Plan Review Details - Permit 19101012
Plan Review Stops For Permit 19101012
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-12-24 Cont ID  
Sent By jgomez Date 2019-12-24 Time 15:42 Rev Time 0.00
Received By jgomez Date 2019-12-24 Time 14:03 Sent To  
Notes
2019-12-24 14:05:29BUILDING REVIEW APPROVED WITH PROVISO:
 (NOTE: PROVIDE INFORMATION FOR REVIEW PRIOR TO
 INSPECTIONS TO AVOID CONFLICTS/DELAYS)
  
 1- PROVIDE COMPLETE PRODUCT APPROVAL (2 COPIES) FOR THE
 FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY IS
 GOING TO BE INSTALLED.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-11-13 Cont ID  
Sent By jgomez Date 2019-11-13 Time 13:16 Rev Time 0.00
Received By jgomez Date 2019-11-12 Time 11:14 Sent To  
Notes
2019-11-12 14:33:58RESIDENTIAL (R3) ADDITION BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL.
 SEC. 107.2.5 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
  
 2- EXISTING BEDROOM #1 (SAME AS PROPOSED BEDROOM #2):
 SPECIFY THE SIZE AND TYPE OF EXISTING WINDOW AND SIZE
 AND TYPE OF PROPOSED WINDOWS TO VERIFY COMPLIANCE WITH
 THE EGRESS REQUIREMENTS OF SEC. 702.5 FBC-EXISTING
 BUILDING.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 B) DOUBLE FRENCH DOORS WITH SIDELITE AS SHOWN ON PLANS.
  
 C) WINDOW MULLIONS AS SHOWN ON PLANS. AND REQUIRED:
 CLEARLY SPECIFY MULLION SIZE TO BE USED TO VERIFY
 COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES.
  
 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
  
 5- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATED TO $62,196. THE
 PERMIT FEE BALANCE IS $1365.02.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-12-25 Cont ID  
Sent By jpearson Date 2019-12-25 Time 10:54 Rev Time 0.00
Received By jpearson Date 2019-12-25 Time 10:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-11-19 Cont ID  
Sent By jpearson Date 2019-11-19 Time 11:16 Rev Time 0.00
Received By jpearson Date 2019-11-19 Time 10:53 Sent To  
Notes
2019-11-19 11:16:07APPROVED WITH PROVISO ON PLAN FOR AIC CALCULATION AND
 WIRE SIZE TO SUB-PANEL.

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2019-12-23 Cont ID  
Sent By fmittner Date 2019-12-23 Time 11:14 Rev Time 0.00
Received By fmittner Date 2019-12-23 Time 11:14 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2019-11-04 Cont ID  
Sent By fmittner Date 2019-11-04 Time 10:48 Rev Time 0.00
Received By fmittner Date 2019-11-04 Time 10:48 Sent To  
Notes
2019-11-04 10:50:48FRONT FRENCH DOOR OPEINGS TO REMAIN SAME WIDTH AS
 EXISITNG WINDOWS. WINDWO LITE PATTERN TO REFLECT
 EXISTING (PRIMARILY 6/1), WINDOWS FLANKING CHIMNEY TO
 REMAIN. THESE ITEMS DISCUSSED WITH OWNER/CONTRACTOR ON
 SITE.
  
 QUESTIONS/CONTACT: FRIEDERIKE MITTNER, (561) 822-1457
 OR [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-01-28 Cont ID  
Sent By jgomez Date 2020-01-28 Time 16:29 Rev Time 0.00
Received By jgomez Date 2020-01-28 Time 16:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2020-01-13 Time   Rev Time 0.00
Received By lmarchan Date 2020-01-08 Time 14:22 Sent To  
Notes
2020-01-09 14:23:09RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-01-02 Time   Rev Time 0.00
Received By lmarchan Date 2019-12-09 Time 15:42 Sent To  
Notes
2019-12-10 15:42:09R18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2019-11-26 Time   Rev Time 0.00
Received By lmarchan Date 2019-10-21 Time 11:34 Sent To  
Notes
2019-10-22 11:34:42R06

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2020-01-28 Cont ID  
Sent By jgomez Date 2020-01-28 Time 16:28 Rev Time 0.00
Received By jgomez Date 2020-01-28 Time 16:22 Sent To  
Notes
2020-01-28 16:29:31$393.79 PAID. MU-2020-002636.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2019-12-24 Cont ID  
Sent By jgomez Date 2019-12-24 Time 14:16 Rev Time 0.00
Received By jgomez Date 2019-12-24 Time 14:16 Sent To  
Notes
2019-12-24 14:16:31IMPACT FEES -
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK
 OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW.
 PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT
 AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-11-13 Cont ID  
Sent By jgomez Date 2019-11-13 Time 13:18 Rev Time 0.00
Received By jgomez Date 2019-11-13 Time 13:18 Sent To  
Notes
2019-11-13 13:19:07IMPACT FEES -
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK
 OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW.
 PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT
 AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-01-13 Cont ID  
Sent By ccole Date 2020-01-13 Time 17:00 Rev Time 0.00
Received By ccole Date 2020-01-13 Time 17:00 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-01-02 Cont ID  
Sent By ccole Date 2020-01-02 Time 10:32 Rev Time 0.00
Received By ccole Date 2020-01-02 Time 10:32 Sent To I
Notes
2020-01-02 10:35:332ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19101012
 1/2/2020
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 2ND REQUEST FOR MECHANICAL PLANS- SEE 1ST REVIEW
 COMMENT PRINTED BELOW.
  
 1) SUBMIT MECHANICAL PLANS, AND ENERGY AND AC
 CALCULATIONS- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2019-11-26 Time   Rev Time 0.00
Received By ccole Date 2019-11-26 Time 08:23 Sent To I
Notes
2019-11-26 08:32:361ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19101012
 11/26/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT MECHANICAL PLANS, AND ENERGY AND AC
 CALCULATIONS- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-12-24 Cont ID  
Sent By jgomez Date 2019-12-24 Time 16:01 Rev Time 0.00
Received By jgomez Date 2019-12-24 Time 15:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-11-08 Cont ID  
Sent By gjohnson Date 2019-11-08 Time 14:02 Rev Time 0.00
Received By gjohnson Date 2019-11-07 Time 10:04 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2019-12-24 Cont ID  
Sent By jgomez Date 2019-12-24 Time 16:02 Rev Time 0.00
Received By jgomez Date 2019-12-24 Time 16:02 Sent To  
Notes
2019-12-24 16:02:42BUILDING REVIEW APPROVED WITH PROVISO:
 (NOTE: PROVIDE INFORMATION FOR REVIEW PRIOR TO
 INSPECTIONS TO AVOID CONFLICTS/DELAYS)
  
 1- PROVIDE COMPLETE PRODUCT APPROVAL (2 COPIES) FOR THE
 FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY IS
 GOING TO BE INSTALLED.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-11-13 Cont ID  
Sent By jgomez Date 2019-11-13 Time 13:20 Rev Time 0.00
Received By jgomez Date 2019-11-13 Time 13:19 Sent To  
Notes
2019-11-13 13:21:281- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2019-12-23 Cont ID  
Sent By fmittner Date 2019-12-23 Time 11:14 Rev Time 0.00
Received By fmittner Date 2019-12-23 Time 11:14 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-11-04 Cont ID  
Sent By fmittner Date 2019-11-04 Time 10:47 Rev Time 0.00
Received By fmittner Date 2019-11-04 Time 10:47 Sent To  
Notes
***NONE***