Plan Review Details - Permit 19100889
Plan Review Stops For Permit 19100889
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2019-12-13 Cont ID  
Sent By shill Date 2019-12-13 Time 17:07 Rev Time 0.00
Received By shill Date 2019-12-13 Time 17:07 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2019-11-26 Cont ID  
Sent By jwitmer Date 2019-11-26 Time 12:54 Rev Time 0.00
Received By jwitmer Date 2019-11-25 Time 12:29 Sent To  
Notes
2019-11-26 12:54:47ASBESTOS COMMERCIAL. PLEASE PROVIDE A SIGNED
 ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD,
 STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF
 ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF
 HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT
 NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL
 INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE
 FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-03-17 Cont ID  
Sent By jwitmer Date 2020-03-17 Time 10:58 Rev Time 0.00
Received By jwitmer Date 2020-03-16 Time 12:01 Sent To  
Notes
2020-03-17 10:58:032017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19100889
 ADD: 2239 PALM BEACH LAKES BLVD.
 CONT: VINTAGE BUILD & DESIGN
 TEL: 561-420-2725
 E-MAIL: [email protected]
 CONTACT: TARA BESWICK
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: TUES. MARCH 17TH/ 202019
 ACTION: BUILDING PROVISO
  
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION 107.3.4.2
 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS SECTION,
 DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF
 THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. BEFORE
 FRAMING INSPECTION AND BUCK INSPECTION.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, , WALL LOUVERS, WALL
 INTAKE OR EXHAUST FANS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS
 (G) PRE-ENGINEERED A/C STANDS
  
 IDENTIFY GLAZING/ MULLIONS. THE SUBMITTED PRODUCT
 APPROVALS THE ELEMENTS LISTED BELOW ARE NOT IDENTIFIED.
 PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED
 OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 JAMES A. WITMER BN, PX, SFP & CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-02-03 Cont ID  
Sent By jwitmer Date 2020-02-03 Time 07:03 Rev Time 0.00
Received By jwitmer Date 2020-01-28 Time 13:15 Sent To  
Notes
2020-02-03 07:03:462017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19100889
 ADD: 2239 PALM BEACH LAKES BLVD.
 CONT: VINTAGE BUILD & DESIGN
 TEL: 561-420-2725
 E-MAIL: [email protected]
 CONTACT: TARA BESWICK
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. FEB. 03/ 2019
 ACTION: DENIED
  
 1-3) COMPLIED.
  
 4) 2ND REVIEW, PRODUCT APPROVALS:
 THE SUBMITTED PRODUCT APPROVALS THE ELEMENTS LISTED
 BELOW ARE NOT IDENTIFIED. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 4A) FL.812-R8 ARMOR SCREEN SERIES 2000 NONE OF THE
 ANCHORING SCHEDULES WITHIN THE APPROVAL HAVE BEEN FILED
 OUT, TYPE OF MOUNTING PER OPENING, CONCRETE, BLOCK
 WALL, EARTH ANCHORS SPACING, TYPE OF ANCHORS AND THE
 SQUARE FOOT OPENING AND ASSOCIATED PRESSURES.
  
 4B) MIAMI-DADE NOA 15-0504.01 THE COOKSON CO. 12 FEET 5
 INCH WIDE STEEL ROLLING DOOR. PLEASE IDENTIFY THE
 OPENING SIZE TO BE INSTALLED, THE ASSOCIATED PRESSURES
 AND ANCHORING TYPE AND SPACING.
  
 4C) MIAMI-DADE NOA DAYBAR INDUSTRIES LS-18 OUTSWING
 DOOR W/ PANIC / LMI 19 PAGES WITHIN THE REPORT NONE OF
 THE DOOR TYPE AND HARDWARE WITH ASSOCIATED PRESSURES
 ARE IDENTIFIED, DOOR SIZE NOT IDENTIFIED, ANCHORING
 SCHEDULE, GLAZING TYPE, AND PRESSURES.
  
 4D) MIAMI-DADE NOA 17-0630.11 CGI WINDOW AND DOORS
 HEAVY DUTY CLIPPED TUBE MULLION, 29 PAGES OF SCHEDULES
 NOTHING IS IDENTIFIED. PLEASE IDENTIFY ON THE PRODUCT
 APPROVAL BEFORE SUBMITTING TO DESIGNER OF RECORD AND
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL
 PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING
 WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
  
 4E) MIAMI-DADE NOA 17-1114.01 CGI WINDOWS & DOORS 18
 PAGES OF SCHEDULES, NOTHING IS IDENTIFIED. PLEASE
 IDENTIFY ON THE PRODUCT APPROVAL BEFORE SUBMITTING TO
 DESIGNER OF RECORD AND BEFORE SUBMISSION TO THE
 BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING,
 PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF
 GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR
 REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B
 1405.13.1.
  
 4F) FL-26048-R1 18 PAGES, NOT MARKED, NOT IDENTIFIED.
 PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED
 OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B
 1405.13.1
  
 4G) FL 9730-R4. PANEL WALLS/ HURRICANE SHUTTERS. 6
 PAGES, NOTHING IS IDENTIFIED. 1609.1.2, 1715.8 & EXIST
 BUILD CODE 706.4 PROCEDURES: A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING OPENING SIZES, STORY
 HEIGHTS, UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT
 STORM BAR REINFORCING REQUIREMENTS, WALL PRESSURE
 ZONES, SLAT TYPES, ETC.
  
 4H) MIAMI-DADE NOA 16-0219.01 TC-5 SERIES STEEL ROOF
 CURB FOR TRANE ROOF TOP UNITS. PAGE 5 OF REPORT STATES
 THE RESTRAINT BRACKET QUANTITY DETERMINED SITE SPECIFIC
 CALCULATIONS BY FLORIDA P.E. OR FLORIDA ARCHITECT.
  
 4I) MIAMI-DADE NOA EITHER ROOF TOP OF SIDEWALL MOUNTED
 EXHAUST FAN. 13 PAGES NOTHING IS MARKED AS UNIT TYPE,
 INSTALLATION TYPE WALL OR ROOF MOUNT, ANCHOR TYPE, SIZE
 OR SPACING WITH ASSOCIATED EITHER WALL OR ROOF
 PRESSURES. IF ROOF MOUNT, CURB TYPE AND ANCHORAGE TO
 THE ROOF, AND ANCHORAGE OF THE EXHAUST FAN TO THE ROOF
 TOP CURB. LATERAL FORCE-RESISTING SYSTEM
 FOR ALL ROOF TOP EQUIPMENT, CURBS, FANS AND OR VENTS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-11-26 Cont ID  
Sent By jwitmer Date 2019-11-26 Time 12:54 Rev Time 0.00
Received By jwitmer Date 2019-11-25 Time 12:29 Sent To  
Notes
2019-11-26 12:54:002017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19100889
 ADD: 2239 PALM BEACH LAKES BLVD.
 CONT: VINTAGE BUILD & DESIGN
 TEL: 561-420-2725
 E-MAIL: [email protected]
 CONTACT: TARA BESWICK
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. NOV. 25/ 2019
 ACTION: DENIED
  
 1) MISSING LIFE SAFETY PLAN. NOT IN THE INDEX OF
 DRAWINGS. 2017 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1OF THE ADMINISTRATIVE
 CODE SECTION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS. THE EXAMINATION OF THE DOCUMENTS BY THE
 BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM
 CRITERIA AND DOCUMENTS:
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED AND OR MIXED OCCUPANCIES.
 MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE
 TABLES 504.3, TABLE 504.4 & TABLE 506.2).
 MEZZANINE REQUIREMENTS FOR AREA & EXITING
 BUILDING HAVE FIRE SPRINKLERS OR NOT?
 FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 SCHEMATIC FIRE SPRINKLERS / PRE-ENGINEERED SYSTEMS
 FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL INCLUDE
 THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS
 LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL
 INCLUDE THE FOLLOWING REQUIREMENTS:
 OCCUPANT LOAD AND EGRESS CAPACITIES
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 SPECIFIC OCCUPANCY REQUIREMENTS: 406 MOTOR-VEHICLE
 RELATED OCCUPANCIES.
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
 1B) PLEASE FOR THE NEXT REVIEW PLACE THE SHEETS IN THE
 FILE FOLDER IN ORDER OF THE PAGE INDEX. 107.2.1.3
 QUALITY OF BUILDING PLANS. THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS
 FOR PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY
 MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE,
 CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORDS
 MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH
 THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES.
  
 2A) SITE PLAN DOES NOT SHOW THE TOTAL OF HOW MANY
 PARKING SPACES ARE FOR THE CLIENTS AND THE REQUIRED
 ACCESSIBLE PARKING SPACES AND ACCESS AISLE. PLEASE SHOW
 COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY CODE 208.2
 MINIMUM NUMBER.
  
 2B) THE MARKING OF THE ACCESSIBLE PARKING SPACE AND
 ACCESS AISLE WILL NEED TO SHOW COMPLIANCE WITH 502.2 &
 502.3.3 ALSO SEE ADVISORY, TO LOCAL STANDARDS. PLEASE
 SEE W. P. B. MUNI CODE ARTICLE XV PARKING CD94:276.
  
 2C) SHOW COMPLIANCE WITH THE 2017 ACCESS. CODE 502.4,
 EXCEPTION ALLOWS FOR SLOPES NOT STEEPER THAN 1:48 SHALL
 BE PERMITTED. PLEASE SHOW THE ELEVATIONS OF THE ACCESS.
 PARKING SPACE AND ACCESS AISLE IN EACH CORNER.
  
 2D) PLEASE PROVIDE THE DISTANCE THE BUILDING IS TO THE
 PROPERTY LINE ON THE SIDE LOT LINES TO ESTABLISH THE
 FIRE RESISTANCE RATING REQUIREMENTS FOR EXTERIOR WALLS
 BASED ON FIRE SEPARATION DISTANCE, FBC-B TABLE 602.
  
 2E) BASED ON THE TABLE 705.8 THE MAXIMUM AREA OF
 EXTERIOR WALL OPENINGS BASED ON THE FIRE SEPARATION
 DISTANCE AND DEGREE OF OPENING PROTECTION.
  
 3) SHEET A-2 PROPOSED FLOOR PLAN:
 3A) PLEASE PROVIDE A NARRATIVE AS TO WHAT THE FRONT
 SHOWROOM AREA IS TO HOUSE? THE FRONT ENTRY DOOR # 102
 IS AN OVERHEAD GARAGE ENTRY DOOR. IT WOULD APPEAR THE
 OVERHEAD GARAGE ENTRY DOOR IS ALUMINUM AND GLASS.
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
  
 3B) WITHOUT THE DESIGNER OF RECORD STATING THE
 OCCUPANCY TYPES WITHIN THIS BUILDING IT IS A GUESSING
 GAME. WE DO NOT KNOW HOW TO CATEGORIZE THE FRONT
 PORTION OF THE BUILDING, AUTO SHOWROOMS ARE A BUSINESS
 , THE DISPLAY COULD BE SMALLER ITEMS WHICH WOULD MAKE
 IT MERCANTILE OCCUPANCY, BUT THERE IS ALSO A WAITING
 AREA, IS THIS FOR CARS OR FOR PEOPLE? THE BACK PORTION
 OF THE BUILDING IS SET UP POSSIBLE AS A REPAIR GARAGE
 OR A S1 OCCUPANCY, BUT THE CLEAN ROOMS COULD BE USED TO
 STORE AUTOMOBILES WHICH COULD POSSIBLY MAKE AN S2
 OCCUPANCY, IS THE BUILDING FIRE SPRINKLERED OR NOT? TO
 MANY UNKNOWNS TO SHOW COMPLIANCE WITH TABLE 508.4
 REQUIRED SEPARATION OF OCCUPANCIES.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-03-11 Cont ID  
Sent By jleahy Date 2020-03-11 Time 08:16 Rev Time 0.00
Received By jleahy Date 2020-03-11 Time 08:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-01-13 Cont ID  
Sent By jleahy Date 2020-01-13 Time 14:26 Rev Time 0.00
Received By jleahy Date 2020-01-13 Time 10:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-11-21 Cont ID  
Sent By jleahy Date 2019-11-21 Time 16:59 Rev Time 0.00
Received By jleahy Date 2019-11-21 Time 16:37 Sent To  
Notes
2019-11-21 17:03:55FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) PAGE E3.1 FAULLT CURRENT LETTER FROM FPL IS CUT OFF
 NOT ALL OF IT IS SHOWN
  
 2) PAGE E-3.1 WIRES TO BE TAPPED IN GUTTER ?? NEED TO
 SHOW SIZE OF CONDUCTORS.
  
 3) PAGE E-3.1 NOTES STATES "OPEN DELTA' ? IS IT OPEN OR
 CLOSED ? NOT TO MANY OPEN DELTAS EXIST IN THE CITY.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-03-10 Cont ID  
Sent By sathomas Date 2020-03-10 Time 00:00 Rev Time 0.00
Received By sathomas Date 2020-03-10 Time 00:00 Sent To M
Notes
2020-03-10 14:16:13PROVISO:
 SUBJECT TO FIELD INSPECTION.
  
 S. THOMAS
 561-804-4728

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2020-01-21 Cont ID  
Sent By sathomas Date 2020-01-21 Time 00:00 Rev Time 0.00
Received By sathomas Date 2020-01-21 Time 00:00 Sent To M
Notes
2020-01-21 13:16:45FIRE COMMENTS WERE NOT ADDRESSED DURING THIS PLAN
 REVIEW SUBMISSION.
  
 A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED
 AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON
 THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED DURING PLAN RESUBMISSION.
 1) PER SECTION 18.2.3.4.1.1 (NFPA 1), FIRE DEPARTMENT
 ACCESS ROADS SHALL HAVE A SURFACE DESIGNED TO
 ACCOMMODATE FIRE APPARATUS WEIGHING AT LEAST 36 TONS.
 ACCESS ROADS SHALL HAVE AN UNOBSTRUCTED WIDTH OF NOT
 LESS THAN 20 FEET AND AN UNOBSTRUCTED VERTICAL
 CLEARANCE OF NOT LESS THAN 13 FEET 6 INCHES.
  
 2) PER SECTION 18.2.3.5.3 (NFPA 1), FIRE LANES SHALL BE
 MARKED WITH FREESTANDING SIGNS READING, ?FIRE LANE - NO
 PARKING BY ORDER OF THE FIRE DEPARTMENT.? SIGNS SHALL
 BE 12? X 18? WITH A WHITE BACKGROUND AND RED LETTERS
 AND SHALL BE A MAXIMUM OF SEVEN FEET IN HEIGHT TO THE
 BOTTOM OF THE SIGN. SIGNS SHALL BE WITHIN SIGHT OF THE
 TRAFFIC FLOW AND BE SPACED A MAXIMUM OF 60 FEET APART.
  
 3) THERE IS NO INDICATION OF A MIXED OR SEPARATED
 OCCUPANCY:
 30.2.2 OCCUPANCY CLASSIFICATION. THE OCCUPANCY
 CLASSIFICATION OF A REPAIR GARAGE SHALL BE A SPECIAL
 PURPOSE INDUSTRIAL OCCUPANCY AS DEFINED IN NFPA 101.
 [30A:7.4.1]
 7.4.3 MEANS OF EGRESS. IN A REPAIR GARAGE, THE REQUIRED
 NUMBER, LOCATION, AND CONSTRUCTION OF MEANS OF EGRESS
 SHALL MEET ALL APPLICABLE REQUIREMENTS FOR SPECIAL
 PURPOSE INDUSTRIAL OCCUPANCIES, AS SET FORTH IN NFPA
 101, LIFE SAFETY CODE. PER SECTION 7.5.2.1, ACCESS TO
 AN EXIT SHALL NOT BE THROUGH KITCHENS, STOREROOMS OTHER
 THAN AS PROVIDED IN CHAPTERS 36 AND 37, RESTROOMS,
 WORKROOMS, CLOSETS, BEDROOMS OR SIMILAR SPACES, OR
 OTHER ROOMS OR SPACES SUBJECT TO LOCKING.
  
 4) PER NFPA 101 CH 6, OCCUPANCY CLASSIFICATION:
 6.1 CLASSIFICATION OF OCCUPANCY.
 6.1.1 GENERAL.
 6.1.1.1 OCCUPANCY CLASSIFICATION. THE OCCUPANCY OF A
 BUILDING OR STRUCTURE, OR PORTION OF A BUILDING OR
 STRUCTURE, SHALL BE CLASSIFIED IN ACCORDANCE WITH 6.1.2
 THROUGH 6.1.13. OCCUPANCY CLASSIFICATION SHALL BE
 SUBJECT TO THE RULING OF THE AUTHORITY HAVING
 JURISDICTION WHERE THERE IS A QUESTION OF PROPER
 CLASSIFICATION IN ANY INDIVIDUAL CASE.
 6.1.14.2 DEFINITIONS.
 6.1.14.2.1 MULTIPLE OCCUPANCY. A BUILDING OR STRUCTURE
 IN WHICH TWO OR MORE CLASSES OF OCCUPANCY EXIST.
 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE
 THE OCCUPANCIES ARE INTERMINGLED.
 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY
 WHERE THE OCCUPANCIES ARE SEPARATED BY FIRE RESISTANCE
 RATED ASSEMBLIES.
 6.1.14.3 MIXED OCCUPANCIES.
 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE
 CLASSIFIED AS TO ITS USE IN ACCORDANCE WITH SECTION
 6.1.
 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST
 RESTRICTIVE REQUIREMENTS OF THE OCCUPANCIES INVOLVED,
 UNLESS SEPARATE SAFEGUARDS ARE APPROVED.
 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.)
 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED,
 EACH PART OF THE BUILDING COMPRISING A DISTINCT
 OCCUPANCY, AS DESCRIBED IN THIS CHAPTER,
 SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY
 FIRE-RESISTIVE ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2,
 6.1.14.4.3, TABLE 6.1.14.4.1(A),
 AND TABLE 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED
 BY APPROVED EXISTING SEPARATIONS OR AS OTHERWISE
 PERMITTED BY 6.1.14.4.6.
  
 7.3.1 OCCUPANCY CLASSIFICATION. THE OCCUPANCY
 CLASSIFICATION OF A MOTOR FUEL DISPENSING FACILITY THAT
 IS LOCATED INSIDE A BUILDING OR STRUCTURE SHALL BE A
 SPECIAL PURPOSE INDUSTRIAL OCCUPANCY AS DEFINED IN NFPA
 101, LIFE SAFETY CODE.
  
 3.3.190.8.3 SPECIAL-PURPOSE INDUSTRIAL OCCUPANCY. AN
 INDUSTRIAL OCCUPANCY IN WHICH ORDINARY AND LOW HAZARD
 INDUSTRIAL OPERATIONS ARE CONDUCTED IN BUILDINGS
 DESIGNED FOR,
 AND SUITABLE ONLY FOR, PARTICULAR TYPES OF OPERATIONS,
 CHARACTERIZED BY A RELATIVELY LOW DENSITY OF EMPLOYEE
 POPULATION, WITH MUCH OF THE AREA OCCUPIED BY MACHINERY
 OR EQUIPMENT.
 (SAF-IND)
  
 THE SEPARATION REQUIRED WOULD NOT JUST BE OCCUPANCY IT
 WOULD BE HAZARD AS WELL.
  
 6.2 HAZARD OF CONTENTS.
 6.2.1 GENERAL.
 6.2.1.1 FOR THE PURPOSE OF THIS CODE, THE HAZARD OF
 CONTENTS SHALL BE THE RELATIVE DANGER OF THE START AND
 SPREAD OF FIRE, THE DANGER OF SMOKE OR GASES GENERATED,
 AND THE DANGER OF EXPLOSION OR OTHER OCCURRENCE
 POTENTIALLY ENDANGERING THE LIVES AND SAFETY OF THE
 OCCUPANTS OF THE BUILDING OR STRUCTURE.
  
 A MIXED OCCUPANCY CLASSIFICATION WOULD STILL NEED TO
 PROVIDE SEPARATION OF THE STORAGE HAZARD.
  
 PLEASE REVIEW AND PROVIDE CLARIFICATIONS
  
 5) A DOOR SCHEDULE IS REQUIRED TO DETERMINE SEPARATION
 REQUIREMENTS FOR ALL AREAS:
  
 THE DOOR SCHEDULE DOES NOT INDICATED THE DOOR
 LOCKING/LATCHING HARDWARE FPR THE APPLICABLE CODE.
  
 PER NFPA , CH 7 MEANS OF EGRESS
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS
 OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER
 EXPOSURE TO ELEVATED TEMPERATURE IN ACCORDANCE WITH THE
 LISTING, BASED ON LABORATORY FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR
 OPERATION FROM THE EGRESS SIDE.
 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3
 SHALL NOT APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18
 THROUGH 23.
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
 ADDITIONAL COMMENTS MAY BE PROVIDED ON THE RE-SUBMITTAL
 OF THE ABOVE.
  
 7) PLANS SHOW A SPIRAL STAIR IN THE CENTER WEST OF THE
 BUILDING, HOWEVER THERE ARE NO PLANS THAT INDICATE WHAT
 WILL BE ON THE SECOND FLOOR AREA.
  
 S. THOMAS
 561804-4728
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-11-21 Cont ID  
Sent By sathomas Date 2019-11-21 Time 13:16 Rev Time 0.00
Received By sathomas Date 2019-11-21 Time 12:57 Sent To E
Notes
2019-11-21 13:16:09A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED
 AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON
 THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED DURING PLAN RESUBMISSION.
 1) PER SECTION 18.2.3.4.1.1 (NFPA 1), FIRE DEPARTMENT
 ACCESS ROADS SHALL HAVE A SURFACE DESIGNED TO
 ACCOMMODATE FIRE APPARATUS WEIGHING AT LEAST 36 TONS.
 ACCESS ROADS SHALL HAVE AN UNOBSTRUCTED WIDTH OF NOT
 LESS THAN 20 FEET AND AN UNOBSTRUCTED VERTICAL
 CLEARANCE OF NOT LESS THAN 13 FEET 6 INCHES.
  
 2) PER SECTION 18.2.3.5.3 (NFPA 1), FIRE LANES SHALL BE
 MARKED WITH FREESTANDING SIGNS READING, ?FIRE LANE - NO
 PARKING BY ORDER OF THE FIRE DEPARTMENT.? SIGNS SHALL
 BE 12? X 18? WITH A WHITE BACKGROUND AND RED LETTERS
 AND SHALL BE A MAXIMUM OF SEVEN FEET IN HEIGHT TO THE
 BOTTOM OF THE SIGN. SIGNS SHALL BE WITHIN SIGHT OF THE
 TRAFFIC FLOW AND BE SPACED A MAXIMUM OF 60 FEET APART.
  
 3) THERE IS NO INDICATION OF A MIXED OR SEPARATED
 OCCUPANCY:
 30.2.2 OCCUPANCY CLASSIFICATION. THE OCCUPANCY
 CLASSIFICATION OF A REPAIR GARAGE SHALL BE A SPECIAL
 PURPOSE INDUSTRIAL OCCUPANCY AS DEFINED IN NFPA 101.
 [30A:7.4.1]
 7.4.3 MEANS OF EGRESS. IN A REPAIR GARAGE, THE REQUIRED
 NUMBER, LOCATION, AND CONSTRUCTION OF MEANS OF EGRESS
 SHALL MEET ALL APPLICABLE REQUIREMENTS FOR SPECIAL
 PURPOSE INDUSTRIAL OCCUPANCIES, AS SET FORTH IN NFPA
 101, LIFE SAFETY CODE. PER SECTION 7.5.2.1, ACCESS TO
 AN EXIT SHALL NOT BE THROUGH KITCHENS, STOREROOMS OTHER
 THAN AS PROVIDED IN CHAPTERS 36 AND 37, RESTROOMS,
 WORKROOMS, CLOSETS, BEDROOMS OR SIMILAR SPACES, OR
 OTHER ROOMS OR SPACES SUBJECT TO LOCKING.
  
 4) PER NFPA 101 CH 6, OCCUPANCY CLASSIFICATION:
 6.1 CLASSIFICATION OF OCCUPANCY.
 6.1.1 GENERAL.
 6.1.1.1 OCCUPANCY CLASSIFICATION. THE OCCUPANCY OF A
 BUILDING OR STRUCTURE, OR PORTION OF A BUILDING OR
 STRUCTURE, SHALL BE CLASSIFIED IN ACCORDANCE WITH 6.1.2
 THROUGH 6.1.13. OCCUPANCY CLASSIFICATION SHALL BE
 SUBJECT TO THE RULING OF THE AUTHORITY HAVING
 JURISDICTION WHERE THERE IS A QUESTION OF PROPER
 CLASSIFICATION IN ANY INDIVIDUAL CASE.
 6.1.14.2 DEFINITIONS.
 6.1.14.2.1 MULTIPLE OCCUPANCY. A BUILDING OR STRUCTURE
 IN WHICH TWO OR MORE CLASSES OF OCCUPANCY EXIST.
 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE
 THE OCCUPANCIES ARE INTERMINGLED.
 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY
 WHERE THE OCCUPANCIES ARE SEPARATED BY FIRE RESISTANCE
 RATED ASSEMBLIES.
 6.1.14.3 MIXED OCCUPANCIES.
 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE
 CLASSIFIED AS TO ITS USE IN ACCORDANCE WITH SECTION
 6.1.
 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST
 RESTRICTIVE REQUIREMENTS OF THE OCCUPANCIES INVOLVED,
 UNLESS SEPARATE SAFEGUARDS ARE APPROVED.
 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.)
 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED,
 EACH PART OF THE BUILDING COMPRISING A DISTINCT
 OCCUPANCY, AS DESCRIBED IN THIS CHAPTER,
 SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY
 FIRE-RESISTIVE ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2,
 6.1.14.4.3, TABLE 6.1.14.4.1(A),
 AND TABLE 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED
 BY APPROVED EXISTING SEPARATIONS OR AS OTHERWISE
 PERMITTED BY 6.1.14.4.6.
  
 7.3.1 OCCUPANCY CLASSIFICATION. THE OCCUPANCY
 CLASSIFICATION OF A MOTOR FUEL DISPENSING FACILITY THAT
 IS LOCATED INSIDE A BUILDING OR STRUCTURE SHALL BE A
 SPECIAL PURPOSE INDUSTRIAL OCCUPANCY AS DEFINED IN NFPA
 101, LIFE SAFETY CODE.
  
 3.3.190.8.3 SPECIAL-PURPOSE INDUSTRIAL OCCUPANCY. AN
 INDUSTRIAL OCCUPANCY IN WHICH ORDINARY AND LOW HAZARD
 INDUSTRIAL OPERATIONS ARE CONDUCTED IN BUILDINGS
 DESIGNED FOR,
 AND SUITABLE ONLY FOR, PARTICULAR TYPES OF OPERATIONS,
 CHARACTERIZED BY A RELATIVELY LOW DENSITY OF EMPLOYEE
 POPULATION, WITH MUCH OF THE AREA OCCUPIED BY MACHINERY
 OR EQUIPMENT.
 (SAF-IND)
  
 THE SEPARATION REQUIRED WOULD NOT JUST BE OCCUPANCY IT
 WOULD BE HAZARD AS WELL.
  
 6.2 HAZARD OF CONTENTS.
 6.2.1 GENERAL.
 6.2.1.1 FOR THE PURPOSE OF THIS CODE, THE HAZARD OF
 CONTENTS SHALL BE THE RELATIVE DANGER OF THE START AND
 SPREAD OF FIRE, THE DANGER OF SMOKE OR GASES GENERATED,
 AND THE DANGER OF EXPLOSION OR OTHER OCCURRENCE
 POTENTIALLY ENDANGERING THE LIVES AND SAFETY OF THE
 OCCUPANTS OF THE BUILDING OR STRUCTURE.
  
 A MIXED OCCUPANCY CLASSIFICATION WOULD STILL NEED TO
 PROVIDE SEPARATION OF THE STORAGE HAZARD.
  
 PLEASE REVIEW AND PROVIDE CLARIFICATIONS
  
 5) A DOOR SCHEDULE IS REQUIRED TO DETERMINE SEPARATION
 REQUIREMENTS FOR ALL AREAS:
  
 THE DOOR SCHEDULE DOES NOT INDICATED THE DOOR
 LOCKING/LATCHING HARDWARE FPR THE APPLICABLE CODE.
  
 PER NFPA , CH 7 MEANS OF EGRESS
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS
 OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER
 EXPOSURE TO ELEVATED TEMPERATURE IN ACCORDANCE WITH THE
 LISTING, BASED ON LABORATORY FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR
 OPERATION FROM THE EGRESS SIDE.
 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3
 SHALL NOT APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18
 THROUGH 23.
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
 ADDITIONAL COMMENTS MAY BE PROVIDED ON THE RE-SUBMITTAL
 OF THE ABOVE.
  
 7) PLANS SHOW A SPIRAL STAIR IN THE CENTER WEST OF THE
 BUILDING, HOWEVER THERE ARE NO PLANS THAT INDICATE WHAT
 WILL BE ON THE SECOND FLOOR AREA.
  
 S. THOMAS
 561804-4728
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-03-20 Cont ID  
Sent By shill Date 2020-03-20 Time 16:44 Rev Time 0.00
Received By shill Date 2020-03-02 Time 10:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-02-05 Time   Rev Time 0.00
Received By lmarchan Date 2020-01-08 Time 09:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-12-03 Cont ID  
Sent By shill Date 2019-12-03 Time 15:22 Rev Time 0.00
Received By shill Date 2019-10-24 Time 14:57 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2020-02-13 Cont ID  
Sent By lmarchan Date 2020-02-13 Time 10:43 Rev Time 0.00
Received By lmarchan Date 2020-02-04 Time 12:36 Sent To  
Notes
2020-02-13 09:32:45MU 2020-004757 - RECEIPT 2020-0214-25 - $4,700.73 -
 PAID
2020-02-04 12:36:552/4/20 EMAILED IMPACT FEE OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-12-02 Cont ID  
Sent By dbattles Date 2019-12-02 Time 14:20 Rev Time 0.00
Received By dbattles Date 2019-11-25 Time 12:29 Sent To  
Notes
2019-12-02 14:20:54109 FBC[AMENDED] PLANS WILL BE REVIEWED BY THE PBC
 IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON
 NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR
 WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE
 WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY
 UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE
 R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU
 ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE
 UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-03-19 Cont ID  
Sent By medwards Date 2020-03-19 Time 12:01 Rev Time 0.00
Received By medwards Date 2020-03-19 Time 12:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-02-05 Cont ID  
Sent By ccole Date 2020-02-05 Time 14:14 Rev Time 0.00
Received By ccole Date 2020-01-31 Time 14:29 Sent To  
Notes
2020-02-05 14:17:002ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19100889
 2/5/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE FIRE DEPARTMENT IS QUESTIONING THE OCCUPANCY
 CLASSIFICATION OF THE PROPOSED PROJECT AND REQUIRES
 MORE INFORMATION. CURRENTLY IS HAS BEEN CLASSIFIED AS A
 BUSINESS OCCUPANCY AS STATED ON SHEET A-1, HOWEVER THE
 PLANS INDICATE THE SPACE WILL BE USED FOR AUTO BODY
 REPAIR AND DETAILING AS STATED ON SHEET M1.1. IT
 APPEARS THEN IT WOULD BE AN S-1 STORAGE OCCUPANCY-
 REPAIR GARAGE. ACCORDING TO THE ENGINEER'S RESPONSE
 NARRATIVE TO 1ST REVIEW COMMENTS "THERE WILL BE NO
 MOTOR VEHICLE REPAIR OR OPERATION WITHIN THIS FACILITY;
 THE VEHICLES WILL BE MOVED USING DOLLIES INSTEAD" FOR
 THAT REASON HE HAS REMOVED THE CO/NO2 SENSORS AND IS
 CITING SECTION 502.14 EXCEPTION #3. A) THE EOR MUST
 PROVIDE THESE STATEMENTS FROM THE NARRATIVE ONTO THE
 PLAN. B) THE EOR AND/OR CONTRACTOR SHALL PROVIDE A
 SUBMITTAL FOR THE CAR DOLLIES WITH A REVIEW AND
 APPROVAL STAMP BY THE EOR- SECTION 107.2.1 WPB. IN
 ADDITION THE PLANS SHALL SHOW THE DESIGNATED STORAGE
 AREA FOR THE DOLLIES.
  
 2) THE EF-7 VENTILATION SYSTEM FOR THE DRIVE IN FRONT
 DRIVE-IN AREA HAS BEEN REMOVED FROM THE RESUBMITTED
 PLAN. PLEASE REPLACE THE SYSTEM AND UPDATE THE PLANS TO
 INCLUDE THE FAN SCHEDULE AND SEQUENCING- SECTION 502.14
 FBC M.
  
 3) REFER TO SECTION 406.8.2 FBC B AND LOCATE THE
 CONTROLS FOR THE MANUAL PURGE SYSTEMS TO THE ENTRANCES
 OF THE BUILDING.
  
 4) SHOW THE LOCATION ON THE PLANS WHERE AUTO BODY AND
 DETAILING MATERIALS WILL BE STORED. REFER TO SECTION
 414.1.3 AND PROVIDE A MATERIALS REPORT AND MSDS SHEETS.
 A REPORT SHALL BE SUBMITTED TO THE BUILDING OFFICIAL
 IDENTIFYING THE MAXIMUM EXPECTED QUANTITIES OF
 HAZARDOUS MATERIALS TO BE STORED, USED IN A CLOSED
 SYSTEM AND USED IN AN OPEN SYSTEM, AND SUBDIVIDED TO
 SEPARATELY ADDRESS HAZARDOUS MATERIAL CLASSIFICATION
 CATEGORIES BASED ON TABLES 307.1(1) AND 307.1(2). THE
 METHODS OF PROTECTION FROM SUCH HAZARDS, INCLUDING BUT
 NOT LIMITED TO CONTROL AREAS, FIRE PROTECTION SYSTEMS
 AND GROUP H OCCUPANCIES SHALL BE INDICATED IN THE
 REPORT AND ON THE CONSTRUCTION DOCUMENTS. THE OPINION
 AND REPORT SHALL BE PREPARED BY A QUALIFIED PERSON,
 FIRM OR CORPORATION APPROVED BY THE BUILDING OFFICIAL
 AND PROVIDED WITHOUT CHARGE TO THE ENFORCING AGENCY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-11-26 Cont ID  
Sent By ccole Date 2019-11-26 Time 14:46 Rev Time 0.00
Received By ccole Date 2019-11-26 Time 14:28 Sent To  
Notes
2019-11-26 15:46:321ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19100889
 11/26/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M0.2 & M1.1: THE HONEYWELL SENSOR ANALYTICS
 ARE FOR THE SERVICE BAY, HOWEVER NO SERVICE BAY IS
 SHOWN ON THE FLOOR PLAN- SECTION 107.2.1 WPB.
  
 2) M0.2 & M1.1: THE O/A CALCULATIONS IDENITFY SOME OF
 THE SPACES AS BOTH REPAIR AND ENCLOSED PARKING GARAGE.
 PLEASE REVISE THE ANALYTICS AND VENTILATION
 CALCULATIONS TO INDICATE A MINIMUM VENTILATION AIRFLOW
 RATE OF 0.05 CFMS PER SF. SHALL BE MAINTAINED
 CONTINOUSLY- SEE SECTION 404.2 FBC M.
  
 3) M0.2 & M1.1: NO SEQUENCES OF OPERATION ARE PROVIDED
 FOR EF-3, EF-4, AND EF-6. THERE ARE NO SENSORS SHOWN IN
 THESE ROOMS, HOWEVER IT APPEARS VEHICLES WILL BE WORKED
 ON OR STORED IN THESE ROOMS. PLEASE NOTE THAT
 RECIRCULATION OF AIR FROM THE DETAIL AREA VIA THE
 TRANSFERS TO THE CLEAN #1 ROOM MAY BE PROHIBITED
 DEPENDING ON WHAT THE USE OF THE ROOM IS - SEE TABLE
 403.3.1.1 FBC M FOOTNOTE B.
  
 4) M0.2: PLEASE PROVIDE AN AIR BALANCE CALCULATION-
 SECTION 501.4 FBC M.
  
 5) M1.1 PROVIDE FL. PRODUCT APPROVALS OR MIAMI-DADE
 NOA'S FOR THE LOUVERS AND WALL FANS- RULE 9N-3 FAC.
 PLEASE NOTE THAT NOA #16-0209.05 SHOWN ON SHEET M0.5 IS
 EXPIRED.
  
 6) M1.1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE AIR
 DRYER AND A PIPING PLAN- SECTION 107.2.1.
  
 7) PROVIDE ENGINEERING FOR INSTALLATION ON THE NEW
 RTU-1- SECTION 301.15 FBC M.
  
 8) THE AC CALCULATIONS ARE INCORRECTLY INDICATING MIAMI
 AS THE PROJECT LOCATION- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2020-03-21 Cont ID  
Sent By shill Date 2020-03-21 Time 13:29 Rev Time 0.00
Received By shill Date 2020-03-21 Time 13:29 Sent To  
Notes
2020-03-21 13:30:1219100889 2239 PALM BEACH LAKES BLVD
  
 PLUMBING APPROVED W/PROVISO
  
 I. OIL/WATER SEPARATOR DRAW OFF TANK
 1. PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, REGARDING
 THE OIL/WATER SEPARATOR DRAW OFF TANK, PROVIDE AS A
 DEFERRED SUBMITTAL THE FOLLOWING:
 CLARIFICATION AS TO WHETHER THE SYSTEM IS NEW OR
 EXISTING. IF EXISTING, SHOW LOCATION AND PROVIDE
 CERTIFICATION SHOWING COMPLIANCE WITH FLORIDA DEP. IF
 NEW, SUBMIT SPECIFICATION, DETAIL AND LOCATION OF NEW
 TANK AND PIPING. DOCUMENT SHALL BE SUBMITTED, APPROVED
 AND ON SITE PRIOR TO FINAL INSPECTION. PROCEED AT YOUR
 OWN RISK.
 II. DRINKING FOUNTAIN
 1. UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH FBC ACC 305 POSITIONED FOR A FORWARD
 APPROACH AND CENTERED ON THE UNIT. KNEE AND TOE
 CLEARANCE COMPLYING WITH FBC ACC 306 SHALL BE PROVIDED
 PER FBC ACC 602.2.
 2. OPERABLE PARTS SHALL COMPLY WITH FBC ACC 309 PER FBC
 ACC 602.3.
 3. SPOUT OUTLETS SHALL BE 36 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND PER FBC ACC 602.4.
 4.THE SPOUT SHALL BE LOCATED 15 INCHES MINIMUM FROM THE
 VERTICAL SUPPORT AND 5 INCHES MAXIMUM FROM THE FRONT
 EDGE OF THE UNIT, INCLUDING BUMPERS PER FBC ACC 602.5.
 III. BREAKROOM SINK
 1. LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE
 FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE AS
 REQUIRED BY FBC ACC 306.2 AND 306.3
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PH: 561-805-6715
  
 19100889 2239 PALM BEACH LAKES BLVD
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2020-03-20 Cont ID  
Sent By shill Date 2020-03-20 Time 16:44 Rev Time 0.00
Received By shill Date 2020-03-19 Time 14:38 Sent To  
Notes
2020-03-20 16:44:10CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 19100889 2239 PALM BEACH LAKES BLVD
  
 3RD REVIEW
 PLUMBING COMMENTS:DENIED
 1. CONCERNING ITEM 10 REVIEW 2; SUBMIT MSDS SHEETS FOR
 THE CHEMICALS TO BE USED IN
 THE CHEMICAL DISPENSER AND THE AMOUNTS TO BE STORED AND
 HOW THEY ARE STORED.WPB AMEND. TO FBC SEC. 107.2.1.
 NEW COMMENT: IF ARCHITECT IS TO RESPOND TO THIS THEN HE
 NEEDS TO DO SO PRIOR TO APPROVAL FOR PLUMBING PERMIT.
 2.CONCERNING ITEM 10 REVIEW 2; SUBMIT MANUFACTURER'S
 SPECIFICATIONS/INSTALLATION
 MANUAL FOR THE WATER SOFTENING SYSTEM. WPB AMEND. TO
 FBC SEC. 107.2.1.
 NEW COMMENT: IF THERE IS NO WATER SOFTENER THEN REMOVE
 REFERENCE TO SOFTENED WATER FOR ITEM W-3 CHEMICAL
 DISPENSING CENTER ON PLAN SHEET P1.1
 3. IS THE OIL/SEPERATOR DRAW OFF TANK AND DRAIN
 EXISTING? IF SO SHOW LOCATION AND PROVIDE CERTIFICATION
 SHOWING COMPLIANCE WITH FLORIDA DEP OR SUBMIT SPEC AND
 DETAIL AND LOCATION OF NEW PIPING AND TANK. CONTACT TIM
 LARGE AT 561-805-6692 FOR FURTHER CLARIFICATION.
  
 PROVISO
 I. DRINKING FOUNTAIN
 1.UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH FBC ACC 305 POSITIONED FOR A FORWARD
 APPROACH AND CENTERED ON THE UNIT. KNEE AND TOE
 CLEARANCE COMPLYING WITH FBC ACC 306 SHALL BE PROVIDED
 PER FBC ACC 602.2.
 2.OPERABLE PARTS SHALL COMPLY WITH FBC ACC 309 PER FBC
 ACC 602.3.
 3.SPOUT OUTLETS SHALL BE 36 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND PER FBC ACC 602.4.
 4.THE SPOUT SHALL BE LOCATED 15 INCHES MINIMUM FROM THE
 VERTICAL SUPPORT AND 5 INCHES MAXIMUM FROM THE FRONT
 EDGE OF THE UNIT, INCLUDING BUMPERS PER FBC ACC 602.5.
 II. BREAKROOM SINK
 1. LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE
 FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE AS
 REQUIRED BY FBC ACC 306.2 AND 306.3
  
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
  
  
 19100889 2239 PALM BEACH LAKES BLVD
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-01-17 Cont ID  
Sent By tklarge Date 2020-01-17 Time 12:58 Rev Time 0.00
Received By tklarge Date 2020-01-16 Time 09:49 Sent To  
Notes
2020-01-17 12:58:131) THE PLANS INDICATE AN AIR COMPRESSOR. SUBMIT A
 COMPRESSED AIR RISER DIAGRAM IF ANY RIDGID AIR PIPING
 IS TO BE INSTALLED. SHOW THE TYPE OF MATERIAL, PIPE
 SIZIES, LOCATION OF VALVES, ETC. NOTE: PVC PIPING IS
 NOT PERMITTED TO BE USED FOR COMPRESSED AIR PER
 MANUFACTURER'S SPECIFICATIONS. WPB AMEND. TO FBC SEC.
 107.2.1.
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION MANUAL FOR THE CHEMICAL DISPENSING UNIT.
 IF THIS IS CONNECTED TO THE POTABLE WATER SYSTEM IN ANY
 MANNER A BACKFLOW DEVICE WILL BE REQUIRED. WPB AMEND.
 TO FBC SEC. 107.2.1.
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE OIL
 INTERCEPTOR. WPB AMEND. TO FBC SEC. 107.2.1.
 4) SHT. P0.2 - DETAIL #6 - THE OIL INTERCEPTOR SHALL
 COMPLY WITH 2017 FBC - PLUMBING SEC.1003.4.2.1.
 5) THE DRINKING FOUNTAIN SHALL BE LOCATED WHERE IT IS
 ACCESSIBLE TO THE CUSTOMERS. THERE IS A TIRE CHANGING
 MACHINE RIGHT NEXT TO THE DRINKING FOUNTAIN. THIS
 CREATES A POSSIBLE UNSAFE ENVIRONMENT FOR A
 NON-EMPLOYEE USING THIS FIXTURE. UNSAF AND I FIND IT
 HARD TO BELIEVE THAT THE BUSINESS ALLOWS CUSTOMERS IN
 THE WORK AREA DUE TO LIABILITY. IF THIS IS THE CASE, A
 NOTARIZED LETTER FROM THE OWNER OF THE BUSINESS SHALL
 BE SUBMITTED SPECIFICALLY STAING THEAT CUSTOMERS WILL
 BE PERMITTED IN THE WORK AREA AND THAT THE BUSINESS
 OWNER ACCEPTS ALL LIABILITY.
 6) A MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED PER
 2017 FBC-PLUMBING SEC. 410.3.
 7) THE WASHING MACINE SHALL BE INSTALLED ON A MINIMUM 3
 INCH WASTE STACK. 2017 FBC-PLUMBING SEC.406.2.
 8) SUBMIT DETAILS/MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE WASHER SYSTEM. WILL ANY RIDGID PIPING BE
 INSTALLED FOR THIS SYSTEM? IF SO, SUBMIT A PIPING
 DIAGRAM SHOWING PIPE MATERIAL, PIPE SIZES, VALVES, ETC.
 9) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE POINT
 OF USE WATER HEATERS AT THE LAVATORIES.WPB AMEND. TO
 FBC SEC. 107.2.1.
 10) SUBMIT MSDS SHEETS FOR THE CHEMICALS TO BE USED IN
 THE CHEMICAL DISPENSER AND THE AMOUNTS TO BE STORED AND
 HOW THEY ARE STORED.WPB AMEND. TO FBC SEC. 107.2.1.
 11) SUBMIT MANUFACTURER'S SPECIFICATIONS/INSTALLATION
 MANUAL FOR THE WATER SOFTENING SYSTEM. WPB AMEND. TO
 FBC SEC. 107.2.1.
 12) THE IRRIGATION SYSTEM WILL NEED A SEPARATE BACKFLOW
 PREVENTION DEVICE AND A SEPARATE PERMIT WILL BE
 REQUIRED FOR THE BACKFLOW PER THE CITY OF WEST PALM
 BEACH CROSS CONNECTION CONTROL MANUAL.
 13) A LINT INTERCEPTTOR IS REQUIRED PER 2017
 FBC-PLUMBING SEC1003.6. AFTER DOING ADDITIONAL RESEARCH
 IN THE IPC COMMENTARY, EXCEPTION #2 REFERS TO WASHING
 MACHINES THAT WOULD BE LOCATED IN COMMON LAUNDRY ROOMS
 IN RESIDENTIAL BUILDINGS, NOT IN A COMMECIAL BUILDING,
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-11-27 Cont ID  
Sent By shill Date 2019-11-27 Time 08:09 Rev Time 0.00
Received By shill Date 2019-11-21 Time 16:59 Sent To  
Notes
2019-11-27 08:09:55PLUMBING 1ST REVIEW**DENIED**19100889
  
 1) SHOW THE WASHER AND DRYER AS BEING ACCESSIBLE WITH A
 PARALLEL APPROACH CENTERED ON THE FIXTURE FBC-ACC 611.2
 AND HEIGHT OF BOTH COMPLYING WITH FBC-ACC 611.4
  
 2) SHOW CABINET HEIGHT DETAIL AND CLEAR FLOOR SPACE FOR
 BOTH THE BREAK ROOM SINK AND SINK LOCATED IN THE
 LAUNDRY ROOM MAX 34?. FBC-ACC 804.3.1, 804.3.2
  
 3) ARE CUSTOMERS PERMITTED IN THE WORK SPACE TO ACCESS
 THE DRINKING FOUNTAIN? PLEASE CLARIFY. FBC 107.2.1
  
 4) PROVIDE BUILDING OCCUPANCY AND OCCUPANT LOAD. FBC
 107.3.5
  
 5) PROVIDE INSTALLATION MANUAL FOR THE TANKLESS WATER
 HEATER AND GREASE INTERCEPTOR. FBC 107.2.1
  
 6) PROVIDE TOTAL DEVELOPED LENGTH OF PIPING FOR THE
 WATER HEATER TO FURTHEST OUTLET. FBC-PLB 607.2
  
 7) PROVIDE LINT INTERCEPTOR FOR THE WASHING MACHINE.
 FBC-PLB 1003.6
  
 8) PROVIDE NOTE RPZ BACKFLOW IF NOT ALREADY ON-SITE
 WILL BE REQUIRED AND INSTALLATION MUST BE PERFORMED BY
 A LIC. PLUMBER ONLY WITH SEPARATE PERMIT. SAME OF
 IRRIGATION SYSTEM ON ITS OWN WATER METER
  
 TIM HUNT
  
 PLUMBING PLANS EXAMINER
  
 CITY OF WEST PALM BEACH (CGA SOLUTIONS)
 [email protected]
  
 561-248-2703
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-03-11 Cont ID  
Sent By shill Date 2020-03-11 Time 07:33 Rev Time 0.00
Received By shill Date 2020-03-11 Time 07:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-02-03 Cont ID  
Sent By shill Date 2020-02-03 Time 16:55 Rev Time 0.00
Received By shill Date 2020-02-03 Time 16:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-12-02 Cont ID  
Sent By dbattles Date 2019-12-02 Time 14:16 Rev Time 0.00
Received By dbattles Date 2019-12-02 Time 14:15 Sent To  
Notes
2019-12-02 14:20:1661G15-23 PE RULES FAC, FS 471 ENGINEERING FS
 DIGITALLY SIGN WITH A DIGITAL SIGNATURE ISSUED TO YOU
 BY A 3RD PARTY CERTIFICATION AUTHORITY.
  
 -ANY ADDITIONAL SHEETS THATY ARE DIGITALLY SIGNED BY AN
 ENGINEER SHOULD BE VERIFIED BY A 3RD PARTY
 CERTIFICATION AUTHORITY.
  
2019-11-26 16:06:44MECH PLANS OK. ENERGY CALCULATION SIGNATURE AND SEAL
 COULD NOT BE VALIDATED.

Review Stop Z ZONING
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2020-03-11 Time   Rev Time 0.00
Received By   Date 2020-03-11 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-02-04 Cont ID  
Sent By awooten Date 2020-02-04 Time   Rev Time 0.00
Received By awooten Date 2020-02-04 Time   Sent To  
Notes
2020-02-04 15:24:16******************************ZONING
 REVIEW******************************
  
 THE LANDSCAPE PLAN REQUIRES A SEPARATE PERMIT.
  
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2019-12-02 Cont ID  
Sent By awooten Date 2019-12-02 Time   Rev Time  
Received By awooten Date 2019-12-02 Time   Sent To  
Notes
***NONE***