Plan Review Details - Permit 19100898
Plan Review Stops For Permit 19100898
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2020-01-14 Cont ID  
Sent By jwitmer Date 2020-01-14 Time 14:24 Rev Time 0.00
Received By jwitmer Date 2020-01-14 Time 14:24 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2019-11-04 Cont ID  
Sent By jwitmer Date 2019-11-04 Time 14:21 Rev Time 0.00
Received By jwitmer Date 2019-11-04 Time 06:18 Sent To  
Notes
2019-11-04 14:21:53ASBESTOS COMMERCIAL: PLEASE PROVIDE A SIGNED
 ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD,
 STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF
 ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF
 HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT
 NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL
 INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE
 FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/_DOCUMENTS/ASBESTOS-
 NOTIFICATION-FORM-PBC-FILLABLE-UPDATE-07-30-2015.PDF
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-01-14 Cont ID  
Sent By jwitmer Date 2020-01-14 Time 14:25 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-11-04 Cont ID  
Sent By jwitmer Date 2019-11-04 Time 14:22 Rev Time 0.00
Received By jwitmer Date 2019-11-04 Time 05:45 Sent To  
Notes
2019-11-04 14:17:532017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19100898
 ADD: 2330 VILLAGE BLVD.
 CONT: BUILT-MOORE LLC
 TEL: 615-925-2075
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. NOV. 04TH/ 2019
 ACTION: DENIED
  
 1) THE COVERSHEET TS LIST:
 1A) THE 2014 FBC 5TH EDITION AS THE CODE IN AFFECT.
 PLEASE NOTE STATEWIDE THE 6TH EDITION OF THE FBC
 (FAMILY OF CODES INCLUDING ACCESSIBILITY CODE), 2017
 WAS ADOPTED STATEWIDE ON DEC. 31, 2017. PLEASE UPDATE
 YOUR PLANS.
  
 1B) THE 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE CHAPTER 1 ADMINISTRATIVE CODE WAS ADOPTED
 ALSO ON DEC. 31, 2017. PLEASE UPDATE YOUR PLANS.
  
 1C) PLEASE CORRECT THE UNIFIED LAND DEVELOPMENT CODE
 (ULDC) AND REFERENCES TO PALM BEACH COUNTY. THE CITY OF
 WEST PALM BEACH IS UNDER HOME RULE NOT PART OF THE PALM
 BEACH COUNTY JURISDICTION, NOT ANY PART DESIGNATED AS
 MUNICIPAL AREA. PLEASE CORRECT THE PLANS.
  
 1D) PLEASE ALSO NOTE ADDITIONAL REFERENCED DOCUMENTS
 (CHAPTER 35 FGI) FOR CONSTRUCTION AND DESIGN THAT NEED
 TO SHOW COMPLIANCE:
 AGENCY FOR HEALTH CARE ADMINISTRATION (AHCA) FOR
 NURSING HOMES. FGI THE FACILITIES GUIDELINE INSTITUTE/
 (GHCF-14)
  
 1E) FLORIDA ADMINISTRATIVE CODE CHAPTER 59A-4
  
 1F) CHAPTER 400 PART II FLORIDA STATUTES
  
 1G) THE GUIDELINES FOR DESIGN AND CONSTRUCTION OF
 RESIDENTIAL HEALTH CARE, AND SUPPORT FACILITIES. THE
 FACILITIES GUIDELINE INSTITUTE/ GHCF-14 CHAPTER 3.2
 SPECIFIC REQUIREMENTS FOR NURSING HOMES.
  
 1H) 2017 FBC-B SECTION 450.1.3. FLORIDA BUILDING CODE,
 EXISTING BUILDINGS, SECTION 101.2, SCOPE EXEMPTS STATE
 LICENSED FACILITIES SUCH AS NURSING HOMES FROM
 COMPLIANCE WITH THAT CODE. ANY, REPAIRS, ALTERATIONS,
 CHANGE OF OCCUPANCY, ADDITION OR RELOCATION OF AN
 EXISTING STATE LICENSED NURSING HOME SHALL COMPLY WITH
 THE APPLICABLE REQUIREMENTS OF THIS CODE AND THIS
 SECTION.
  
 THE LIFE SAFETY SHEET LIST UNDER THE PROJECT SCOPE A
 LEVEL 1 ALTERATION. PLEASE UPDATE THE PLANS. ALL WORK
 IS TO BE CONSIDERED AS NEW WORK AND MEET ALL OF THE
 REQUIREMENTS UNDER ALL OF THE ABOVE CODES AND
 STANDARDS.
  
 2) SHEET R101 THE LIFE SAFETY SHEET:
 2A) HEADING, EXISTING BUILDING DATA MAKES REFERENCE TO
 THE IBC. PLEASE NOTE THE IBC MAYBE THE BASE CODE, BUT
 FLORIDA HAS ADOPTED THE 2017 FAMILY OF FBC CODES. THE
 FLORIDA CODE IS MORE RESTRICTIVE, PLEASE USE THE 2017
 FBC AS YOUR DESIGN CRITERIA AS WELL AS THE REFERENCED
 STANDARDS, FLORIDA STATUTES AND ADMINISTRATIVE CODE FOR
 DESIGN PURPOSES.
  
 2B) THE EXISTING BUILDING DATA HAS LEFT BLANK THE
 CONSTRUCTION TYPE? PLEASE REVIEW THE 2017 FBC-B TABLES
 504.3, 504.4 & 506.2.
  
 2C) PLEASE UPDATE PLANS AS TO THE REFERENCED CODE, NOT
 THE IBC, BUT THE 2017 FBC-B IN REGARDS TO THE OCCUPANCY
 TYPE.
  
 2D) SHEET R-101 THE LIFE SAFETY PLAN: EXISTING BUILDING
 DATA GIVES THE SQUARE FOOT AREA OF 21,041 SQUARE FEET.
 THE P. B. COUNTY GEO NAV MAPPING SHOWS 54,850 SQUARE
 FEET IN AREA. WHY SUCH A DIFFERENCE IN SQ. FOOTAGE?
 PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-B SECTION
 407.5 FOR SMOKE COMPARTMENTS. SMOKE BARRIERS SHALL BE
 PROVIDED TO SUBDIVIDE EVERY STORY USED BY PERSONS
 RECEIVING CARE, TREATMENT OR SLEEPING AND TO DIVIDE
 OTHER STORIES WITH AN OCCUPANT LOAD OF 50 OR MORE
 PERSONS, INTO NO FEWER THAN TWO SMOKE COMPARTMENTS.
 SUCH STORIES SHALL BE DIVIDED INTO SMOKE COMPARTMENTS
 WITH AN AREA OF NOT MORE THAN 22,500 SQUARE FEET (2092
 M2) IN GROUP I-2, CONDITION 1, AND NOT MORE THAN 40,000
 SQUARE FEET (3716 M2) IN GROUP I-2, CONDITION 2, AND
 THE DISTANCE OF TRAVEL FROM ANY POINT IN A SMOKE
 COMPARTMENT TO A SMOKE BARRIER DOOR SHALL BE NOT
 GREATER THAN 200 FEET (60 960 MM). THE SMOKE BARRIER
 SHALL BE IN ACCORDANCE WITH SECTION 709SECTION 709.
  
 2E) THE LIFE SAFETY PLAN SHOWS A WALL LEGEND FOR THE
 FIRE AND SMOKE RATINGS OF WALLS. PLEASE NOTE THERE ARE
 NO RATING OF WALLS ON THE PLANS. THE PLANS CURRENTLY
 UNDER THIS REVIEW DO NOT SHOW COMPLIANCE WITH SECTION
 407.5 NOR INFORMATION ON THE DOORS LEADING FROM EACH
 SMOKE COMPARTMENT.
  
 3) A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN
 SINCE THERE WAS A GREAT DEFICIENCY IN PLANS AND
 REQUIRED DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE
 THERE MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW
 PLANS AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-01-16 Cont ID  
Sent By jpearson Date 2020-01-16 Time 15:49 Rev Time 0.00
Received By jpearson Date 2020-01-16 Time 15:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-11-12 Cont ID  
Sent By jpearson Date 2019-11-12 Time 13:51 Rev Time 0.00
Received By jpearson Date 2019-11-12 Time 13:43 Sent To  
Notes
2019-11-12 13:51:12CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5
 2. REMOVE ALL KEY NOTES NOT APPLICABLE TO THIS PLAN.
 THERE ARE SOME NOTES THAT ARE NOT SHOWN ON THE PLAN.
 WPB FBC 107.2.1
 3. THE NEC AND FBC SPECIFIED FOR DESIGN IS NOT THE
 CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE
 CURRENT CODES ABOVE)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-01-09 Cont ID  
Sent By pleduc Date 2020-01-09 Time   Rev Time 0.00
Received By pleduc Date 2020-01-09 Time 14:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-10-22 Cont ID  
Sent By J.Walker Date 2019-10-22 Time   Rev Time 0.00
Received By jwalker Date 2019-10-22 Time 10:35 Sent To  
Notes
2019-10-22 10:41:38PROVISO:
 LIFE SAFETY SYSTEMS TO REMAIN FUNCTIONAL AND INTACT FOR
 THE DURATION OF THE PROJECT.
 SUB-PERMIT AND OR DETAILED NARRITIVE WITH REGARDS TO
 FIRE SPRINKLER AND FIRE ALARM WORK WILL BE REQUIRED.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-01-16 Time   Rev Time 0.00
Received By lmarchan Date 2020-01-07 Time 13:07 Sent To  
Notes
2020-01-08 13:07:59B29

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-11-12 Time   Rev Time 0.00
Received By lmarchan Date 2019-10-17 Time 13:21 Sent To  
Notes
2019-10-18 13:21:34B29

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-11-04 Cont ID  
Sent By jwitmer Date 2019-11-04 Time 14:20 Rev Time 0.00
Received By jwitmer Date 2019-11-04 Time 05:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2020-01-14 Cont ID  
Sent By ccole Date 2020-01-14 Time 11:59 Rev Time 0.00
Received By ccole Date 2020-01-14 Time 11:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-11-01 Cont ID  
Sent By ccole Date 2019-11-01 Time 14:57 Rev Time 0.00
Received By ccole Date 2019-11-01 Time 14:56 Sent To  
Notes
2019-11-01 15:00:541ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19100898
 11/1/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET MEP100: KEYNOTE M1 IS NOT USED ON PLAN. PLEASE
 CONFIRM WITH A NOTE THAT NO MECHANICAL WORK WILL BE
 INCLUDED IN THE SCOPE OF WORK FOR THIS PERMIT- SECTION
 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status N Date 2020-02-21 Cont ID  
Sent By gjohnson Date 2020-02-21 Time 10:21 Rev Time 0.00
Received By gjohnson Date 2020-02-21 Time 10:21 Sent To  
Notes
2020-02-21 10:22:55NO PLUMBING WORK SHOWN ON PLANS SEPARATE PERMIT AND
 PLANS REQUIRED FOR ANY PLUMBING WORK BEING DONE
 INCLUDING REPLACEMENT OF FIXTURES.

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-01-15 Cont ID  
Sent By gjohnson Date 2020-01-15 Time 14:22 Rev Time 0.00
Received By gjohnson Date 2020-01-15 Time 12:25 Sent To  
Notes
2020-01-15 14:22:322ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. IF THERE IS NO PLUMBING IN THE SCOPE OF WORK PLEASE
 REMOVE ACCESSIBILITY MOUNTING DETAILS FOR ALL PLUMBING
 FIXTURES ON SHEET R100 AND NOTE #5 UNDER PROJECT SCOPE
 ON SHEET R101. PER WPB AMEND TO FBC 107.2.1
  
 2. PLEASE REMOVE REFERENCE TO PLUMBING WORK ON PERMIT
 APPLICATION. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-10-22 Cont ID  
Sent By jesmith Date 2019-10-22 Time 15:20 Rev Time 0.00
Received By jesmith Date 2019-10-22 Time 15:19 Sent To  
Notes
2019-10-22 15:20:26CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 1. RE: PLAN SHEET D100; DEMO PLAN KEY NOTE 23 CALLS FOR
 REMOVAL OF CASEWORK AND SINK. CANNOT FIND REFERENCE TO
 THAT KEY NOTE ON THE FLOOR PLAN. PER WPB FBC 107.2.1,
 PLEASE CLARIFY.
 2. RE: PLAN SHEET D100; PLUMBING SCOPE NOTES ARE NOT
 REFERENCED ON THE FLOOR PLAN. PER WPB FBC 107.2.1,
 PLEASE CLARIFY.
 3. RE: PLAN SHEET D100; PLUMBING SCOPE NOTE P5 REFERS
 TO ID DRAWINGS FOR FIXTURE TYPES. HAVE FOUND NO
 INFORMATION ON THE ID DRAWINGS PERTAINING TO PLUMBING
 FIXTURES. PER WPB FBC 107.2.1, PLEASE CLARIFY.
 4. RE: PLAN SHEET D100; PLUMBING SCOPE NOTE P5 CALLS
 FOR NEW PLUMBING FIXTURE IN NEW LOCATION. CONNECT TO
 EXISTING WATER & WASTE LINES. PER WPB FBC 107.2.1,
 SANITARY AND WATER RISER DIAGRAMS ARE REQUIRED TO SHOW
 COMPLIANCE WITH FBC PL (FLORIDA PLUMBING CODE 2017 6TH
 EDITION)
  
 A COMPLETE AND COMPREHENSIVE PLUMBING REVIEW COULD NOT
 BE CPERFORMED AT THIS TIME.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19100898 2330 VILLAGE BLVD
  
  