Plan Review Details - Permit 19100889
| Plan Review Stops For Permit 19100889 |
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
2 |
Status |
P |
Date |
2019-12-13 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-12-13 |
Time |
17:07 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-12-13 |
Time |
17:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2019-11-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2019-11-26 |
Time |
12:54 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2019-11-25 |
Time |
12:29 |
Sent To |
|
|
| Notes |
| 2019-11-26 12:54:47 | ASBESTOS COMMERCIAL. PLEASE PROVIDE A SIGNED | | | ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD, | | | STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF | | | ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF | | | HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT | | | NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL | | | INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE | | | FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | | | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | | [email protected]. THE INFORMATION SHOULD BE IN PDF | | | FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE | | | THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2020-03-17 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2020-03-17 |
Time |
10:58 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2020-03-16 |
Time |
12:01 |
Sent To |
|
|
| Notes |
| 2020-03-17 10:58:03 | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 19100889 | | | ADD: 2239 PALM BEACH LAKES BLVD. | | | CONT: VINTAGE BUILD & DESIGN | | | TEL: 561-420-2725 | | | E-MAIL: [email protected] | | | CONTACT: TARA BESWICK | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION. | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 3RD REVIEW | | | DATE: TUES. MARCH 17TH/ 202019 | | | ACTION: BUILDING PROVISO | | | | | | 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION 107.3.4.2 | | | DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, | | | DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF | | | THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE | | | APPLICATION AND THAT ARE TO BE SUBMITTED TO THE | | | BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. BEFORE | | | FRAMING INSPECTION AND BUCK INSPECTION. | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | | OFFICIAL. | | | | | | 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, | | | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS | | | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT | | | APPROVALS: | | | (31)(A) EXTERIOR DOORS ,MULLIONS | | | (B) WINDOWS & MULLIONS | | | (C) PANEL WALLS: STOREFRONTS, , WALL LOUVERS, WALL | | | INTAKE OR EXHAUST FANS, EFIS SYSTEMS, | | | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS | | | (G) PRE-ENGINEERED A/C STANDS | | | | | | IDENTIFY GLAZING/ MULLIONS. THE SUBMITTED PRODUCT | | | APPROVALS THE ELEMENTS LISTED BELOW ARE NOT IDENTIFIED. | | | PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE | | | SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION | | | TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH | | | GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, | | | TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED | | | OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND | | | ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B | | | 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE | | | INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S | | | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE | | | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED | | | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. | | | | | | JAMES A. WITMER BN, PX, SFP & CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2020-02-03 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2020-02-03 |
Time |
07:03 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2020-01-28 |
Time |
13:15 |
Sent To |
|
|
| Notes |
| 2020-02-03 07:03:46 | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 19100889 | | | ADD: 2239 PALM BEACH LAKES BLVD. | | | CONT: VINTAGE BUILD & DESIGN | | | TEL: 561-420-2725 | | | E-MAIL: [email protected] | | | CONTACT: TARA BESWICK | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION. | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 2ND REVIEW | | | DATE: MON. FEB. 03/ 2019 | | | ACTION: DENIED | | | | | | 1-3) COMPLIED. | | | | | | 4) 2ND REVIEW, PRODUCT APPROVALS: | | | THE SUBMITTED PRODUCT APPROVALS THE ELEMENTS LISTED | | | BELOW ARE NOT IDENTIFIED. PLEASE IDENTIFY ON THE | | | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF | | | RECORD AND BEFORE SUBMISSION TO THE BUILDING | | | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE | | | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, | | | MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED | | | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE | | | PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1 | | | INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN | | | ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. | | | FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH | | | INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM | | | LOADS AND SPACING USED IN THE TESTS. | | | | | | 4A) FL.812-R8 ARMOR SCREEN SERIES 2000 NONE OF THE | | | ANCHORING SCHEDULES WITHIN THE APPROVAL HAVE BEEN FILED | | | OUT, TYPE OF MOUNTING PER OPENING, CONCRETE, BLOCK | | | WALL, EARTH ANCHORS SPACING, TYPE OF ANCHORS AND THE | | | SQUARE FOOT OPENING AND ASSOCIATED PRESSURES. | | | | | | 4B) MIAMI-DADE NOA 15-0504.01 THE COOKSON CO. 12 FEET 5 | | | INCH WIDE STEEL ROLLING DOOR. PLEASE IDENTIFY THE | | | OPENING SIZE TO BE INSTALLED, THE ASSOCIATED PRESSURES | | | AND ANCHORING TYPE AND SPACING. | | | | | | 4C) MIAMI-DADE NOA DAYBAR INDUSTRIES LS-18 OUTSWING | | | DOOR W/ PANIC / LMI 19 PAGES WITHIN THE REPORT NONE OF | | | THE DOOR TYPE AND HARDWARE WITH ASSOCIATED PRESSURES | | | ARE IDENTIFIED, DOOR SIZE NOT IDENTIFIED, ANCHORING | | | SCHEDULE, GLAZING TYPE, AND PRESSURES. | | | | | | 4D) MIAMI-DADE NOA 17-0630.11 CGI WINDOW AND DOORS | | | HEAVY DUTY CLIPPED TUBE MULLION, 29 PAGES OF SCHEDULES | | | NOTHING IS IDENTIFIED. PLEASE IDENTIFY ON THE PRODUCT | | | APPROVAL BEFORE SUBMITTING TO DESIGNER OF RECORD AND | | | BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL | | | PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING | | | WIDTH & HEIGHT, TYPE OF GLAZING, | | | MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED | | | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE | | | PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1 | | | | | | 4E) MIAMI-DADE NOA 17-1114.01 CGI WINDOWS & DOORS 18 | | | PAGES OF SCHEDULES, NOTHING IS IDENTIFIED. PLEASE | | | IDENTIFY ON THE PRODUCT APPROVAL BEFORE SUBMITTING TO | | | DESIGNER OF RECORD AND BEFORE SUBMISSION TO THE | | | BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, | | | PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF | | | GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR | | | REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND | | | ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B | | | 1405.13.1. | | | | | | 4F) FL-26048-R1 18 PAGES, NOT MARKED, NOT IDENTIFIED. | | | PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE | | | SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION | | | TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH | | | GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, | | | TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED | | | OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND | | | ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B | | | 1405.13.1 | | | | | | 4G) FL 9730-R4. PANEL WALLS/ HURRICANE SHUTTERS. 6 | | | PAGES, NOTHING IS IDENTIFIED. 1609.1.2, 1715.8 & EXIST | | | BUILD CODE 706.4 PROCEDURES: A COMPLETE INSTALLATION | | | SCHEDULE SUMMARIZING & IDENTIFYING OPENING SIZES, STORY | | | HEIGHTS, UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT | | | STORM BAR REINFORCING REQUIREMENTS, WALL PRESSURE | | | ZONES, SLAT TYPES, ETC. | | | | | | 4H) MIAMI-DADE NOA 16-0219.01 TC-5 SERIES STEEL ROOF | | | CURB FOR TRANE ROOF TOP UNITS. PAGE 5 OF REPORT STATES | | | THE RESTRAINT BRACKET QUANTITY DETERMINED SITE SPECIFIC | | | CALCULATIONS BY FLORIDA P.E. OR FLORIDA ARCHITECT. | | | | | | 4I) MIAMI-DADE NOA EITHER ROOF TOP OF SIDEWALL MOUNTED | | | EXHAUST FAN. 13 PAGES NOTHING IS MARKED AS UNIT TYPE, | | | INSTALLATION TYPE WALL OR ROOF MOUNT, ANCHOR TYPE, SIZE | | | OR SPACING WITH ASSOCIATED EITHER WALL OR ROOF | | | PRESSURES. IF ROOF MOUNT, CURB TYPE AND ANCHORAGE TO | | | THE ROOF, AND ANCHORAGE OF THE EXHAUST FAN TO THE ROOF | | | TOP CURB. LATERAL FORCE-RESISTING SYSTEM | | | FOR ALL ROOF TOP EQUIPMENT, CURBS, FANS AND OR VENTS, | | | DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL | | | AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. | | | 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL | | | MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY | | | METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT | | | EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY | | | AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. | | | EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE | | | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES | | | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND | | | LOADS. | | | | | | 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-11-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2019-11-26 |
Time |
12:54 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2019-11-25 |
Time |
12:29 |
Sent To |
|
|
| Notes |
| 2019-11-26 12:54:00 | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 19100889 | | | ADD: 2239 PALM BEACH LAKES BLVD. | | | CONT: VINTAGE BUILD & DESIGN | | | TEL: 561-420-2725 | | | E-MAIL: [email protected] | | | CONTACT: TARA BESWICK | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION. | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: MON. NOV. 25/ 2019 | | | ACTION: DENIED | | | | | | 1) MISSING LIFE SAFETY PLAN. NOT IN THE INDEX OF | | | DRAWINGS. 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FLORIDA BUILDING CODE, CHAPTER 1OF THE ADMINISTRATIVE | | | CODE SECTION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR | | | BUILDINGS. THE EXAMINATION OF THE DOCUMENTS BY THE | | | BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM | | | CRITERIA AND DOCUMENTS: | | | 107.3.5.1 COMMERCIAL BUILDINGS: | | | 107.3.5.1.1 BUILDING | | | OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS | | | SHALL BE DETERMINED AND OR MIXED OCCUPANCIES. | | | MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE | | | TABLES 504.3, TABLE 504.4 & TABLE 506.2). | | | MEZZANINE REQUIREMENTS FOR AREA & EXITING | | | BUILDING HAVE FIRE SPRINKLERS OR NOT? | | | FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: | | | SCHEMATIC FIRE SPRINKLERS / PRE-ENGINEERED SYSTEMS | | | FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL INCLUDE | | | THE FOLLOWING COMPONENTS: | | | FIRE-RESISTANT SEPARATIONS | | | FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION | | | PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS | | | LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL | | | INCLUDE THE FOLLOWING REQUIREMENTS: | | | OCCUPANT LOAD AND EGRESS CAPACITIES | | | OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: | | | OCCUPANCY LOAD | | | GROSS | | | NET | | | MEANS OF EGRESS | | | EXIT ACCESS | | | EXIT | | | EXIT DISCHARGE | | | STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION | | | DOORS | | | EMERGENCY LIGHTING AND EXIT SIGNS | | | SPECIFIC OCCUPANCY REQUIREMENTS: 406 MOTOR-VEHICLE | | | RELATED OCCUPANCIES. | | | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE | | | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED | | | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE | | | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS | | | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. | | | 1B) PLEASE FOR THE NEXT REVIEW PLACE THE SHEETS IN THE | | | FILE FOLDER IN ORDER OF THE PAGE INDEX. 107.2.1.3 | | | QUALITY OF BUILDING PLANS. THE BUILDING OFFICIAL MAY | | | ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS | | | FOR PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE | | | CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY | | | MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE, | | | CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORDS | | | MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH | | | THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES. | | | | | | 2A) SITE PLAN DOES NOT SHOW THE TOTAL OF HOW MANY | | | PARKING SPACES ARE FOR THE CLIENTS AND THE REQUIRED | | | ACCESSIBLE PARKING SPACES AND ACCESS AISLE. PLEASE SHOW | | | COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY CODE 208.2 | | | MINIMUM NUMBER. | | | | | | 2B) THE MARKING OF THE ACCESSIBLE PARKING SPACE AND | | | ACCESS AISLE WILL NEED TO SHOW COMPLIANCE WITH 502.2 & | | | 502.3.3 ALSO SEE ADVISORY, TO LOCAL STANDARDS. PLEASE | | | SEE W. P. B. MUNI CODE ARTICLE XV PARKING CD94:276. | | | | | | 2C) SHOW COMPLIANCE WITH THE 2017 ACCESS. CODE 502.4, | | | EXCEPTION ALLOWS FOR SLOPES NOT STEEPER THAN 1:48 SHALL | | | BE PERMITTED. PLEASE SHOW THE ELEVATIONS OF THE ACCESS. | | | PARKING SPACE AND ACCESS AISLE IN EACH CORNER. | | | | | | 2D) PLEASE PROVIDE THE DISTANCE THE BUILDING IS TO THE | | | PROPERTY LINE ON THE SIDE LOT LINES TO ESTABLISH THE | | | FIRE RESISTANCE RATING REQUIREMENTS FOR EXTERIOR WALLS | | | BASED ON FIRE SEPARATION DISTANCE, FBC-B TABLE 602. | | | | | | 2E) BASED ON THE TABLE 705.8 THE MAXIMUM AREA OF | | | EXTERIOR WALL OPENINGS BASED ON THE FIRE SEPARATION | | | DISTANCE AND DEGREE OF OPENING PROTECTION. | | | | | | 3) SHEET A-2 PROPOSED FLOOR PLAN: | | | 3A) PLEASE PROVIDE A NARRATIVE AS TO WHAT THE FRONT | | | SHOWROOM AREA IS TO HOUSE? THE FRONT ENTRY DOOR # 102 | | | IS AN OVERHEAD GARAGE ENTRY DOOR. IT WOULD APPEAR THE | | | OVERHEAD GARAGE ENTRY DOOR IS ALUMINUM AND GLASS. | | | 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED. | | | | | | 3B) WITHOUT THE DESIGNER OF RECORD STATING THE | | | OCCUPANCY TYPES WITHIN THIS BUILDING IT IS A GUESSING | | | GAME. WE DO NOT KNOW HOW TO CATEGORIZE THE FRONT | | | PORTION OF THE BUILDING, AUTO SHOWROOMS ARE A BUSINESS | | | , THE DISPLAY COULD BE SMALLER ITEMS WHICH WOULD MAKE | | | IT MERCANTILE OCCUPANCY, BUT THERE IS ALSO A WAITING | | | AREA, IS THIS FOR CARS OR FOR PEOPLE? THE BACK PORTION | | | OF THE BUILDING IS SET UP POSSIBLE AS A REPAIR GARAGE | | | OR A S1 OCCUPANCY, BUT THE CLEAN ROOMS COULD BE USED TO | | | STORE AUTOMOBILES WHICH COULD POSSIBLY MAKE AN S2 | | | OCCUPANCY, IS THE BUILDING FIRE SPRINKLERED OR NOT? TO | | | MANY UNKNOWNS TO SHOW COMPLIANCE WITH TABLE 508.4 | | | REQUIRED SEPARATION OF OCCUPANCIES. | | | | | | 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE | | | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED | | | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE | | | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS | | | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. | | | | | | | | | JAMES A. WITMER BN, PX, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2020-03-11 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-03-11 |
Time |
08:16 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-03-11 |
Time |
08:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2020-01-13 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-01-13 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-01-13 |
Time |
10:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-11-21 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-11-21 |
Time |
16:59 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-11-21 |
Time |
16:37 |
Sent To |
|
|
| Notes |
| 2019-11-21 17:03:55 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) PAGE E3.1 FAULLT CURRENT LETTER FROM FPL IS CUT OFF | | | NOT ALL OF IT IS SHOWN | | | | | | 2) PAGE E-3.1 WIRES TO BE TAPPED IN GUTTER ?? NEED TO | | | SHOW SIZE OF CONDUCTORS. | | | | | | 3) PAGE E-3.1 NOTES STATES "OPEN DELTA' ? IS IT OPEN OR | | | CLOSED ? NOT TO MANY OPEN DELTAS EXIST IN THE CITY. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2020-03-10 |
|
|
Cont ID |
|
| Sent By |
sathomas |
Date |
2020-03-10 |
Time |
00:00 |
Rev Time |
0.00 |
| Received By |
sathomas |
Date |
2020-03-10 |
Time |
00:00 |
Sent To |
M |
|
| Notes |
| 2020-03-10 14:16:13 | PROVISO: | | | SUBJECT TO FIELD INSPECTION. | | | | | | S. THOMAS | | | 561-804-4728 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2020-01-21 |
|
|
Cont ID |
|
| Sent By |
sathomas |
Date |
2020-01-21 |
Time |
00:00 |
Rev Time |
0.00 |
| Received By |
sathomas |
Date |
2020-01-21 |
Time |
00:00 |
Sent To |
M |
|
| Notes |
| 2020-01-21 13:16:45 | FIRE COMMENTS WERE NOT ADDRESSED DURING THIS PLAN | | | REVIEW SUBMISSION. | | | | | | A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED | | | AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON | | | THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED DURING PLAN RESUBMISSION. | | | 1) PER SECTION 18.2.3.4.1.1 (NFPA 1), FIRE DEPARTMENT | | | ACCESS ROADS SHALL HAVE A SURFACE DESIGNED TO | | | ACCOMMODATE FIRE APPARATUS WEIGHING AT LEAST 36 TONS. | | | ACCESS ROADS SHALL HAVE AN UNOBSTRUCTED WIDTH OF NOT | | | LESS THAN 20 FEET AND AN UNOBSTRUCTED VERTICAL | | | CLEARANCE OF NOT LESS THAN 13 FEET 6 INCHES. | | | | | | 2) PER SECTION 18.2.3.5.3 (NFPA 1), FIRE LANES SHALL BE | | | MARKED WITH FREESTANDING SIGNS READING, ?FIRE LANE - NO | | | PARKING BY ORDER OF THE FIRE DEPARTMENT.? SIGNS SHALL | | | BE 12? X 18? WITH A WHITE BACKGROUND AND RED LETTERS | | | AND SHALL BE A MAXIMUM OF SEVEN FEET IN HEIGHT TO THE | | | BOTTOM OF THE SIGN. SIGNS SHALL BE WITHIN SIGHT OF THE | | | TRAFFIC FLOW AND BE SPACED A MAXIMUM OF 60 FEET APART. | | | | | | 3) THERE IS NO INDICATION OF A MIXED OR SEPARATED | | | OCCUPANCY: | | | 30.2.2 OCCUPANCY CLASSIFICATION. THE OCCUPANCY | | | CLASSIFICATION OF A REPAIR GARAGE SHALL BE A SPECIAL | | | PURPOSE INDUSTRIAL OCCUPANCY AS DEFINED IN NFPA 101. | | | [30A:7.4.1] | | | 7.4.3 MEANS OF EGRESS. IN A REPAIR GARAGE, THE REQUIRED | | | NUMBER, LOCATION, AND CONSTRUCTION OF MEANS OF EGRESS | | | SHALL MEET ALL APPLICABLE REQUIREMENTS FOR SPECIAL | | | PURPOSE INDUSTRIAL OCCUPANCIES, AS SET FORTH IN NFPA | | | 101, LIFE SAFETY CODE. PER SECTION 7.5.2.1, ACCESS TO | | | AN EXIT SHALL NOT BE THROUGH KITCHENS, STOREROOMS OTHER | | | THAN AS PROVIDED IN CHAPTERS 36 AND 37, RESTROOMS, | | | WORKROOMS, CLOSETS, BEDROOMS OR SIMILAR SPACES, OR | | | OTHER ROOMS OR SPACES SUBJECT TO LOCKING. | | | | | | 4) PER NFPA 101 CH 6, OCCUPANCY CLASSIFICATION: | | | 6.1 CLASSIFICATION OF OCCUPANCY. | | | 6.1.1 GENERAL. | | | 6.1.1.1 OCCUPANCY CLASSIFICATION. THE OCCUPANCY OF A | | | BUILDING OR STRUCTURE, OR PORTION OF A BUILDING OR | | | STRUCTURE, SHALL BE CLASSIFIED IN ACCORDANCE WITH 6.1.2 | | | THROUGH 6.1.13. OCCUPANCY CLASSIFICATION SHALL BE | | | SUBJECT TO THE RULING OF THE AUTHORITY HAVING | | | JURISDICTION WHERE THERE IS A QUESTION OF PROPER | | | CLASSIFICATION IN ANY INDIVIDUAL CASE. | | | 6.1.14.2 DEFINITIONS. | | | 6.1.14.2.1 MULTIPLE OCCUPANCY. A BUILDING OR STRUCTURE | | | IN WHICH TWO OR MORE CLASSES OF OCCUPANCY EXIST. | | | 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE | | | THE OCCUPANCIES ARE INTERMINGLED. | | | 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY | | | WHERE THE OCCUPANCIES ARE SEPARATED BY FIRE RESISTANCE | | | RATED ASSEMBLIES. | | | 6.1.14.3 MIXED OCCUPANCIES. | | | 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE | | | CLASSIFIED AS TO ITS USE IN ACCORDANCE WITH SECTION | | | 6.1. | | | 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST | | | RESTRICTIVE REQUIREMENTS OF THE OCCUPANCIES INVOLVED, | | | UNLESS SEPARATE SAFEGUARDS ARE APPROVED. | | | 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.) | | | 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED, | | | EACH PART OF THE BUILDING COMPRISING A DISTINCT | | | OCCUPANCY, AS DESCRIBED IN THIS CHAPTER, | | | SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY | | | FIRE-RESISTIVE ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2, | | | 6.1.14.4.3, TABLE 6.1.14.4.1(A), | | | AND TABLE 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED | | | BY APPROVED EXISTING SEPARATIONS OR AS OTHERWISE | | | PERMITTED BY 6.1.14.4.6. | | | | | | 7.3.1 OCCUPANCY CLASSIFICATION. THE OCCUPANCY | | | CLASSIFICATION OF A MOTOR FUEL DISPENSING FACILITY THAT | | | IS LOCATED INSIDE A BUILDING OR STRUCTURE SHALL BE A | | | SPECIAL PURPOSE INDUSTRIAL OCCUPANCY AS DEFINED IN NFPA | | | 101, LIFE SAFETY CODE. | | | | | | 3.3.190.8.3 SPECIAL-PURPOSE INDUSTRIAL OCCUPANCY. AN | | | INDUSTRIAL OCCUPANCY IN WHICH ORDINARY AND LOW HAZARD | | | INDUSTRIAL OPERATIONS ARE CONDUCTED IN BUILDINGS | | | DESIGNED FOR, | | | AND SUITABLE ONLY FOR, PARTICULAR TYPES OF OPERATIONS, | | | CHARACTERIZED BY A RELATIVELY LOW DENSITY OF EMPLOYEE | | | POPULATION, WITH MUCH OF THE AREA OCCUPIED BY MACHINERY | | | OR EQUIPMENT. | | | (SAF-IND) | | | | | | THE SEPARATION REQUIRED WOULD NOT JUST BE OCCUPANCY IT | | | WOULD BE HAZARD AS WELL. | | | | | | 6.2 HAZARD OF CONTENTS. | | | 6.2.1 GENERAL. | | | 6.2.1.1 FOR THE PURPOSE OF THIS CODE, THE HAZARD OF | | | CONTENTS SHALL BE THE RELATIVE DANGER OF THE START AND | | | SPREAD OF FIRE, THE DANGER OF SMOKE OR GASES GENERATED, | | | AND THE DANGER OF EXPLOSION OR OTHER OCCURRENCE | | | POTENTIALLY ENDANGERING THE LIVES AND SAFETY OF THE | | | OCCUPANTS OF THE BUILDING OR STRUCTURE. | | | | | | A MIXED OCCUPANCY CLASSIFICATION WOULD STILL NEED TO | | | PROVIDE SEPARATION OF THE STORAGE HAZARD. | | | | | | PLEASE REVIEW AND PROVIDE CLARIFICATIONS | | | | | | 5) A DOOR SCHEDULE IS REQUIRED TO DETERMINE SEPARATION | | | REQUIREMENTS FOR ALL AREAS: | | | | | | THE DOOR SCHEDULE DOES NOT INDICATED THE DOOR | | | LOCKING/LATCHING HARDWARE FPR THE APPLICABLE CODE. | | | | | | PER NFPA , CH 7 MEANS OF EGRESS | | | | | | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. | | | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED | | | READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS | | | OCCUPIED. | | | 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY | | | TO DOOR LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER | | | EXPOSURE TO ELEVATED TEMPERATURE IN ACCORDANCE WITH THE | | | LISTING, BASED ON LABORATORY FIRE TEST PROCEDURES. | | | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE | | | OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR | | | OPERATION FROM THE EGRESS SIDE. | | | 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3 | | | SHALL NOT APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 | | | THROUGH 23. | | | | | | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | ADDITIONAL COMMENTS MAY BE PROVIDED ON THE RE-SUBMITTAL | | | OF THE ABOVE. | | | | | | 7) PLANS SHOW A SPIRAL STAIR IN THE CENTER WEST OF THE | | | BUILDING, HOWEVER THERE ARE NO PLANS THAT INDICATE WHAT | | | WILL BE ON THE SECOND FLOOR AREA. | | | | | | S. THOMAS | | | 561804-4728 | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2019-11-21 |
|
|
Cont ID |
|
| Sent By |
sathomas |
Date |
2019-11-21 |
Time |
13:16 |
Rev Time |
0.00 |
| Received By |
sathomas |
Date |
2019-11-21 |
Time |
12:57 |
Sent To |
E |
|
| Notes |
| 2019-11-21 13:16:09 | A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED | | | AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON | | | THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED DURING PLAN RESUBMISSION. | | | 1) PER SECTION 18.2.3.4.1.1 (NFPA 1), FIRE DEPARTMENT | | | ACCESS ROADS SHALL HAVE A SURFACE DESIGNED TO | | | ACCOMMODATE FIRE APPARATUS WEIGHING AT LEAST 36 TONS. | | | ACCESS ROADS SHALL HAVE AN UNOBSTRUCTED WIDTH OF NOT | | | LESS THAN 20 FEET AND AN UNOBSTRUCTED VERTICAL | | | CLEARANCE OF NOT LESS THAN 13 FEET 6 INCHES. | | | | | | 2) PER SECTION 18.2.3.5.3 (NFPA 1), FIRE LANES SHALL BE | | | MARKED WITH FREESTANDING SIGNS READING, ?FIRE LANE - NO | | | PARKING BY ORDER OF THE FIRE DEPARTMENT.? SIGNS SHALL | | | BE 12? X 18? WITH A WHITE BACKGROUND AND RED LETTERS | | | AND SHALL BE A MAXIMUM OF SEVEN FEET IN HEIGHT TO THE | | | BOTTOM OF THE SIGN. SIGNS SHALL BE WITHIN SIGHT OF THE | | | TRAFFIC FLOW AND BE SPACED A MAXIMUM OF 60 FEET APART. | | | | | | 3) THERE IS NO INDICATION OF A MIXED OR SEPARATED | | | OCCUPANCY: | | | 30.2.2 OCCUPANCY CLASSIFICATION. THE OCCUPANCY | | | CLASSIFICATION OF A REPAIR GARAGE SHALL BE A SPECIAL | | | PURPOSE INDUSTRIAL OCCUPANCY AS DEFINED IN NFPA 101. | | | [30A:7.4.1] | | | 7.4.3 MEANS OF EGRESS. IN A REPAIR GARAGE, THE REQUIRED | | | NUMBER, LOCATION, AND CONSTRUCTION OF MEANS OF EGRESS | | | SHALL MEET ALL APPLICABLE REQUIREMENTS FOR SPECIAL | | | PURPOSE INDUSTRIAL OCCUPANCIES, AS SET FORTH IN NFPA | | | 101, LIFE SAFETY CODE. PER SECTION 7.5.2.1, ACCESS TO | | | AN EXIT SHALL NOT BE THROUGH KITCHENS, STOREROOMS OTHER | | | THAN AS PROVIDED IN CHAPTERS 36 AND 37, RESTROOMS, | | | WORKROOMS, CLOSETS, BEDROOMS OR SIMILAR SPACES, OR | | | OTHER ROOMS OR SPACES SUBJECT TO LOCKING. | | | | | | 4) PER NFPA 101 CH 6, OCCUPANCY CLASSIFICATION: | | | 6.1 CLASSIFICATION OF OCCUPANCY. | | | 6.1.1 GENERAL. | | | 6.1.1.1 OCCUPANCY CLASSIFICATION. THE OCCUPANCY OF A | | | BUILDING OR STRUCTURE, OR PORTION OF A BUILDING OR | | | STRUCTURE, SHALL BE CLASSIFIED IN ACCORDANCE WITH 6.1.2 | | | THROUGH 6.1.13. OCCUPANCY CLASSIFICATION SHALL BE | | | SUBJECT TO THE RULING OF THE AUTHORITY HAVING | | | JURISDICTION WHERE THERE IS A QUESTION OF PROPER | | | CLASSIFICATION IN ANY INDIVIDUAL CASE. | | | 6.1.14.2 DEFINITIONS. | | | 6.1.14.2.1 MULTIPLE OCCUPANCY. A BUILDING OR STRUCTURE | | | IN WHICH TWO OR MORE CLASSES OF OCCUPANCY EXIST. | | | 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE | | | THE OCCUPANCIES ARE INTERMINGLED. | | | 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY | | | WHERE THE OCCUPANCIES ARE SEPARATED BY FIRE RESISTANCE | | | RATED ASSEMBLIES. | | | 6.1.14.3 MIXED OCCUPANCIES. | | | 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE | | | CLASSIFIED AS TO ITS USE IN ACCORDANCE WITH SECTION | | | 6.1. | | | 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST | | | RESTRICTIVE REQUIREMENTS OF THE OCCUPANCIES INVOLVED, | | | UNLESS SEPARATE SAFEGUARDS ARE APPROVED. | | | 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.) | | | 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED, | | | EACH PART OF THE BUILDING COMPRISING A DISTINCT | | | OCCUPANCY, AS DESCRIBED IN THIS CHAPTER, | | | SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY | | | FIRE-RESISTIVE ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2, | | | 6.1.14.4.3, TABLE 6.1.14.4.1(A), | | | AND TABLE 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED | | | BY APPROVED EXISTING SEPARATIONS OR AS OTHERWISE | | | PERMITTED BY 6.1.14.4.6. | | | | | | 7.3.1 OCCUPANCY CLASSIFICATION. THE OCCUPANCY | | | CLASSIFICATION OF A MOTOR FUEL DISPENSING FACILITY THAT | | | IS LOCATED INSIDE A BUILDING OR STRUCTURE SHALL BE A | | | SPECIAL PURPOSE INDUSTRIAL OCCUPANCY AS DEFINED IN NFPA | | | 101, LIFE SAFETY CODE. | | | | | | 3.3.190.8.3 SPECIAL-PURPOSE INDUSTRIAL OCCUPANCY. AN | | | INDUSTRIAL OCCUPANCY IN WHICH ORDINARY AND LOW HAZARD | | | INDUSTRIAL OPERATIONS ARE CONDUCTED IN BUILDINGS | | | DESIGNED FOR, | | | AND SUITABLE ONLY FOR, PARTICULAR TYPES OF OPERATIONS, | | | CHARACTERIZED BY A RELATIVELY LOW DENSITY OF EMPLOYEE | | | POPULATION, WITH MUCH OF THE AREA OCCUPIED BY MACHINERY | | | OR EQUIPMENT. | | | (SAF-IND) | | | | | | THE SEPARATION REQUIRED WOULD NOT JUST BE OCCUPANCY IT | | | WOULD BE HAZARD AS WELL. | | | | | | 6.2 HAZARD OF CONTENTS. | | | 6.2.1 GENERAL. | | | 6.2.1.1 FOR THE PURPOSE OF THIS CODE, THE HAZARD OF | | | CONTENTS SHALL BE THE RELATIVE DANGER OF THE START AND | | | SPREAD OF FIRE, THE DANGER OF SMOKE OR GASES GENERATED, | | | AND THE DANGER OF EXPLOSION OR OTHER OCCURRENCE | | | POTENTIALLY ENDANGERING THE LIVES AND SAFETY OF THE | | | OCCUPANTS OF THE BUILDING OR STRUCTURE. | | | | | | A MIXED OCCUPANCY CLASSIFICATION WOULD STILL NEED TO | | | PROVIDE SEPARATION OF THE STORAGE HAZARD. | | | | | | PLEASE REVIEW AND PROVIDE CLARIFICATIONS | | | | | | 5) A DOOR SCHEDULE IS REQUIRED TO DETERMINE SEPARATION | | | REQUIREMENTS FOR ALL AREAS: | | | | | | THE DOOR SCHEDULE DOES NOT INDICATED THE DOOR | | | LOCKING/LATCHING HARDWARE FPR THE APPLICABLE CODE. | | | | | | PER NFPA , CH 7 MEANS OF EGRESS | | | | | | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. | | | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED | | | READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS | | | OCCUPIED. | | | 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY | | | TO DOOR LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER | | | EXPOSURE TO ELEVATED TEMPERATURE IN ACCORDANCE WITH THE | | | LISTING, BASED ON LABORATORY FIRE TEST PROCEDURES. | | | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE | | | OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR | | | OPERATION FROM THE EGRESS SIDE. | | | 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3 | | | SHALL NOT APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 | | | THROUGH 23. | | | | | | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | ADDITIONAL COMMENTS MAY BE PROVIDED ON THE RE-SUBMITTAL | | | OF THE ABOVE. | | | | | | 7) PLANS SHOW A SPIRAL STAIR IN THE CENTER WEST OF THE | | | BUILDING, HOWEVER THERE ARE NO PLANS THAT INDICATE WHAT | | | WILL BE ON THE SECOND FLOOR AREA. | | | | | | S. THOMAS | | | 561804-4728 | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2020-03-20 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-03-20 |
Time |
16:44 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-03-02 |
Time |
10:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2020-02-05 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-01-08 |
Time |
09:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-12-03 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-12-03 |
Time |
15:22 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-10-24 |
Time |
14:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2020-02-13 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2020-02-13 |
Time |
10:43 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-02-04 |
Time |
12:36 |
Sent To |
|
|
| Notes |
| 2020-02-13 09:32:45 | MU 2020-004757 - RECEIPT 2020-0214-25 - $4,700.73 - | | | PAID | | 2020-02-04 12:36:55 | 2/4/20 EMAILED IMPACT FEE OFFICE FOR REVIEW. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2019-12-02 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-12-02 |
Time |
14:20 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-11-25 |
Time |
12:29 |
Sent To |
|
|
| Notes |
| 2019-12-02 14:20:54 | 109 FBC[AMENDED] PLANS WILL BE REVIEWED BY THE PBC | | | IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON | | | NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR | | | WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE | | | WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY | | | UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO | | | YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE | | | QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE | | | R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU | | | ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE | | | UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2020-03-19 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-03-19 |
Time |
12:01 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-03-19 |
Time |
12:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2020-02-05 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-02-05 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2020-01-31 |
Time |
14:29 |
Sent To |
|
|
| Notes |
| 2020-02-05 14:17:00 | 2ND REVIEW FBC-2017 MECHANICAL | | | PERMIT #19100889 | | | 2/5/20 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE FIRE DEPARTMENT IS QUESTIONING THE OCCUPANCY | | | CLASSIFICATION OF THE PROPOSED PROJECT AND REQUIRES | | | MORE INFORMATION. CURRENTLY IS HAS BEEN CLASSIFIED AS A | | | BUSINESS OCCUPANCY AS STATED ON SHEET A-1, HOWEVER THE | | | PLANS INDICATE THE SPACE WILL BE USED FOR AUTO BODY | | | REPAIR AND DETAILING AS STATED ON SHEET M1.1. IT | | | APPEARS THEN IT WOULD BE AN S-1 STORAGE OCCUPANCY- | | | REPAIR GARAGE. ACCORDING TO THE ENGINEER'S RESPONSE | | | NARRATIVE TO 1ST REVIEW COMMENTS "THERE WILL BE NO | | | MOTOR VEHICLE REPAIR OR OPERATION WITHIN THIS FACILITY; | | | THE VEHICLES WILL BE MOVED USING DOLLIES INSTEAD" FOR | | | THAT REASON HE HAS REMOVED THE CO/NO2 SENSORS AND IS | | | CITING SECTION 502.14 EXCEPTION #3. A) THE EOR MUST | | | PROVIDE THESE STATEMENTS FROM THE NARRATIVE ONTO THE | | | PLAN. B) THE EOR AND/OR CONTRACTOR SHALL PROVIDE A | | | SUBMITTAL FOR THE CAR DOLLIES WITH A REVIEW AND | | | APPROVAL STAMP BY THE EOR- SECTION 107.2.1 WPB. IN | | | ADDITION THE PLANS SHALL SHOW THE DESIGNATED STORAGE | | | AREA FOR THE DOLLIES. | | | | | | 2) THE EF-7 VENTILATION SYSTEM FOR THE DRIVE IN FRONT | | | DRIVE-IN AREA HAS BEEN REMOVED FROM THE RESUBMITTED | | | PLAN. PLEASE REPLACE THE SYSTEM AND UPDATE THE PLANS TO | | | INCLUDE THE FAN SCHEDULE AND SEQUENCING- SECTION 502.14 | | | FBC M. | | | | | | 3) REFER TO SECTION 406.8.2 FBC B AND LOCATE THE | | | CONTROLS FOR THE MANUAL PURGE SYSTEMS TO THE ENTRANCES | | | OF THE BUILDING. | | | | | | 4) SHOW THE LOCATION ON THE PLANS WHERE AUTO BODY AND | | | DETAILING MATERIALS WILL BE STORED. REFER TO SECTION | | | 414.1.3 AND PROVIDE A MATERIALS REPORT AND MSDS SHEETS. | | | A REPORT SHALL BE SUBMITTED TO THE BUILDING OFFICIAL | | | IDENTIFYING THE MAXIMUM EXPECTED QUANTITIES OF | | | HAZARDOUS MATERIALS TO BE STORED, USED IN A CLOSED | | | SYSTEM AND USED IN AN OPEN SYSTEM, AND SUBDIVIDED TO | | | SEPARATELY ADDRESS HAZARDOUS MATERIAL CLASSIFICATION | | | CATEGORIES BASED ON TABLES 307.1(1) AND 307.1(2). THE | | | METHODS OF PROTECTION FROM SUCH HAZARDS, INCLUDING BUT | | | NOT LIMITED TO CONTROL AREAS, FIRE PROTECTION SYSTEMS | | | AND GROUP H OCCUPANCIES SHALL BE INDICATED IN THE | | | REPORT AND ON THE CONSTRUCTION DOCUMENTS. THE OPINION | | | AND REPORT SHALL BE PREPARED BY A QUALIFIED PERSON, | | | FIRM OR CORPORATION APPROVED BY THE BUILDING OFFICIAL | | | AND PROVIDED WITHOUT CHARGE TO THE ENFORCING AGENCY. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2019-11-26 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-11-26 |
Time |
14:46 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-11-26 |
Time |
14:28 |
Sent To |
|
|
| Notes |
| 2019-11-26 15:46:32 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #19100889 | | | 11/26/19 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M0.2 & M1.1: THE HONEYWELL SENSOR ANALYTICS | | | ARE FOR THE SERVICE BAY, HOWEVER NO SERVICE BAY IS | | | SHOWN ON THE FLOOR PLAN- SECTION 107.2.1 WPB. | | | | | | 2) M0.2 & M1.1: THE O/A CALCULATIONS IDENITFY SOME OF | | | THE SPACES AS BOTH REPAIR AND ENCLOSED PARKING GARAGE. | | | PLEASE REVISE THE ANALYTICS AND VENTILATION | | | CALCULATIONS TO INDICATE A MINIMUM VENTILATION AIRFLOW | | | RATE OF 0.05 CFMS PER SF. SHALL BE MAINTAINED | | | CONTINOUSLY- SEE SECTION 404.2 FBC M. | | | | | | 3) M0.2 & M1.1: NO SEQUENCES OF OPERATION ARE PROVIDED | | | FOR EF-3, EF-4, AND EF-6. THERE ARE NO SENSORS SHOWN IN | | | THESE ROOMS, HOWEVER IT APPEARS VEHICLES WILL BE WORKED | | | ON OR STORED IN THESE ROOMS. PLEASE NOTE THAT | | | RECIRCULATION OF AIR FROM THE DETAIL AREA VIA THE | | | TRANSFERS TO THE CLEAN #1 ROOM MAY BE PROHIBITED | | | DEPENDING ON WHAT THE USE OF THE ROOM IS - SEE TABLE | | | 403.3.1.1 FBC M FOOTNOTE B. | | | | | | 4) M0.2: PLEASE PROVIDE AN AIR BALANCE CALCULATION- | | | SECTION 501.4 FBC M. | | | | | | 5) M1.1 PROVIDE FL. PRODUCT APPROVALS OR MIAMI-DADE | | | NOA'S FOR THE LOUVERS AND WALL FANS- RULE 9N-3 FAC. | | | PLEASE NOTE THAT NOA #16-0209.05 SHOWN ON SHEET M0.5 IS | | | EXPIRED. | | | | | | 6) M1.1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE AIR | | | DRYER AND A PIPING PLAN- SECTION 107.2.1. | | | | | | 7) PROVIDE ENGINEERING FOR INSTALLATION ON THE NEW | | | RTU-1- SECTION 301.15 FBC M. | | | | | | 8) THE AC CALCULATIONS ARE INCORRECTLY INDICATING MIAMI | | | AS THE PROJECT LOCATION- SECTION 107.2.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2020-03-21 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-03-21 |
Time |
13:29 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-03-21 |
Time |
13:29 |
Sent To |
|
|
| Notes |
| 2020-03-21 13:30:12 | 19100889 2239 PALM BEACH LAKES BLVD | | | | | | PLUMBING APPROVED W/PROVISO | | | | | | I. OIL/WATER SEPARATOR DRAW OFF TANK | | | 1. PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, REGARDING | | | THE OIL/WATER SEPARATOR DRAW OFF TANK, PROVIDE AS A | | | DEFERRED SUBMITTAL THE FOLLOWING: | | | CLARIFICATION AS TO WHETHER THE SYSTEM IS NEW OR | | | EXISTING. IF EXISTING, SHOW LOCATION AND PROVIDE | | | CERTIFICATION SHOWING COMPLIANCE WITH FLORIDA DEP. IF | | | NEW, SUBMIT SPECIFICATION, DETAIL AND LOCATION OF NEW | | | TANK AND PIPING. DOCUMENT SHALL BE SUBMITTED, APPROVED | | | AND ON SITE PRIOR TO FINAL INSPECTION. PROCEED AT YOUR | | | OWN RISK. | | | II. DRINKING FOUNTAIN | | | 1. UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE | | | COMPLYING WITH FBC ACC 305 POSITIONED FOR A FORWARD | | | APPROACH AND CENTERED ON THE UNIT. KNEE AND TOE | | | CLEARANCE COMPLYING WITH FBC ACC 306 SHALL BE PROVIDED | | | PER FBC ACC 602.2. | | | 2. OPERABLE PARTS SHALL COMPLY WITH FBC ACC 309 PER FBC | | | ACC 602.3. | | | 3. SPOUT OUTLETS SHALL BE 36 INCHES MAXIMUM ABOVE THE | | | FINISH FLOOR OR GROUND PER FBC ACC 602.4. | | | 4.THE SPOUT SHALL BE LOCATED 15 INCHES MINIMUM FROM THE | | | VERTICAL SUPPORT AND 5 INCHES MAXIMUM FROM THE FRONT | | | EDGE OF THE UNIT, INCLUDING BUMPERS PER FBC ACC 602.5. | | | III. BREAKROOM SINK | | | 1. LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE | | | FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 | | | INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC | | | ACC 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE AS | | | REQUIRED BY FBC ACC 306.2 AND 306.3 | | | | | | | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PH: 561-805-6715 | | | | | | 19100889 2239 PALM BEACH LAKES BLVD | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2020-03-20 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-03-20 |
Time |
16:44 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-03-19 |
Time |
14:38 |
Sent To |
|
|
| Notes |
| 2020-03-20 16:44:10 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL | | | MANUAL REVISED 2017 | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | 19100889 2239 PALM BEACH LAKES BLVD | | | | | | 3RD REVIEW | | | PLUMBING COMMENTS:DENIED | | | 1. CONCERNING ITEM 10 REVIEW 2; SUBMIT MSDS SHEETS FOR | | | THE CHEMICALS TO BE USED IN | | | THE CHEMICAL DISPENSER AND THE AMOUNTS TO BE STORED AND | | | HOW THEY ARE STORED.WPB AMEND. TO FBC SEC. 107.2.1. | | | NEW COMMENT: IF ARCHITECT IS TO RESPOND TO THIS THEN HE | | | NEEDS TO DO SO PRIOR TO APPROVAL FOR PLUMBING PERMIT. | | | 2.CONCERNING ITEM 10 REVIEW 2; SUBMIT MANUFACTURER'S | | | SPECIFICATIONS/INSTALLATION | | | MANUAL FOR THE WATER SOFTENING SYSTEM. WPB AMEND. TO | | | FBC SEC. 107.2.1. | | | NEW COMMENT: IF THERE IS NO WATER SOFTENER THEN REMOVE | | | REFERENCE TO SOFTENED WATER FOR ITEM W-3 CHEMICAL | | | DISPENSING CENTER ON PLAN SHEET P1.1 | | | 3. IS THE OIL/SEPERATOR DRAW OFF TANK AND DRAIN | | | EXISTING? IF SO SHOW LOCATION AND PROVIDE CERTIFICATION | | | SHOWING COMPLIANCE WITH FLORIDA DEP OR SUBMIT SPEC AND | | | DETAIL AND LOCATION OF NEW PIPING AND TANK. CONTACT TIM | | | LARGE AT 561-805-6692 FOR FURTHER CLARIFICATION. | | | | | | PROVISO | | | I. DRINKING FOUNTAIN | | | 1.UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE | | | COMPLYING WITH FBC ACC 305 POSITIONED FOR A FORWARD | | | APPROACH AND CENTERED ON THE UNIT. KNEE AND TOE | | | CLEARANCE COMPLYING WITH FBC ACC 306 SHALL BE PROVIDED | | | PER FBC ACC 602.2. | | | 2.OPERABLE PARTS SHALL COMPLY WITH FBC ACC 309 PER FBC | | | ACC 602.3. | | | 3.SPOUT OUTLETS SHALL BE 36 INCHES MAXIMUM ABOVE THE | | | FINISH FLOOR OR GROUND PER FBC ACC 602.4. | | | 4.THE SPOUT SHALL BE LOCATED 15 INCHES MINIMUM FROM THE | | | VERTICAL SUPPORT AND 5 INCHES MAXIMUM FROM THE FRONT | | | EDGE OF THE UNIT, INCLUDING BUMPERS PER FBC ACC 602.5. | | | II. BREAKROOM SINK | | | 1. LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE | | | FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 | | | INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC | | | ACC 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE AS | | | REQUIRED BY FBC ACC 306.2 AND 306.3 | | | | | | | | | | | | END OF COMMENTS. | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE | | | DESIGNER IN ACCORDANCE WITH FAC AND FS. | | | | | | | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | | | | | | | 19100889 2239 PALM BEACH LAKES BLVD | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2020-01-17 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2020-01-17 |
Time |
12:58 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2020-01-16 |
Time |
09:49 |
Sent To |
|
|
| Notes |
| 2020-01-17 12:58:13 | 1) THE PLANS INDICATE AN AIR COMPRESSOR. SUBMIT A | | | COMPRESSED AIR RISER DIAGRAM IF ANY RIDGID AIR PIPING | | | IS TO BE INSTALLED. SHOW THE TYPE OF MATERIAL, PIPE | | | SIZIES, LOCATION OF VALVES, ETC. NOTE: PVC PIPING IS | | | NOT PERMITTED TO BE USED FOR COMPRESSED AIR PER | | | MANUFACTURER'S SPECIFICATIONS. WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | 2) SUBMIT MANUFACTURER'S SPECIFICATIONS AND | | | INSTALLATION MANUAL FOR THE CHEMICAL DISPENSING UNIT. | | | IF THIS IS CONNECTED TO THE POTABLE WATER SYSTEM IN ANY | | | MANNER A BACKFLOW DEVICE WILL BE REQUIRED. WPB AMEND. | | | TO FBC SEC. 107.2.1. | | | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE OIL | | | INTERCEPTOR. WPB AMEND. TO FBC SEC. 107.2.1. | | | 4) SHT. P0.2 - DETAIL #6 - THE OIL INTERCEPTOR SHALL | | | COMPLY WITH 2017 FBC - PLUMBING SEC.1003.4.2.1. | | | 5) THE DRINKING FOUNTAIN SHALL BE LOCATED WHERE IT IS | | | ACCESSIBLE TO THE CUSTOMERS. THERE IS A TIRE CHANGING | | | MACHINE RIGHT NEXT TO THE DRINKING FOUNTAIN. THIS | | | CREATES A POSSIBLE UNSAFE ENVIRONMENT FOR A | | | NON-EMPLOYEE USING THIS FIXTURE. UNSAF AND I FIND IT | | | HARD TO BELIEVE THAT THE BUSINESS ALLOWS CUSTOMERS IN | | | THE WORK AREA DUE TO LIABILITY. IF THIS IS THE CASE, A | | | NOTARIZED LETTER FROM THE OWNER OF THE BUSINESS SHALL | | | BE SUBMITTED SPECIFICALLY STAING THEAT CUSTOMERS WILL | | | BE PERMITTED IN THE WORK AREA AND THAT THE BUSINESS | | | OWNER ACCEPTS ALL LIABILITY. | | | 6) A MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED PER | | | 2017 FBC-PLUMBING SEC. 410.3. | | | 7) THE WASHING MACINE SHALL BE INSTALLED ON A MINIMUM 3 | | | INCH WASTE STACK. 2017 FBC-PLUMBING SEC.406.2. | | | 8) SUBMIT DETAILS/MANUFACTURER'S SPECIFICATIONS FOR THE | | | PRESSURE WASHER SYSTEM. WILL ANY RIDGID PIPING BE | | | INSTALLED FOR THIS SYSTEM? IF SO, SUBMIT A PIPING | | | DIAGRAM SHOWING PIPE MATERIAL, PIPE SIZES, VALVES, ETC. | | | 9) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE POINT | | | OF USE WATER HEATERS AT THE LAVATORIES.WPB AMEND. TO | | | FBC SEC. 107.2.1. | | | 10) SUBMIT MSDS SHEETS FOR THE CHEMICALS TO BE USED IN | | | THE CHEMICAL DISPENSER AND THE AMOUNTS TO BE STORED AND | | | HOW THEY ARE STORED.WPB AMEND. TO FBC SEC. 107.2.1. | | | 11) SUBMIT MANUFACTURER'S SPECIFICATIONS/INSTALLATION | | | MANUAL FOR THE WATER SOFTENING SYSTEM. WPB AMEND. TO | | | FBC SEC. 107.2.1. | | | 12) THE IRRIGATION SYSTEM WILL NEED A SEPARATE BACKFLOW | | | PREVENTION DEVICE AND A SEPARATE PERMIT WILL BE | | | REQUIRED FOR THE BACKFLOW PER THE CITY OF WEST PALM | | | BEACH CROSS CONNECTION CONTROL MANUAL. | | | 13) A LINT INTERCEPTTOR IS REQUIRED PER 2017 | | | FBC-PLUMBING SEC1003.6. AFTER DOING ADDITIONAL RESEARCH | | | IN THE IPC COMMENTARY, EXCEPTION #2 REFERS TO WASHING | | | MACHINES THAT WOULD BE LOCATED IN COMMON LAUNDRY ROOMS | | | IN RESIDENTIAL BUILDINGS, NOT IN A COMMECIAL BUILDING, | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2019-11-27 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-11-27 |
Time |
08:09 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-11-21 |
Time |
16:59 |
Sent To |
|
|
| Notes |
| 2019-11-27 08:09:55 | PLUMBING 1ST REVIEW**DENIED**19100889 | | | | | | 1) SHOW THE WASHER AND DRYER AS BEING ACCESSIBLE WITH A | | | PARALLEL APPROACH CENTERED ON THE FIXTURE FBC-ACC 611.2 | | | AND HEIGHT OF BOTH COMPLYING WITH FBC-ACC 611.4 | | | | | | 2) SHOW CABINET HEIGHT DETAIL AND CLEAR FLOOR SPACE FOR | | | BOTH THE BREAK ROOM SINK AND SINK LOCATED IN THE | | | LAUNDRY ROOM MAX 34?. FBC-ACC 804.3.1, 804.3.2 | | | | | | 3) ARE CUSTOMERS PERMITTED IN THE WORK SPACE TO ACCESS | | | THE DRINKING FOUNTAIN? PLEASE CLARIFY. FBC 107.2.1 | | | | | | 4) PROVIDE BUILDING OCCUPANCY AND OCCUPANT LOAD. FBC | | | 107.3.5 | | | | | | 5) PROVIDE INSTALLATION MANUAL FOR THE TANKLESS WATER | | | HEATER AND GREASE INTERCEPTOR. FBC 107.2.1 | | | | | | 6) PROVIDE TOTAL DEVELOPED LENGTH OF PIPING FOR THE | | | WATER HEATER TO FURTHEST OUTLET. FBC-PLB 607.2 | | | | | | 7) PROVIDE LINT INTERCEPTOR FOR THE WASHING MACHINE. | | | FBC-PLB 1003.6 | | | | | | 8) PROVIDE NOTE RPZ BACKFLOW IF NOT ALREADY ON-SITE | | | WILL BE REQUIRED AND INSTALLATION MUST BE PERFORMED BY | | | A LIC. PLUMBER ONLY WITH SEPARATE PERMIT. SAME OF | | | IRRIGATION SYSTEM ON ITS OWN WATER METER | | | | | | TIM HUNT | | | | | | PLUMBING PLANS EXAMINER | | | | | | CITY OF WEST PALM BEACH (CGA SOLUTIONS) | | | [email protected] | | | | | | 561-248-2703 | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2020-03-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-03-11 |
Time |
07:33 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-03-11 |
Time |
07:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2020-02-03 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-02-03 |
Time |
16:55 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-02-03 |
Time |
16:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2019-12-02 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-12-02 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-12-02 |
Time |
14:15 |
Sent To |
|
|
| Notes |
| 2019-12-02 14:20:16 | 61G15-23 PE RULES FAC, FS 471 ENGINEERING FS | | | DIGITALLY SIGN WITH A DIGITAL SIGNATURE ISSUED TO YOU | | | BY A 3RD PARTY CERTIFICATION AUTHORITY. | | | | | | -ANY ADDITIONAL SHEETS THATY ARE DIGITALLY SIGNED BY AN | | | ENGINEER SHOULD BE VERIFIED BY A 3RD PARTY | | | CERTIFICATION AUTHORITY. | | | | | 2019-11-26 16:06:44 | MECH PLANS OK. ENERGY CALCULATION SIGNATURE AND SEAL | | | COULD NOT BE VALIDATED. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2020-03-11 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
2020-03-11 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2020-02-04 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2020-02-04 |
Time |
|
Rev Time |
0.00 |
| Received By |
awooten |
Date |
2020-02-04 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-02-04 15:24:16 | ******************************ZONING | | | REVIEW****************************** | | | | | | THE LANDSCAPE PLAN REQUIRES A SEPARATE PERMIT. | | | | | | | | | ALANA WOOTEN | | | PLANNER | | | PLANNING DIVISION | | | 561-822-1449 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2019-12-02 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2019-12-02 |
Time |
|
Rev Time |
|
| Received By |
awooten |
Date |
2019-12-02 |
Time |
|
Sent To |
|
|
| Notes |
|
|
|