC 107.2.1 - INFORMATION ON CONSTRUCTION
 DOCUMENTS. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 21) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2019-10-24 Cont ID  
Sent By jleahy Date 2019-10-24 Time 12:47 Rev Time 0.00
Received By jleahy Date 2019-10-24 Time 12:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-10-22 Cont ID  
Sent By jleahy Date 2019-10-22 Time 09:16 Rev Time 0.00
Received By jleahy Date 2019-10-22 Time 09:16 Sent To  
Notes
2019-10-22 09:21:04FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED TO SHOW CIRCUITS AND SIZES OF CIRCUITS ON PLANS
 215.5
  
 PANEL SCHEDULE FOR THE ELECTRICAL CIRCUITS 408.4
  
 LOCATION OF PANEL
  
 SERVICE RISER DIAGRAM. 215.5
  
 ONLY PERMITS FOR THIS SPACE IS A DEMO< HAS A DEMO BEEN
 DONE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-10-25 Cont ID  
Sent By pleduc Date 2019-10-25 Time   Rev Time 0.00
Received By pleduc Date 2019-10-25 Time 09:33 Sent To  
Notes
2019-10-25 09:45:55FIRE CONDUCTED A SITE REVIEW AT 1PM AND FOUND MOST OF
 THE CONDITIONS ADDRESSED AND ACCEPTABLE. A FLAME TEST
 ON THE WHITE AND BLACK DRAPERY MATERIAL WAS CONDUCTED
 AND PASSED. FIRE HAS ENTERED A PASS ON THE PERMIT
 REVIEW.
  
 THE FOLLOWING WILL BE REVIEWED ON SATURDAY BEFORE
 OPENING:
  
 *****A RAILING WILL BE INSTALLED AT THE REAR RAMP TO
 THE SOUTH EMERGENCY EXIT AREAS DUE TO A TRIP
 HAZARD.*****
  
 *****FIRE EXTINGUISHERS WERE NOT INSTALLED BUT WILL BE
 INSTALLED BY TOMORROW FOR REVIEW******
  
 *****THE SOUTH STORAGE EMERGENCY EXIT AREA HAS VARIOUS
 PILES OF MATERIAL THAT WILL BE MOVED TO THE SIDE WALLS
 SO THAT THAT AREA WILL BE CLEAR PRIOR TO OPENING*****
  
 ****THERE WERE VARIOUS AREAS OF CONSTRUCTION RELATED
 MATERIALS AND EXTENSION CORDS THAT WILL BE CLEARED
 PRIOR TO OPENING*****
  
 ***THE FIRE DEPARTMENT WILL HAVE FIRE INSPECTORS IN
 ATTENDANCE THROUGHOUT THE EVENING TO REVIEW THE ABOVE
 ITEMS AS WELL AS REVIEW COMPLIANCE WITH NO MORE THAN10
 PATRONS AT A TIME****
  
 ****THE FIRE DEPARTMENT AND CITY RESERVES THE RIGHT TO
 CEASE AND DESIST ALL ACTIVITY, AT ANY TIME, FOR ANY
 REASON FOUND IN VIOLATION OF THE FIRE CODE OR AN
 IMMINENT THREAT TO LIFE SAFETY.*****
  
  
  
  
 FIRE CONDUCTED A SITE REVIEW AND FOUND THE DOORS LOCKED
 AND NO RESPRESATIVE ON SITE.
  
 I HAVE REMOVED THE PASS UNDER FIRE PENDING A SITE VISIT
 AND THE FOLLOWING:
  
 ******THROUGH AVAILABE WINDOWS, IT WAS NOTED THAT A
 WHITE SHEET/CLOTH MATERIAL WAS NOTED TO BE HANGING
 THROUGHOUT THE INTERIOR AREAS. THE SUBMITTED FLAME
 RETARDENT CERTIFICATION DOES NOT COVER THAT MATERIAL
 AND IT SHALL BE REMOVED UNLESS A SPECIFIC
 CERTITIFACTION IS PROVIDED.******
  
  
  
  
  
 THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ADDRESS ALL OTHER CITY DISCIPLINE COMMENTS AND
 CONDITIONS.
  
  
  
  
 2) A SITE INSPECTIONS SHALL BE CONDUCTED TO VERIFY
 CONDITIONS AND ENSURE COMPLIANCE OF ALL APPLICABLE
 AREAS.
  
 THESE INSPECTIONS SHALL TAKE PLACE ON FIRDAY MORNING
 BEGINING AT 11 AM AND MAY CONTINUE UNTIL ALL NOTED LIFE
 SAFETY CONCERNS HAVE BEEN ADDRESSED.
  
 SITE INSPECTIONS SHALL ALSO TAKE PLACE ON SATURDAY
 AFTERNOON BEFORE ANY GUESTS WILL BE ALLOWED INSIDE AND
 AT VARIOUS TIMES DURING THE MOONFEST EVENT.
  
  
  
 3) NO MORE THAN 10 GUESTS/PATRONS/PUBLIC SHALL BE
 ALLOWED INSIDE AT ANY TIME. ONCE ALL TEN GUESTS ARE OUT
 AND ACCOUNTED FOR, 10 OTHERS SHALL BE ALLOWED TO ENTER.
  
 THIS CONDITION WILL BE STRICTLY ENFORCED, ACURATE AND
 ACTIVE COUNTS SHALL BE MAINTAINED AT ALL TIMES.
  
  
  
 4) THE FIRE DEPARTMENT AND CITY RESERVES THE RIGHT TO
 CEASE AND DESIST ALL ACTIVITY, AT ANY TIME, FOR ANY
 REASON FOUND IN VIOLATION OF THE FIRE CODE OR AN
 IMMINENT THREAT TO LIFE SAFETY.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-10-23 Cont ID  
Sent By pleduc Date 2019-10-23 Time   Rev Time 0.00
Received By pleduc Date 2019-10-23 Time 09:30 Sent To  
Notes
2019-10-23 09:57:28THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 A SITE REVIEW WAS CONDUCTED AND FOUND THE FOLLOWING
 WHICH IS NOT ADDRESS NOR INDICATED ON THE SUBMITTED
 PLAN SETS:
  
 ? PER FLORIDA ACCESSIBILITY CODE AND THE AMERICANS WITH
 DISABILITIES ACT (ADA) ALL FACILITIES SHALL BE
 ACCESSIBLE TO PERSONS WITH DISABILITIES. THE FLOOR OF
 THE BUILDING IS UNEVEN WITH SEVERAL AREAS OF DIFFERENT
 TYPES OF FLOORING MATERIALS. THE NORTH ROOM OF THE
 BUILDING HAS AREAS THAT ARE FILLED IN WITH PLYWOOD,
 SOME AREAS THAT ARE BARE CONCRETE AND OTHERS HAVE
 REMNANTS OF MUD SET TILE FLOORING. THERE ARE NUMEROUS
 TRIPPING HAZARDS AND THE FLOOR WILL NEED AN EXTENSIVE
 AMOUNT OF WORK IN ORDER TO MEET FLORIDA ACCESSIBILITY
 REQUIREMENTS FOR AN ACCESSIBLE ROUTE. THE SOUTH PORTION
 OF THE BUILDING APPEARS TO BE A NEWER ADDITION AND THE
 FLOOR ELEVATION IS APPROXIMATELY 6 TO 8 INCHES HIGHER
 THAN THE OLDER NORTH PART. THIS CHANGE IN ELEVATION
 WOULD REQUIRE ACCESSIBLE RAMPS.
 ? METAL SHORING JACKS. THE ROOF AND CEILING OF THE
 FRONT ROOM ARE WOOD FRAME AND THE LARGE WOODEN BEAM
 THAT RUNS DOWN THE CENTER OF THE NORTH ROOM IS SHORED
 UP WITH METAL SHORING JACKS THIS BEAM HAS EXTENSIVE
 TERMITE DAMAGE IN SOME AREAS. SOME OF THE CEILING
 JOISTS ALSO HAVE VISIBLE TERMITE DAMAGE. THE PROPOSED
 USE OF THE SPACE WITH LOW LIGHT LEVELS, STROBE LIGHTS,
 AND DISORIENTING SOUNDS, MAY CAUSE PATRONS TO IMPACT
 THE SHORING AND POTENTIALLY CAUSE LATERAL MOVEMENT OF
 THE SHORING AND REMOVAL OF SUPPORT FOR THE WOODEN BEAM.
 ? FLAME RETARDANT TREATMENT OF CURTAINS. FLAME
 RETARDANT TREATMENT CERTIFICATE FOR THE CURTAIN FABRIC
 MUST BE PROVIDED TO SHOW THAT THE SPREAD OF FLAME WILL
 NOT POSE UNACCEPTABLE RISK TO OCCUPANTS AS THEY LEAVE
 THE BUILDING IN AN EMERGENCY. THIS IS THE SAME
 REQUIREMENT THAT APPLIES TO TENTS.
 ? PLYWOOD PANEL WALLS ATTACHMENT TO CEILING JOISTS. WE
 COULD NOT DETERMINE HOW THE 2X4S THAT SUPPORT THE
 PLYWOOD PANEL WALLS ARE ATTACHED TO THE CEILING JOISTS.
 WE WERE ABLE TO MOVE ONE OF THE WALLS BY PUSHING ON IT
 WITH VERY LITTLE FORCE. THE PROPOSED USE OF THE SPACE
 WITH LOW LIGHT LEVELS, STROBE LIGHTS, AND DISORIENTING
 SOUNDS, MAY CAUSE PATRONS TO IMPACT THE PLYWOOD WALL
 PANELS AND POTENTIALLY DETACH THEM FROM THE CEILING
 JOISTS AND CAUSE THE WALL PANELS TO FALL. ALSO, THE
 CEILING JOISTS WERE NOT INTENDED TO CARRY THE TORQUE
 (TWISTING) FORCE OF A 12 FOOT LONG LEVER WITH A PERSON
 RUNNING INTO IT.
 ? IN THE EVENT OF AN EMERGENCY THE LIGHTING MUST TURN
 ON AND PROVIDE SUFFICIENT LIGHTING LEVELS FOR SAFE
 EGRESS. THERE ARE ONLY TWO EXISTING FOUR FOOT
 FLORESCENT LIGHTING FIXTURES IN THE NORTH ROOM. THEY DO
 NOT PROVIDE ADEQUATE LIGHTING FOR THAT AREA.
 ? EACH EXIT SHALL BE MARKED BY ILLUMINATED EXIT SIGNS.
 THE EXIT LIGHTS ARE NOT FUNCTIONING AT THIS TIME. SOME
 WERE JUST HANGING BY THE ELECTRICAL CONNECTION.
 ? STORED MATERIALS. THERE ARE SOME MATERIALS STORED IN
 THE SOUTH ROOM OF THE BUILDING THAT IS BLOCKING ONE OF
 THE EXITS AND EXIT PATHS.
 ? CONSTRUCTION SITE. THE BUILDING APPEARS TO BE A
 CONSTRUCTION SITE RATHER THAN A SHELL BUILDING READY
 FOR OCCUPANCY.
 ? PLAN REVIEW. PLEASE ADDRESS ALL PLAN REVIEW COMMENTS
 ENTERED UNDER PERMIT APPLICATION # 19101052.
  
  
 1) THIS EVENT/BUILDING IS DEFINED IN THE FLORIDA FIRE
 PREVENTION CODE AS A SPECIAL AMUSEMENT BUILDING AND AN
 ASSEMBLY OCCUPANCY:
  
 3.3.29.10* SPECIAL AMUSEMENT BUILDING. A BUILDING THAT
 IS
 TEMPORARY, PERMANENT, OR MOBILE AND CONTAINS A DEVICE
 OR
 SYSTEM THAT CONVEYS PASSENGERS OR PROVIDES A WALKWAY
 ALONG,
 AROUND, OR OVER A COURSE IN ANY DIRECTION AS A FORM OF
 AMUSEMENT ARRANGED SO THAT THE EGRESS PATH IS NOT
 READILY
 APPARENT DUE TO VISUAL OR AUDIO DISTRACTIONS OR AN
 INTENTIONALLY
 CONFOUNDED EGRESS PATH, OR IS NOT READILY AVAILABLE DUE
 TO THE
 MODE OF CONVEYANCE THROUGH THE BUILDING OR STRUCTURE.
  
 3.3.183.3* ASSEMBLY OCCUPANCY. AN OCCUPANCY (1) USED
 FOR A
 GATHERING OF 50 OR MORE PERSONS FOR DELIBERATION,
 WORSHIP,
 ENTERTAINMENT, EATING, DRINKING, AMUSEMENT, AWAITING
 TRANSPORTATION, OR SIMILAR USES; OR (2) USED AS A
 SPECIAL
 AMUSEMENT BUILDING, REGARDLESS OF OCCUPANT LOAD.
  
 PER NFPA 1 CH 20 FIRE SPRINKLERS ARE REQUIRED.
  
 20.1.4.2* AUTOMATIC SPRINKLERS. EVERY SPECIAL AMUSEMENT
 BUILDING,
 OTHER THAN BUILDINGS OR STRUCTURES NOT EXCEEDING 10 FT
 (3050 MM) IN
 HEIGHT AND NOT EXCEEDING 160 FT2 (15 M2) IN AGGREGATE
 HORIZONTAL
 PROJECTION, SHALL BE PROTECTED THROUGHOUT BY AN
 APPROVED, SUPERVISED
 AUTOMATIC SPRINKLER SYSTEM INSTALLED AND MAINTAINED IN
 ACCORDANCE
 WITH SECTION 13.3.
  
 ADDITIONAL REQUIREMENTS:
  
 20.1.4.4 SMOKE DETECTION. WHERE THE NATURE OF THE
 SPECIAL
 AMUSEMENT BUILDING IS SUCH THAT IT OPERATES IN REDUCED
 LIGHTING LEVELS,
 THE BUILDING SHALL BE PROTECTED THROUGHOUT BY AN
 APPROVED AUTOMATIC
 SMOKE DETECTION SYSTEM IN ACCORDANCE WITH SECTION 13.7.
 [101:12.4.8.4; 101: 13.4.8.4]
 20.1.4.5 ALARM INITIATION. ACTUATION OF ANY SMOKE
 DETECTION SYSTEM
 DEVICE SHALL SOUND AN ALARM AT A CONSTANTLY ATTENDED
 LOCATION ON THE
 PREMISES. [101: 12.4.8.5, 101: 13.4.8.5]
 20.1.4.6 ILLUMINATION. ACTUATION OF THE AUTOMATIC
 SPRINKLER SYSTEM,
 OR ANY OTHER SUPPRESSION SYSTEM, OR ACTUATION OF A
 SMOKE DETECTION
 SYSTEM HAVING AN APPROVED VERIFICATION OR CROSS-ZONING
 OPERATION
 CAPABILITY SHALL PROVIDE FOR THE FOLLOWING:
 (1) INCREASE IN ILLUMINATION IN THE MEANS OF EGRESS TO
 THAT REQUIRED
 BY SECTION 14.12
 (2) TERMINATION OF ANY CONFLICTING OR CONFUSING SOUNDS
 AND VISUALS
 [101: 12.4.8.6; 101: 13.4.8.6]
 20.1.4.7 EXIT MARKING.
 20.1.4.7.1 EXIT MARKING SHALL BE IN ACCORDANCE WITH
 SECTION 14.14.
 [101: 12.4.8.7.1; 101: 13.4.8.7.1]
 20.1.4.7.2 FLOOR PROXIMITY EXIT SIGNS SHALL BE PROVIDED
 IN ACCORDANCE
 WITH 14.14.1.6. [101: 12.4.8.7.2; 101: 13.4.8.7.2]
 20.1.4.7.3* IN SPECIAL AMUSEMENT BUILDINGS WHERE MAZES,
 MIRRORS, OR
 OTHER DESIGNS ARE USED TO CONFOUND THE EGRESS PATH,
 APPROVED
 DIRECTIONAL EXIT MARKING THAT BECOMES APPARENT IN AN
 EMERGENCY SHALL
 BE PROVIDED.
  
 IN AN EFFORT TO CONSIDER ALTERNATIVES TO THE ABOVE
 REQUIREMENTS, THE SITE FINDINGS NEED TO BE ADDRESSED
 AND CORRECTED.
  
  
  
 2) ADDITIONALLY, PER NFPA 101 CH 7 MEANS OF EGRESS, THE
 FLOOR WALKING SERFACE SHALL MEET THE FOLLOWING:
  
 7.1.6 WALKING SURFACES IN THE MEANS OF EGRESS.
 7.1.6.1 GENERAL.
 7.1.6.1.1 WALKING SURFACES IN THE MEANS OF EGRESS SHALL
 COMPLY
 WITH 7.1.6.2 THROUGH 7.1.6.4.
 7.1.6.1.2 APPROVED EXISTING WALKING SURFACES SHALL BE
 PERMITTED.
 7.1.6.2 CHANGES IN ELEVATION. ABRUPT CHANGES IN
 ELEVATION OF
 WALKING SURFACES SHALL NOT EXCEED ? IN. (6.3 MM).
 CHANGES IN
 ELEVATION EXCEEDING ? IN. (6.3 MM), BUT NOT EXCEEDING ?
 IN. (13
 MM), SHALL BE BEVELED WITH A SLOPE OF 1 IN 2. CHANGES
 IN ELEVATION
 EXCEEDING ? IN. (13 MM) SHALL BE CONSIDERED A CHANGE IN
 LEVEL
 AND SHALL BE SUBJECT TO THE REQUIREMENTS OF 7.1.7.
 7.1.6.3 LEVEL.
 7.1.6.3.1 WALKING SURFACES SHALL COMPLY WITH ALL OF THE
 FOLLOWING:
 (1) WALKING SURFACES SHALL BE NOMINALLY LEVEL.
 (2) THE SLOPE OF A WALKING SURFACE IN THE DIRECTION OF
 TRAVEL SHALL
 NOT EXCEED 1 IN 20, UNLESS THE RAMP REQUIREMENTS OF
 7.2.5 ARE
 MET.
 (3) THE SLOPE PERPENDICULAR TO THE DIRECTION OF TRAVEL
 SHALL NOT
 EXCEED 1 IN 48.
 7.1.7 CHANGES IN LEVEL IN MEANS OF EGRESS.
 7.1.7.1 CHANGES IN LEVEL IN MEANS OF EGRESS SHALL BE
 ACHIEVED BY
 AN APPROVED MEANS OF EGRESS WHERE THE ELEVATION
 DIFFERENCE
 EXCEEDS 21 IN. (535 MM).
 7.1.7.2* CHANGES IN LEVEL IN MEANS OF EGRESS NOT IN
 EXCESS OF 21
 IN. (535 MM) SHALL BE ACHIEVED EITHER BY A RAMP
 COMPLYING WITH
 THE REQUIREMENTS OF 7.2.5 OR BY A STAIR COMPLYING WITH
 THE
 REQUIREMENTS OF 7.2.2.
 7.1.7.2.1 WHERE A RAMP IS USED TO MEET THE REQUIREMENTS
 OF
 7.1.7.2, THE PRESENCE AND LOCATION OF RAMPED PORTIONS
 OF WALKWAYS
 SHALL BE READILY APPARENT.
 7.1.7.2.2 WHERE A STAIR IS USED TO MEET THE
 REQUIREMENTS OF 7.1.7.2,
 THE TREAD DEPTH OF SUCH STAIR SHALL BE NOT LESS THAN 13
 IN. (330 MM).
 7.1.7.2.3 TREAD DEPTH IN INDUSTRIAL EQUIPMENT ACCESS
 AREAS AS
 PROVIDED IN 40.2.5.3 SHALL BE PERMITTED.
 7.1.7.2.4 THE PRESENCE AND LOCATION OF EACH STEP SHALL
 BE READILY
 APPARENT.
  
 3) BASED ON THE ABOVE SITE CONDITIONS AND PROPOSED
 AMUSEMENT USE, THE FOLLOWING MEANS OF EGRESS
 REQUIRMENTS SHALL BE MET:
  
 7.1.9 IMPEDIMENTS TO EGRESS. ANY DEVICE OR ALARM
 INSTALLED TO
 RESTRICT THE IMPROPER USE OF A MEANS OF EGRESS SHALL BE
 DESIGNED
 AND INSTALLED SO THAT IT CANNOT, EVEN IN CASE OF
 FAILURE, IMPEDE OR
 PREVENT EMERGENCY USE OF SUCH MEANS OF EGRESS, UNLESS
 OTHERWISE
 PROVIDED IN 7.2.1.6 AND CHAPTERS 18, 19, 22, AND 23.
 7.1.10 MEANS OF EGRESS RELIABILITY.
 7.1.10.1* MAINTENANCE. MEANS OF EGRESS SHALL BE
 CONTINUOUSLY
 MAINTAINED FREE OF ALL OBSTRUCTIONS OR IMPEDIMENTS TO
 FULL INSTANT
 USE IN THE CASE OF FIRE OR OTHER EMERGENCY.
 7.1.10.2 FURNISHINGS AND DECORATIONS IN MEANS OF
 EGRESS.
 7.1.10.2.1 NO FURNISHINGS, DECORATIONS, OR OTHER
 OBJECTS SHALL
 OBSTRUCT EXITS OR THEIR ACCESS THERETO, EGRESS THERE
 FROM, OR
 VISIBILITY THEREOF.
 7.1.10.2.2 NO OBSTRUCTION BY RAILINGS, BARRIERS, OR
 GATES SHALL
 DIVIDE THE MEANS OF EGRESS INTO SECTIONS APPURTENANT TO
 INDIVIDUAL
 ROOMS, APARTMENTS, OR OTHER OCCUPIED SPACES. WHERE THE
 AUTHORITY
 HAVING JURISDICTION FINDS THE REQUIRED PATH OF TRAVEL
 TO BE
 OBSTRUCTED BY FURNITURE OR OTHER MOVABLE OBJECTS, THE
 AUTHORITY
 SHALL BE PERMITTED TO REQUIRE THAT SUCH OBJECTS BE
 SECURED OUT OF
 THE WAY OR SHALL BE PERMITTED TO REQUIRE THAT RAILINGS
 OR OTHER
 PERMANENT BARRIERS BE INSTALLED TO PROTECT THE PATH OF
 TRAVEL AGAINST
 ENCROACHMENT.
 7.1.10.2.3 MIRRORS SHALL NOT BE PLACED ON EXIT DOOR
 LEAVES. MIRRORS
 SHALL NOT BE PLACED IN OR ADJACENT TO ANY EXIT IN SUCH
 A MANNER AS
 TO CONFUSE THE DIRECTION OF EGRESS.
  
  
 PLEASE PROVIDE DETAILS OF EACH MEANS OF EGRESS.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-10-25 Cont ID  
Sent By rmcdouga Date 2019-10-25 Time 14:48 Rev Time 0.00
Received By rmcdouga Date 2019-10-24 Time 11:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-10-24 Cont ID  
Sent By shill Date 2019-10-24 Time 07:39 Rev Time 0.00
Received By shill Date 2019-10-21 Time 18:11 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-10-21 Cont ID  
Sent By ajones Date 2019-10-21 Time 15:23 Rev Time 0.00
Received By ajones Date 2019-10-21 Time 15:23 Sent To  
Notes
***NONE***