Plan Review Details - Permit 19100986
Plan Review Stops For Permit 19100986
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-11-05 Cont ID  
Sent By cthroop Date 2019-11-05 Time 09:28 Rev Time 0.00
Received By cthroop Date 2019-11-01 Time 15:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-11-15 Cont ID  
Sent By jleahy Date 2019-11-15 Time 15:00 Rev Time 0.00
Received By jleahy Date 2019-11-15 Time 15:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-11-05 Cont ID  
Sent By jpearson Date 2019-11-05 Time 10:13 Rev Time 0.00
Received By jpearson Date 2019-11-05 Time 09:34 Sent To I
Notes
2019-11-05 09:47:23CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. THERE ARE SEVERAL DISCREPANCIES
 BETWEEN THE PANEL SCHEDULE AND THE LOAD CALCULATION
 PROVIDED. IS THE WATER HEATER 5000 VA, OR 8000 VA.? IS
 THE RANGE 8000 VA OR 12000 VA? COORECT ALL
 DISCREPANCIES. NEC 215.2, 220, 408.30; FBC RE E3602.2
 2. PROVIDE ACCURATE RISER DIAGRAM OF NEW SERVICE. THE
 RISER PROVIDED DOES NOT SHOW THE INTERIOR PANEL, OR THE
 WIRE SIZES FOR THE SERVICE AND THE FEED TO THE INTERIOR
 PANEL. NEC 215.5; WPB FBC 107.2.1
 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC
 RE E3606.3
 4. PROVIDE AIC RATING OF ANY SERVICE DISCONNECTS AND
 PANELS. NEC 110.3, 110.9; FBC RE E3606.3
 5. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
 6. SHOW ALL EXISTING OUTLETS IN ROOMS WHERE WORK IS TO
 BE COMPLETED TO COMPLY WITH WALL SPACING REQUIREMENTS
 PER CODE. NEC 210.52; FBC RE E3901.2
 7. PROVIDE SMOKE ALARMS IN EACH LOCATION REQUIRED PER
 CODE. SMOKE ALARMS SHALL BE INSTALLED IN EACH SLEEPING
 ROOM AND OUTSIDE EACH SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOM. FBC RE R314.3, R315.1; WPB FBC
 107.2.1
 8. RECEPTACLES INSTALLED TO SERVE THE COUNTER TOP IN
 KITCHEN, INCLUDING RECEPTACLES INSTALLED ON THE ISLAND,
 REQUIRE GFCI PROTECTION. PROVIDE CORRECTION. NEC 210.8;
 FBC RE E3902.6
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2019-10-30 Cont ID  
Sent By fmittner Date 2019-10-30 Time 16:17 Rev Time 0.00
Received By fmittner Date 2019-10-30 Time 16:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-11-15 Cont ID  
Sent By jleahy Date 2019-11-15 Time 15:01 Rev Time 0.00
Received By jleahy Date 2019-11-15 Time 15:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-11-05 Time   Rev Time 0.00
Received By lmarchan Date 2019-10-18 Time 10:49 Sent To  
Notes
2019-10-21 10:49:17R02

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2019-11-05 Cont ID  
Sent By cthroop Date 2019-11-05 Time 08:56 Rev Time 0.00
Received By cthroop Date 2019-11-05 Time 08:56 Sent To  
Notes
2019-11-05 08:56:43MECHANICAL UNDER SEPERATE PERMIT #19110176. CT

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-10-21 Cont ID  
Sent By lcrespo Date 2019-10-21 Time 07:11 Rev Time 0.00
Received By lcrespo Date 2019-10-21 Time 07:11 Sent To  
Notes
2019-10-21 07:12:2510/21/19 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  