Plan Review Details - Permit 19101003
| Plan Review Stops For Permit 19101003 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2021-07-27 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2021-07-27 |
Time |
16:21 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2021-07-27 |
Time |
10:42 |
Sent To |
|
|
| Notes |
| 2021-07-27 16:22:24 | RESIDENTIAL(R3) ALTERATION, THIRD BUILDING REVIEW | | | CHECKLIST. | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | PERMIT: 19101003 | | | | | | NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 1- OK | | | 2- OK | | | 3- OK | | | 4- OK. | | | 5- OK. | | | | | | ORIGINAL COMMENT: | | | 6- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC | | | 61G20-3.001 FOR: | | | A)DINING ROOM SLIDING GLASS DOORS AS SHOWN ON PLANS. | | | B)EXTERIOR SWING DOOR ADJACENT TO THE NEW BATHROOM ON | | | THE BACK OF THE HOUSE. | | | NOTE: IT IS NOT CLEAR IF THESE DOORS ARE GOING TO BE | | | REPLACED. SCOPE OF WORK AND DEMOLITION NOTES CALL FOR | | | REMOVAL OF THESE DOORS. IF THESE DOORS ARE NEW, THEN | | | THEY NEED THE CORRESPONDING PRODUCT APPROVAL. | | | ALSO, IT IS NOT CLEAR IF THE DOOR OF THE EXTERIOR | | | UTILITY CLOSET BEHIND THE MASTER BATHROOM IS NEW OR IF | | | IT'S GOING TO BE REPLACED. | | | SEC. 107.2.1 CITY AMENDMENTS. | | | | | | ORIGINAL COMMENT: | | | 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS | | | (INCLUDING THE ROOFING PRODUCT APPROVALS) AS REQUIRED | | | BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | | | 8- OK | | | | | | ORIGINAL COMMENT: | | | 9- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | | LOW BASED ON ALL THE SCOPE OF WORK SHOWN ON PLANS. | | | VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S | | | OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS | | | REQUIRED BY SEC. 109.3 CITY AMENDMENTS. PROVIDE COPY OF | | | SIGNED CONTRACTS INCLUDING DESIGN PROFESSIONAL FEES FOR | | | BUILDING OFFICIAL REVIEW/APPROVAL. | | | | | | RESPONSE: | | | REPEAT COMMENT (THREE TIMES). VALUED DECLARED IN THE | | | NEW PERMIT APPLICATION STILL EXTREMELY TOO LOW FOR ALL | | | THE SCOPE OF WORK SHOWN ON PLANS. PROVIDE A REALISTIC | | | MARKET VALUE INCLUDING ALL MATERIALS, LABOR, | | | CONTRACTOR'S OVERHEAD AND PROFIT AND ENGINEER OF RECORD | | | FEES OR PROVIDE COPIES OF ALL SIGNED CONTRACTS | | | (INCLUDING THE SUBCONTRACTORS) CLEARLY DEPICTING ALL | | | THE WORK SHOWN ON PLANS, AND COPY OF SIGNED CONTRACT | | | WITH ENGINEER OF RECORD. | | | | | | NEW COMMENT: | | | 10- NONE OF THE PLANS SUBMITTED HAVE THE ENGINEER'S OF | | | RECORD SEAL AND SIGNATURE. ALL PLANS NEED TO HAVE THE | | | ENGINEER'S ORIGINAL SEAL/SIGNATURE AS REQUIRED BY 471 | | | F.S. WHEN SUBMITTING PLANS /DOCUMENTS FOR PUBLIC | | | RECORDS. | | | | | | NOTE: | | | PLANS CAN BE UPLOADED TO PROJECTDOX WITH DIGITAL | | | SIGNATURE OR HARD COPIES WITH ENGINEER'S ORIGINAL | | | SIGNATURE/SEAL MAY BE DROPPED OFF IN CITY HALL. | | | | | | ENGINEERS | | | 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND | | | SEALING ELECTRONICALLY TRANSMITTED PLANS, | | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. | | | | | | 11- EXTERIOR UTILITY CLOSET: | | | A)PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS | | | FOR THE RECONSTRUCTION OF THE EXTERIOR UTILITY CLOSET | | | BEHIND THE MASTER BATHROOM. PROVIDE COMPLETE WALL | | | SECTION SHOWING ALL FRAMING MEMBERS AND FASTENERS. | | | PROVIDE COMPLETE INFORMATION FOR INTERIOR AND EXTERIOR | | | CONSTRUCTION. SEC. R301.1 FBC-RESIDENTIAL. | | | | | | B) PROVIDE DOOR FRAMING DETAIL. SPECIFY ALL FRAMING | | | MEMBERS AND FASTENERS. | | | SEC. R301.1 FBC-RESIDENTIAL. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE | | | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE | | | COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2020-02-28 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2020-02-28 |
Time |
17:33 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2020-02-28 |
Time |
15:57 |
Sent To |
|
|
| Notes |
| 2020-02-28 17:33:37 | RESIDENTIAL (R3) ALTERATION BUILDING REVIEW COMMENTS | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | ORIGINAL COMMENT: | | | 1- PLANS SUBMITTED CALL FOR REMOVAL OF ENTIRE SECOND | | | FLOOR AND STAIRS. NEED TO PROVIDE COMPLETE FRAMING | | | PLANS, DETAILS AND SPECIFICATIONS FOR NEW ROOF. SPECIFY | | | THE CURRENT CODE, WIND DESIGN CRITERIA INCLUDING THE | | | ULTIMATE WIND LOAD AND NOMINAL WIND LOAD, BUILDING | | | EXPOSURE, ETC. AS REQUIRED BY SEC. SEC. R301.2.1 | | | FBC-RESIDENTIAL AND SEC. 107.3.5.3 CITY AMENDMENTS. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | ORIGINAL COMMENT: | | | 2- PLANS SUBMITTED CALL FOR A NEW LARGE SLIDING GLASS | | | DOOR BY THE PROPOSED DINING AREA. NEED TO PROVIDE | | | COMPLETE FRAMING PLANS, DETAILS AND SPECIFICATIONS FOR | | | NEW SLIDING GLASS DOORS. ALSO, SPECIFY THE SIZE OF THE | | | GLASS DOORS. SEC. R301.2.1 FBC-RESIDENTIAL AND SEC. | | | 107.2.1 CITY AMENDMENTS. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | ORIGINAL COMMENT: | | | 3- PROPOSED PLANS SUBMITTED SHOW A DOOR TO BE REPLACED | | | WITH A WINDOW AT THE REAR OF THE LIVING AREA. NEED TO | | | PROVIDE COMPLETE FRAMING PLANS, DETAILS AND | | | SPECIFICATIONS FOR NEW WINDOW. ALSO, SPECIFY THE TYPE | | | AND SIZE OF THE NEW WINDOW. SEC. R301.2.1 | | | FBC-RESIDENTIAL AND SEC. 107.2.1 CITY AMENDMENTS. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | 4- OK. | | | | | | 5- OK. | | | | | | 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | FAC 61G20-3.001 FOR: | | | | | | ORIGINAL COMMENT: | | | A) SLIDING GLASS DOORS AS SHOWN ON PLANS. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | ORIGINAL COMMENT: | | | B) NEW WINDOWS AS SHOWN ON PLANS. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | C) OK. EXISTING EXTERIOR DOOR TO REMAIN. | | | | | | ORIGINAL COMMENT: | | | 7- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS | | | (INCLUDING THE ROOFING PRODUCT APPROVALS) AS REQUIRED | | | BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | ORIGINAL COMMENT: | | | 8- ENGINEER DOING THE RAS 117 CALCULATIONS SPECIFIED | | | ONE ROW OF FASTENERS AT 4 INCHES O.C. AT THE LAP AND 8 | | | ROWS OF FASTENERS IN THE FIELD AT 4 INCHES O.C. | | | ENGINEER TO PROVIDE SKETCH SHOWING HOW THE 9 ROWS OF | | | FASTENERS ARE GOING TO BE PLACED IF FASTENERS CAN NOT | | | BE PLACED LESS THAN 4 INCHES O.C. SEE SEC. 8.1 OF RAS | | | 117. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. | | | NOTE: THERE IS A ROOFING PERMIT FOR THIS PROPERTY. BUT | | | IS NOT CLEAR WHY THE ROOFING PERMIT WAS ISSUED BEFORE | | | THE NEW ROOF IS INSTALLED. THIS NEEDS COORDINATION. | | | | | | ORIGINAL COMMENT: | | | 9- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | | LOW BASED ON ALL THE SCOPE OF WORK SHOWN ON PLANS. | | | VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S | | | OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS | | | REQUIRED BY SEC. 109.3 CITY AMENDMENTS. PROVIDE COPY OF | | | SIGNED CONTRACTS INCLUDING DESIGN PROFESSIONAL FEES FOR | | | BUILDING OFFICIAL REVIEW/APPROVAL. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | NEW COMMENT BASED ON NEW SET OF DRAWINGS SUBMITTED: | | | | | | 10- SPECIFY THE SIZE OF THE NEW ATTIC ACCESS. SEC. R807 | | | FBC-RESIDENTIAL. | | | | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE | | | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE | | | COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-11-13 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-11-13 |
Time |
18:07 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-11-13 |
Time |
13:34 |
Sent To |
P |
|
| Notes |
| 2019-11-13 18:07:29 | RESIDENTIAL (R3) ALTERATION BUILDING REVIEW COMMENTS | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 1- PLANS SUBMITTED CALL FOR REMOVAL OF ENTIRE SECOND | | | FLOOR AND STAIRS. NEED TO PROVIDE COMPLETE FRAMING | | | PLANS, DETAILS AND SPECIFICATIONS FOR NEW ROOF. SPECIFY | | | THE CURRENT CODE, WIND DESIGN CRITERIA INCLUDING THE | | | ULTIMATE WIND LOAD AND NOMINAL WIND LOAD, BUILDING | | | EXPOSURE, ETC. AS REQUIRED BY SEC. SEC. R301.2.1 | | | FBC-RESIDENTIAL AND SEC. 107.3.5.3 CITY AMENDMENTS. | | | | | | 2- PLANS SUBMITTED CALL FOR A NEW LARGE SLIDING GLASS | | | DOOR BY THE PROPOSED DINING AREA. NEED TO PROVIDE | | | COMPLETE FRAMING PLANS, DETAILS AND SPECIFICATIONS FOR | | | NEW SLIDING GLASS DOORS. ALSO, SPECIFY THE SIZE OF THE | | | GLASS DOORS. SEC. R301.2.1 FBC-RESIDENTIAL AND SEC. | | | 107.2.1 CITY AMENDMENTS. | | | | | | 3- PROPOSED PLANS SUBMITTED SHOW A DOOR TO BE REPLACED | | | WITH A WINDOW AT THE REAR OF THE LIVING AREA. NEED TO | | | PROVIDE COMPLETE FRAMING PLANS, DETAILS AND | | | SPECIFICATIONS FOR NEW WINDOW. ALSO, SPECIFY THE TYPE | | | AND SIZE OF THE NEW WINDOW. SEC. R301.2.1 | | | FBC-RESIDENTIAL AND SEC. 107.2.1 CITY AMENDMENTS. | | | | | | 4- PROPOSED FLOOR PLAN DOESN'T HAVE ANY DIMENSIONS. | | | PROVIDE ALL THE DIMENSIONS FOR ALL NEW AREAS. SEC. | | | 107.2.1 CITY AMENDMENTS. | | | | | | 5- PROVIDE THE NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN. SEC. 107.2.1 CITY | | | AMENDMENTS. | | | | | | 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | FAC 61G20-3.001 FOR: | | | A) SLIDING GLASS DOORS AS SHOWN ON PLANS. | | | | | | B) NEW WINDOWS AS SHOWN ON PLANS. | | | | | | C) NEW INSWING ENTRY DOOR AS SHOWN ON PLANS. | | | | | | 7- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS | | | (INCLUDING THE ROOFING PRODUCT APPROVALS) AS REQUIRED | | | BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | | | 8- ENGINEER DOING THE RAS 117 CALCULATIONS SPECIFIED | | | ONE ROW OF FASTENERS AT 4 INCHES O.C. AT THE LAP AND 8 | | | ROWS OF FASTENERS IN THE FIELD AT 4 INCHES O.C. | | | ENGINEER TO PROVIDE SKETCH SHOWING HOW THE 9 ROWS OF | | | FASTENERS ARE GOING TO BE PLACED IF FASTENERS CAN NOT | | | BE PLACED LESS THAN 4 INCHES O.C. SEE SEC. 8.1 OF RAS | | | 117. | | | | | | 9- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | | LOW BASED ON ALL THE SCOPE OF WORK SHOWN ON PLANS. | | | VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S | | | OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS | | | REQUIRED BY SEC. 109.3 CITY AMENDMENTS. UPDATE | | | VALUATION OR PROVIDE COPY OF SIGNED CONTRACTS INCLUDING | | | DESIGN PROFESSIONAL FEES FOR BUILDING OFFICIAL | | | REVIEW/APPROVAL. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE | | | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE | | | COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2021-07-19 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-07-19 |
Time |
17:03 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-07-19 |
Time |
16:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2020-02-27 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2020-02-27 |
Time |
10:50 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2020-02-27 |
Time |
10:50 |
Sent To |
|
|
| Notes |
| 2020-02-27 10:40:22 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL | | | BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- | | | AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY | | | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, | | | DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, | | | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS | | | SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND | | | POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH | | | AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC | | | 210.8, 210.12; FBC RE E3902; FBC EX 607.1.1 OR 801.1, | | | 801.2, OR 901.2 AS APPLICABLE. | | | 2. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE | | | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL | | | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF | | | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL | | | CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE. | | | FBC EC C405.1, R404.1 | | | 3. LIGHTING IN CLOSETS APPEARS TO BE STANDARD RECESS | | | LIGHTS. PER CODE, LIGHTING WITH OPEN OR PARTIALLY | | | ENCLOSED LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS | | | SHALL NOT BE PERMITTED IN CLOTHES CLOSETS. PROVIDE | | | CORRECTION. NEC 410.16; FBC RE E4003.12 | | | 4. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE | | | SUITABLE FOR DAMP LOCATIONS. PROVIDE CORRECTION OR NOTE | | | FOR COMPLIANCE. NEC 410.10(D); FBC RE E4003.11 | | | 5. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING | | | REQUIREMENTS FOR RECEPTACLE OUTLETS. RECEPTACLES SHALL | | | BE INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY | | | ALONG THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 | | | FEET FROM A RECEPTACLE OUTLET. THE WALL SPACING | | | REQUIREMENTS FOR KITCHEN COUNTER SPACE STATE THAT | | | RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT NO POINT | | | ALONG THE WALL LINE IS MORE THAN 24 INCHES MEASURED | | | HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT SPACE. | | | THE PLAN PROVIDED DOES NOT MEET THIS CODE IN SOME | | | AREAS. PROVIDE CORRECTION. NEC 210.52(C)(1); FBC RE | | | E3901 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH | | | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. | | | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL | | | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. | | | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD | | | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-11-19 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-11-19 |
Time |
13:06 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-11-19 |
Time |
10:52 |
Sent To |
|
|
| Notes |
| 2019-11-19 13:06:46 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED(AND | | | SEALED WHERE APPLICABLE) BY THE PERSON RESPONSIBLE FOR | | | THE DESIGN. WPB FBC 107.2.1, 107.3.5; FS 471, 481 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH | | | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. | | | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL | | | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. | | | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD | | | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2021-07-27 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2021-07-27 |
Time |
16:27 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2021-07-16 |
Time |
12:19 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-03-25 |
|
|
Cont ID |
|
| Sent By |
ccarvaja |
Date |
2020-03-25 |
Time |
14:12 |
Rev Time |
0.00 |
| Received By |
ccarvaja |
Date |
2020-02-11 |
Time |
14:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-11-26 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-11-26 |
Time |
|
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-10-28 |
Time |
14:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2021-07-19 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-07-19 |
Time |
12:37 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-07-19 |
Time |
12:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2020-02-14 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-02-14 |
Time |
07:58 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2020-02-14 |
Time |
07:57 |
Sent To |
|
|
| Notes |
| 2020-02-14 08:06:54 | 2ND REVIEW FBC-2017 MECHANICAL | | | PERMIT #19101003 | | | 2/14/20 | | | | | | CODES IN EFFECT: | | | | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2017 | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE MECHANICAL PLANS SHOWING: | | | | | | A) DUCT ALTERATIONS FOR THE NEW FLOOR PLAN LAYOUT- | | | SECTION M1601.1 FBC RES. | | | | | | B) NEW KITCHEN EXHAUST VENTILATION DETAILS- SECTIONS | | | M1503.1 & TABLE M1507.3.3(2) FBC RES | | | | | | C) NEW BATH EXHAUST VENTILATION DETAILS- SECTION R303.3 | | | & TABLE 1507.4 FBC RES | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2019-11-26 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-11-26 |
Time |
09:58 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-11-26 |
Time |
08:36 |
Sent To |
I |
|
| Notes |
| 2019-11-26 10:06:33 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #19101003 | | | 11/26/19 | | | | | | CODES IN EFFECT: | | | | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2017 | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET A1.01: IT APPEARS BY THE SCOPE OF WORK NOTES | | | THAT THE AC SYSTEM IS TO BE REPLACED. PLEASE PROVIDE | | | MECHANICAL PLANS AND/OR AN AC CHANGE OUT FORM IF THE | | | SCOPE IS LIMITED TO JUST CHANGING THE SYSTEM- SECION | | | 107.2.1 WPB. PLEASE NOTE THE CHANGE OUT FORM CAN BE | | | LOCATED ON THE CITY OF WEST PALM BEACH WEBSITE. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2021-07-19 |
|
|
Cont ID |
|
| Sent By |
abelisle |
Date |
2021-07-19 |
Time |
12:13 |
Rev Time |
0.00 |
| Received By |
abelisle |
Date |
2021-07-19 |
Time |
09:18 |
Sent To |
|
|
| Notes |
| 2021-07-19 11:54:21 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | 7/19/2021 19101003 | | | | | | 3RD REVIEW | | | PLUMBING COMMENTS: DENIED | | | | | | 1. THIRD REQUEST; PER WPB FBC 107.2.1, INFORMATION ON | | | PLAN SHEET P-1; WATER HEATER SCHEDULE PLAN STATES | | | EXISTING WATER HEATER DETAIL SHALL COMPLY WITH FBC RES | | | P2801 AND P2903.4 (THERMAL EXPANSION CONTROL | | | 2. PER WPB FBC 107.2.1, PROVIDE NOTE REQUIRING WATER | | | HAMMER ARRESTORS FOR DISHWASHER AND ICE LINE AND | | | WASHING MACHINE IN ACCORDANCE WITH FBC RES P2903.5. | | | 3.. PER FBC PL 2017 406.2WASTE CONNECTION. | | | THE WASTE FROM AN AUTOMATIC CLOTHES WASHER SHALL | | | DISCHARGE THROUGH AN AIR BREAK INTO A STANDPIPE IN | | | ACCORDANCE WITH SECTION 802.3.3 OR INTO A LAUNDRY SINK. | | | THE TRAP AND FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES | | | WASHER STANDPIPE SHALL BE NOT LESS THAN 2 INCHES (51 | | | MM) IN DIAMETER. THE FIXTURE DRAIN FOR THE STANDPIPE | | | SERVING AN AUTOMATIC CLOTHES WASHER SHALL CONNECT TO A | | | 3-INCH (76 MM) OR LARGER DIAMETER FIXTURE BRANCH OR | | | STACK. AUTOMATIC CLOTHES WASHERS THAT DISCHARGE BY | | | GRAVITY SHALL BE PERMITTED TO DRAIN TO A WASTE RECEPTOR | | | OR AN APPROVED TRENCH DRAIN. | | | 4. RE: A-1; FIXTURE SCHEDULE, FLOOR MOUNTED TUB FILLER. | | | A. PER FBC RES P2713.3, PROVIDE A TEMPERATURE LIMITING | | | DEVICE CONFORMING TO ASSE 1070 OR SHOW THAT THE TUB | | | FILL VALVE CONFORMS TO ONE OF THE FOLLOWING; ASSE 1016, | | | ASMEA112.1016 OR CSA B125.16 AS REQUIRED BY FBC RES | | | P2708.4 FOR COMBINATION TUB/SHOWER CONTROL VALVES. | | | B. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR CONNECTION | | | OF HOT AND COLD WATER SUPPLY LINES TO THE FLOOR MOUNTED | | | TUB FILLER; PROVIDE ACCESS TO THE CONNECTIONS IN THE | | | CONCRETE SLAB AS REQUIRED BY FBC RES P2906.7. | | | 5. PER WPB FBC 107.2.1, PROVIDE SIZED SANITARY PLAN | | | VIEW AND RISER DIAGRAM FOR THE ADDED SOAKING OR | | | WHIRLPOOL TUB IN THE MASTER BATH. PROVIDE TRAP, VENT | | | AND POINT OF CONNECTION OF FIXTURE DRAIN COMPLYING WITH | | | FBC RES CHAPTERS 30,31 AND 32. | | | 6. PLAN SHEET P-1 THE SANITARY ISOMETRIC SHALL BE | | | REVISED TO COMPLY WITH FBC PL 2017 910.- FBC PL 2017 | | | 915 | | | | | | END OF COMMENTS. | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED | | | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. | | | | | | ATELYO BELISLE | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | | [email protected] | | | 561-805-6695 | | | | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2020-03-10 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2020-03-10 |
Time |
11:51 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2020-03-10 |
Time |
08:52 |
Sent To |
|
|
| Notes |
| 2020-03-10 11:49:53 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | | | | 1ST REVIEW | | | PLUMBING COMMENTS: DENIED | | | 1. SECOND REQUEST; PER WPB FBC 107.2.1, PROVIDE | | | SIZE(CAPACITY) OF EXISTING WATER HEATER. PLEASE NOTE | | | THAT THREE FIXTURES, A LARGE SOAKING OR WHIRLPOOL TUB, | | | A SHOWER AND A LAVATORY, ALL REQUIRING HOT WATER HAVE | | | BEEN ADDED TO THE PROJECT. THE INFORMATION ON PLAN | | | SHEET P-1; WATER HEATER SCHEDULE PLAN STATES EXISTING | | | WATER HEATER BUT PROVIDES NO DETAILS. PROVIDE AS A | | | MINIMUM THAT THE EXISTING CAPACITY WILL ADEQUATELY | | | SUPPORT ALL PLUMBING FIXTURES IN THE HOUSE, INCLUSIVE | | | OF LAUNDRY FACILITIES. PROVIDE CALCULATIONS; REFER TO | | | FBC RES P2903.6 AND TABLES P2903.6/P2903.6(1). IF | | | EXISTING WATER HEATER IS NOT ADEQUATE, PROVIDE A NEW | | | WATER HEATER AND SPECIFICATION/SCHEDULE. DETAIL SHALL | | | COMPLY WITH FBC RES P2801 AND P2903.4 (THERMAL | | | EXPANSION CONTROL). ADDITIONALLY, SHOW LOCATION ON THE | | | FLOOR PLAN. | | | 2. A FULL BATHROOM GROUP AS WELL AS AN ADDITIONAL | | | SHOWER HAS EACH BEEN ADDED TO THE PROJECT. PROVIDE AS | | | MINIMUM THAT THE EXISTING WATER SERVICE WILL ADEQUATELY | | | SUPPORT ALL PLUMBING FIXTURES IN THE HOUSE. PROVIDE | | | CALCULATIONS; REFER TO FBC RES P2903.6 AND TABLES | | | P2903.6/P2903.6(1). IF EXISTING SERVICE IS NOT | | | ADEQUATE, THEN UPGRADE WATER SERVICE AND DISTRIBUTION | | | TO ADEQUATELY SUPPORT ALL PLUMBING FIXTURES, INCLUDING | | | THE LAUNDRY FACILITIES. | | | 3. PER WPB FBC 107.2.1, PROVIDE NOTE REQUIRING WATER | | | HAMMER ARRESTORS FOR DISHWASHER AND ICE LINE AND | | | WASHING MACHINE IN ACCORDANCE WITH FBC RES P2903.5. | | | 4. PER WPB FBC 107.2.1, SHOW LOCATION OF THE EXISTING | | | CLOTHES WASHER AND IF APPLICABLE, THE LAUNDRY TUB. | | | 5. PER WPB FBC 107.2.1, PROVIDE NOTE ON PLAN REQUIRING | | | NEW SHOWER/ TUB VALVES SHALL COMPLY WITH FBC RES | | | P2708.4 AND P2708.5. | | | | | | 6. RE: A-1; FIXTURE SCHEDULE, FLOOR MOUNTED TUB FILLER. | | | A. PER FBC RES P2713.3, PROVIDE A TEMPERATURE LIMITING | | | DEVICE CONFORMING TO ASSE 1070 OR SHOW THAT THE TUB | | | FILL VALVE CONFORMS TO ONE OF THE FOLLOWING; ASSE 1016, | | | ASMEA112.1016 OR CSA B125.16 AS REQUIRED BY FBC RES | | | P2708.4 FOR COMBINATION TUB/SHOWER CONTROL VALVES. | | | B. PROVIDE BACKFLOW PREVENTION DEVICE FOR THE HAND-HELD | | | SHOWER; COMPLY WITH FBC RES P2708.5 | | | C. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR CONNECTION | | | OF HOT AND COLD WATER SUPPLY LINES TO THE FLOOR MOUNTED | | | TUB FILLER; PROVIDE ACCESS TO THE CONNECTIONS IN THE | | | CONCRETE SLAB AS REQUIRED BY FBC RES P2906.7. | | | | | | 7. PER WPB FBC 107.2.1, PROVIDE SIZED SANITARY PLAN | | | VIEW AND RISER DIAGRAM FOR THE ADDED SOAKING OR | | | WHIRLPOOL TUB IN THE MASTER BATH. PROVIDE TRAP, VENT | | | AND POINT OF CONNECTION OF FIXTURE DRAIN COMPLYING WITH | | | FBC RES CHAPTERS 30,31 AND 32. | | | 8. PER WPB FBC 107.2.1, PROVIDE A SLAB REPAIR DETAIL ON | | | THE PLANS. SHOW THE WIDTH OF THE REPAIR, THE MINIMUM | | | THICKNESS AND PSI OF THE CONCRETE TO BE REPLACED. SHOW | | | SIZE, LENGTH, SPACING (ON CENTER), MINIMUM EMBEDMENT | | | AND ANCHORING/ADHESIVE MATERIAL FOR DOWELS. THE REPAIR | | | SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AS | | | WELL AS THE REQUIRED VAPOR BARRIER OVER WELL COMPACTED | | | SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE | | | FOR FINAL INSPECTION. | | | 9. PLAN SHEET P-1 ON ONE OF THE TWO RESUBMITTALS IS | | | MISSING THE ENGINEER?S STAMP/SEAL. PLEASE WHEN | | | RESUBMITTING BE SURE THAT ALL PLANS ARE SIGNED AND | | | STAMPED/SEALED AS REQUIRED BY FLORIDA ADMINISTRATIVE | | | CODE AND FLORIDA STATUTES | | | | | | | | | END OF COMMENTS. | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED | | | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. | | | | | | | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-805-6715 | | | | | | 19101003 212 GREGORY PL | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2019-11-14 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-11-14 |
Time |
08:47 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-11-07 |
Time |
10:04 |
Sent To |
|
|
| Notes |
| 2019-11-14 09:01:31 | 1ST REVIEW: | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. PROVIDE DIMENSIONS FOR NEW POWDER ROOM SHALL COMPLY | | | WITH FBC RES P2705.1 | | | | | | 2. PROVIDE SANITARY ISOMETRICS DRAWING FOR NEW POWDER | | | ROOM PER WPB AMEND TO FBC 107.3.5.3(12) | | | | | | 3. NOTE ON PLAN IF THE SHOWER/ TUB VALES ARE EXISTING | | | OR BEING REPLACED SHALL COMPLY WITH FNBC RES P2708.4 , | | | P2708.5 | | | | | | 4. NOTE ON PLAN IF WATER HEATER IS NEW OR EXISTING WHAT | | | SIZE. PER FBC RES SECTION P2801 | | | | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
N |
Date |
2021-07-27 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2021-07-27 |
Time |
16:23 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2021-07-27 |
Time |
16:23 |
Sent To |
|
|
| Notes |
| 2021-07-27 16:25:12 | NO ROOFING REVIEW DONE. COMPLETE INFORMATION TO BE | | | PROVIDED UNDER A SEPARATE PERMIT. JG. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2020-02-28 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2020-02-28 |
Time |
17:34 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2020-02-28 |
Time |
17:34 |
Sent To |
|
|
| Notes |
| 2020-02-28 17:34:45 | ORIGINAL COMMENT: | | | 1-- ENGINEER DOING THE RAS 117 CALCULATIONS SPECIFIED | | | ONE ROW OF FASTENERS AT 4 INCHES O.C. AT THE LAP AND 8 | | | ROWS OF FASTENERS IN THE FIELD AT 4 INCHES O.C. | | | ENGINEER TO PROVIDE SKETCH SHOWING HOW THE 9 ROWS OF | | | FASTENERS ARE GOING TO BE PLACED IF FASTENERS CAN NOT | | | BE PLACED LESS THAN 4 INCHES O.C. SEE SEC. 8.1 OF RAS | | | 117. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. | | | NOTE: THERE IS A ROOFING PERMIT FOR THIS PROPERTY. BUT | | | IS NOT CLEAR WHY THE ROOFING PERMIT WAS ISSUED BEFORE | | | THE NEW ROOF IS INSTALLED. THIS NEEDS COORDINATION. | | | | | | | | | ****************************************** | | | | | | ORIGINAL REVIEW COMMENTS: | | | | | | 1- ENGINEER DOING THE RAS 117 CALCULATIONS SPECIFIED | | | ONE ROW OF FASTENERS AT 4 INCHES O.C. AT THE LAP AND 8 | | | ROWS OF FASTENERS IN THE FIELD AT 4 INCHES O.C. | | | ENGINEER TO PROVIDE SKETCH SHOWING HOW THE 9 ROWS OF | | | FASTENERS ARE GOING TO BE PLACED IF FASTENERS CAN NOT | | | BE PLACED LESS THAN 4 INCHES O.C. SEE SEC. 8.1 OF RAS | | | 117. | | | | | | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE | | | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE | | | COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | 1) CERTAIN TEED NOA 15-0622.21 (FLAT ROOF) | | | 2) CERTAIN TEED NOA 17-1211.08 (SHINGLES) |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2019-11-13 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-11-13 |
Time |
18:11 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-11-13 |
Time |
18:07 |
Sent To |
|
|
| Notes |
| 2019-11-13 18:14:04 | 1- ENGINEER DOING THE RAS 117 CALCULATIONS SPECIFIED | | | ONE ROW OF FASTENERS AT 4 INCHES O.C. AT THE LAP AND 8 | | | ROWS OF FASTENERS IN THE FIELD AT 4 INCHES O.C. | | | ENGINEER TO PROVIDE SKETCH SHOWING HOW THE 9 ROWS OF | | | FASTENERS ARE GOING TO BE PLACED IF FASTENERS CAN NOT | | | BE PLACED LESS THAN 4 INCHES O.C. SEE SEC. 8.1 OF RAS | | | 117. | | | | | | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE | | | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE | | | COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | | | | | | | 1) CERTAIN TEED NOA 15-0622.21 (FLAT ROOF) | | | 2) CERTAIN TEED NOA 17-1211.08 (SHINGLES) |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2021-07-27 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2021-07-27 |
Time |
16:25 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2021-07-27 |
Time |
16:25 |
Sent To |
|
|
| Notes |
| 2021-07-27 16:26:22 | SIGNATURE REVIEW COMMENTS. | | | | | | 1- NONE OF THE PLANS SUBMITTED HAVE THE ENGINEER'S OF | | | RECORD SEAL AND SIGNATURE. ALL PLANS NEED TO HAVE THE | | | ENGINEER'S ORIGINAL SEAL/SIGNATURE AS REQUIRED BY 471 | | | F.S. WHEN SUBMITTING PLANS /DOCUMENTS FOR PUBLIC | | | RECORDS. | | | | | | NOTE: | | | PLANS CAN BE UPLOADED TO PROJECTDOX WITH DIGITAL | | | SIGNATURE OR HARD COPIES WITH ENGINEER'S ORIGINAL | | | SIGNATURE/SEAL MAY BE DROPPED OFF IN CITY HALL. | | | | | | ENGINEERS | | | 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND | | | SEALING ELECTRONICALLY TRANSMITTED PLANS, | | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. | | | | | | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE | | | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE | | | COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2020-03-25 |
|
|
Cont ID |
|
| Sent By |
rfalcone |
Date |
2020-03-25 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
rfalcone |
Date |
2020-03-25 |
Time |
10:10 |
Sent To |
I |
|
| Notes |
| 2020-02-28 16:23:25 | NEW SET OF PLANS SUBMITTED. JG. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2019-11-04 |
|
|
Cont ID |
|
| Sent By |
rfalcone |
Date |
2019-11-04 |
Time |
10:49 |
Rev Time |
0.00 |
| Received By |
rfalcone |
Date |
2019-11-04 |
Time |
10:49 |
Sent To |
I |
|
| Notes |
| 2019-11-04 10:50:16 | 11/4/19 PASSED. RF | | | | | | THERE ARE NO MODIFICATIONS BEING MADE TO THE EXISITING | | | FOOTPRINT OF THE STRUCTURE. INTERIOR RENOVATIONS AND | | | DEMOLITION OF SECOND FLOOR ONLY. |
|
|
|