| Plan Review Stops For Permit 19100856 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2019-12-14 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-12-14 |
Time |
11:12 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-12-14 |
Time |
08:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-10-19 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-10-19 |
Time |
11:30 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-10-16 |
Time |
15:50 |
Sent To |
|
|
| Notes |
| 2019-10-19 11:31:18 | BUILDING PLAN REVIEW | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | | | | ADMINISTRATIVE NOTICE: | | | | | | A SEPERATE PERMIT NUMBER (19100856) HAS BEEN ASSIGNED | | | TO THE CABANA. A VALUE OF $30,000.00 HAS BEEN ASSIGNED | | | TO IT WITH A CORRESPONDING REDUCTION IN VALUE OF THE | | | MAIN RESIDENCE, PERMIT NUMBER (19090792). | | | | | | 1. AN ELEVATION CERTIFICATE IS REQUIRED. SEE COMMENTS | | | UNDER THE NFIP REVIEW. | | | | | | 2. PROVIDE A SOILS REPORT. | | | R401.4 SOIL TESTS. | | | WHERE QUANTIFIABLE DATA CREATED BY ACCEPTED SOIL | | | SCIENCE METHODOLOGIES INDICATE EXPANSIVE, COMPRESSIBLE, | | | SHIFTING OR OTHER QUESTIONABLE SOIL CHARACTERISTICS ARE | | | LIKELY TO BE PRESENT, THE BUILDING OFFICIAL SHALL | | | DETERMINE WHETHER TO REQUIRE A SOIL TEST TO DETERMINE | | | THE SOIL?S CHARACTERISTICS AT A PARTICULAR LOCATION. | | | THIS TEST SHALL BE DONE BY AN APPROVED AGENCY USING AN | | | APPROVED METHOD. | | | | | | 3. PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. | | | SEE COMMENTS UNDER THE IMPACT FEE REVIEW. | | | | | | 4. THIS PROPERTY IS LOCATED WITHIN A HISTORIC DISTRICT. | | | DEFERRAL OF PRODUCT APPROVALS AS NOTED ON PLAN PAGE | | | A-0.0 ARE NOT ALLOWED. SUBMIT ALL PRODUCT APPROVALS FOR | | | REVIEW. | | | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE ROOFING, WINDOW AND DOOR | | | SUBMITTALS. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED. | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2020-02-01 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-02-01 |
Time |
09:37 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-02-01 |
Time |
08:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2019-12-16 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-12-16 |
Time |
09:23 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-12-14 |
Time |
08:39 |
Sent To |
|
|
| Notes |
| 2019-12-16 09:23:48 | PLAN REVIEW - ELECTRICAL | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 2ND REVIEW | | | | | | RESULTS: DENIED | | | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PROVIDE SERVICE OUTLET AT CU-1 & CU-6. | | | E3901.12 HVAC OUTLET. | | | | | | 2. AVAILABLE FAULT CURRENT FROM FPL TRANSFORMER IS | | | 30684. FAULT CURRENT USED ON PAGE E-5 FOR AVAILABLE | | | FAULT CURRENT CALCULATIONS IS 52,205. PLEASE CORRECT. | | | PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT CURRENT | | | AT NEW PANEL TO CONFIRM AIC RATING IS ADEQUATE. NEC | | | 110.10 & FBC RE E3404.3 | | | | | | 3. REMOVE PANEL DP FROM RISER DIAGRAHM. PANEL DP IS TO | | | BE REMOVED FROM SOW PER RESPONSE LETTER FROM DESIGNER. | | | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | 4. PANEL B SHOWS A TOTAL LOAD OF 119 AMPS. OVERCURRENT | | | PROTECTION FROM MDP IS 100 AMPS. PLEASE CORRECT. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-10-22 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2019-10-22 |
Time |
07:00 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2019-10-22 |
Time |
06:36 |
Sent To |
|
|
| Notes |
| 2019-10-22 07:00:47 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | | | | 1. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET AND SWITCH | | | CONTROLLED LIGHT FOR SERVICING EACH AHU LOCATED IN AN | | | ATTIC. FBC MECHANICAL CODE M306.3.1 | | | | | | 2. RECEPTACLES IN OUTSIDE GRILL/PATIO AREA MUST BE GFCI | | | PROTECTED. NEC 210.8A3 | | | | | | 3. SERVICE RECEPTACLE WITH GFCI PROTECTION REQUIRED | | | WITHIN 25FT OF CU OUTSIDE. NEC 210.63 | | | | | | 4. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A | | | DISCONNECTING MEANS AT THE BUILDING OR SEPARATE | | | STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR | | | MAIN BREAKER AT THE PANEL FOR PANEL P. NEC 225.31, | | | 225.32 | | | | | | 5. A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE | | | ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND | | | CONNECTED TOGETHER. PROVIDE DETAILS ON PLAN OF | | | GROUNDING ELECTRODE SYSTEM AND WIRING. NEC 250.32; FBC | | | RE E3607.3 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-657-1653 | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
P |
Date |
2020-02-06 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2020-02-06 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2020-02-06 |
Time |
15:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2019-12-23 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2019-12-23 |
Time |
11:40 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2019-12-23 |
Time |
11:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-12-24 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2019-12-24 |
Time |
08:04 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-10-16 |
Time |
15:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2020-02-06 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2020-02-06 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-12-23 |
Time |
09:39 |
Sent To |
|
|
| Notes |
| 2020-02-06 15:51:16 | SEE 19090792 |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2019-10-19 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-10-19 |
Time |
11:27 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-10-16 |
Time |
15:50 |
Sent To |
|
|
| Notes |
| 2019-10-19 11:28:39 | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL | | | (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE | | | PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE | | | RETURN STAMPED AND WITH A COPY OF THE RECEIPT AS | | | APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE | | | QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE | | | FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD | | | MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2019-10-19 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-10-19 |
Time |
08:32 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-10-16 |
Time |
15:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
4 |
Status |
P |
Date |
2020-02-03 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-02-03 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-02-03 |
Time |
16:26 |
Sent To |
|
|
| Notes |
| 2020-10-27 15:48:09 | PROVISO: A BUILDING UNDER CONSTRUCTION ELEVATION | | | CERTIFICATE IS REQUIRED AT PLACEMENT OF 1ST FLOOR. | | | NOTE: PROVIDE THIS EC TO CITY BUILDING INSPECTOR. | | | | | | A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS | | | REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL | | | PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY. | | | NOTE: YOU MAY SUBMIT THIS EC FOR REVIEW AFTER FINAL | | | GRADE AND PLACEMENT OF EQUIPMENT SERVICING THE | | | BUILDING. | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
3 |
Status |
F |
Date |
2020-02-01 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-02-01 |
Time |
08:32 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-02-01 |
Time |
08:32 |
Sent To |
|
|
| Notes |
| 2020-02-01 08:33:12 | PLAN REVIEW - NFIP | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 3RD REVIEW | | | | | | RESULTS: DENIED | | | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. SECTION C2 REQUIRES BENCHMARK UTILIZED TO BE | | | DESCRIBED IN COMMENTS SECTION. | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
2 |
Status |
F |
Date |
2019-12-23 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-12-23 |
Time |
09:37 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-12-14 |
Time |
13:42 |
Sent To |
|
|
| Notes |
| 2019-12-23 09:38:26 | PLAN REVIEW - NFIP | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. SECTION C2 REQUIRES BENCHMARK UTILIZED TO BE | | | DESCRIBED IN COMMENTS SECTION. | | | | | | | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
1 |
Status |
F |
Date |
2019-10-19 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-10-19 |
Time |
11:26 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-10-19 |
Time |
07:44 |
Sent To |
|
|
| Notes |
| 2019-10-19 11:27:02 | NFIP REVIEW | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | THIS PROPERTY IS LOCATED IN A FLOOD ZONE AE. AN | | | ELEVATION CERTIFICATE IS REQUIRED. | | | | | | NFIP REVIEW | | | CITY OF WEST PALM BEACH ORDINANCE NO. 4658-16 | | | AS OF OCTOBER 5, 2017, THE FEDERAL EMERGENCY MANAGEMENT | | | AGENCY (FEMA) ESTABLISHED A NEW FLOOD INSURANCE RATE | | | MAP (FIRM) UTILIZING THE RECENTLY COMPLETED FLOOD | | | HAZARD DETERMINATION (FHD) FOR THE CITY OF WEST PALM | | | BEACH, FL. | | | ALL NEW BASE FLOOD ELEVATIONS (BFE) SHALL BE BASED ON | | | NAVD88 DATUM. ON AUGUST 23, 2017, THE CITY OF WEST PALM | | | BEACH, BY ORDINANCE, NO. 4658-16, ESTABLISHED A TWO | | | FOOT FREEBOARD ABOVE THE (BFE). | | | | | | THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD AREA | | | (SFHA). THE SPECIFIC ZONE DESIGNATION FOR THIS SITE IS | | | AE WITH A BASE FLOOD ELEVATION (BFE) OF 7FT. THE CITY | | | OF WEST PALM BEACH (THROUGH ORDINANCE) REQUIRES AN | | | ADDITIONAL 24 INCHES OF FREEBOARD REQUIRING THE DESIGN | | | FLOOD ELEVATION (DFE) TO BE 9. 0 FEET. PLEASE NOTE THIS | | | INFORMATION ON YOUR PLANS. | | | | | | A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS | | | REQUIRED AT TIME OF PERMIT APPLICATION. | | | NOTE: ALL EQUIPMENT SERVICING THE BUILDINGS ON THIS | | | SITE ARE REQUIRED TO BE AT OR ABOVE 9 FEET NAVD. | | | | | | AN UNDER CONSTRUCTION (FORMBOARD) SURVEY WITH FINISHED | | | FLOOR ELEVATION IS REQUIRED. | | | | | | A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS | | | REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL | | | PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY. | | | THIS EC MAY BE SUBMITTED FOR REVIEW PRIOR TO BUILDING | | | FINAL. | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2020-02-04 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2020-02-04 |
Time |
10:57 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2020-02-04 |
Time |
10:55 |
Sent To |
|
|
| Notes |
| 2020-02-04 10:57:21 | PLUMBING COMMENTS: APPROVED | | | ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD | | | INSPECTOR'S APPROVAL | | | RE: PERMIT 19100856 FOR MAIN HOUSE |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2019-12-20 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-12-20 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-12-14 |
Time |
08:39 |
Sent To |
|
|
| Notes |
| 2019-12-20 11:34:18 | SEE PLUMBING REVIEW COMMENTS ON PERMIT 19090792. CT |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2020-01-28 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-01-28 |
Time |
11:31 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-01-28 |
Time |
11:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2019-12-14 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-12-14 |
Time |
11:13 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-12-14 |
Time |
11:13 |
Sent To |
|
|
| Notes |
| 2019-12-14 11:14:15 | BUILDING PLAN REVIEW - ROOFING | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 2ND REVIEW | | | | | | RESULTS: DENIED | | | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. THIS PROPERTY IS LOCATED WITHIN A HISTORIC DISTRICT. | | | DEFERRAL OF PRODUCT APPROVALS AS NOTED ON PLAN PAGE | | | A-0.0 ARE NOT ALLOWED. SUBMIT ALL PRODUCT APPROVALS FOR | | | REVIEW. | | | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE ROOFING, WINDOW AND DOOR | | | SUBMITTALS. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED. | | | | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2019-10-19 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-10-19 |
Time |
11:28 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-10-16 |
Time |
15:50 |
Sent To |
|
|
| Notes |
| 2019-10-19 11:29:53 | BUILDING PLAN REVIEW - ROOFING | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. THIS PROPERTY IS LOCATED WITHIN A HISTORIC DISTRICT. | | | DEFERRAL OF PRODUCT APPROVALS AS NOTED ON PLAN PAGE | | | A-0.0 ARE NOT ALLOWED. SUBMIT ALL PRODUCT APPROVALS FOR | | | REVIEW. | | | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE ROOFING, WINDOW AND DOOR | | | SUBMITTALS. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED. | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2019-12-14 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-12-14 |
Time |
11:12 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-12-14 |
Time |
08:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2020-02-06 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2020-02-06 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2020-02-06 |
Time |
15:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2019-12-23 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2019-12-23 |
Time |
11:40 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2019-12-23 |
Time |
11:40 |
Sent To |
|
|
| Notes |
|
|