| Plan Review Stops For Permit 19100818 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2019-12-03 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-12-03 |
Time |
10:59 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-12-03 |
Time |
10:40 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-10-25 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-10-25 |
Time |
06:58 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-10-25 |
Time |
06:34 |
Sent To |
|
|
| Notes |
| 2019-10-25 06:49:26 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | 1) THE P.E. DID NOT SIGN AND SEAL THE POOL PLANS. | | | 61G15-23.003 PROCEDURES FOR PHYSICALLY SIGNING AND | | | SEALING PLANS, SPECIFICATIONS, REPORTS OR OTHER | | | DOCUMENTS. | | | ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER | | | DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN | | | ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025, | | | F.S., AND RULE 61G15-23.001, F.A.C. MUST BE PHYSICALLY | | | SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE | | | PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. | | | (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE | | | LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE | | | SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR | | | COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE | | | USED. | | | (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY | | | CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY | | | OVERLAPPING THE LICENSEE'S SIGNATURE ON EACH PAGE | | | REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL | | | NOT RENDER THE SIGNATURE ILLEGIBLE. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2019-11-26 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-11-26 |
Time |
11:39 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-11-26 |
Time |
11:39 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-11-04 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2019-11-04 |
Time |
06:53 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2019-11-04 |
Time |
05:59 |
Sent To |
I |
|
| Notes |
| 2019-11-04 06:53:36 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED BY THE | | | ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS | | | 471.003(2)(H); 471.025; WPB FBC 107.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN | | | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE | | | 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A | | | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO | | | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT | | | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE | | | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: | | | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | | UILDING-PERMIT-FORMS | | | | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-657-1653 | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2019-10-31 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2019-10-31 |
Time |
07:26 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2019-10-31 |
Time |
07:26 |
Sent To |
|
|
| Notes |
| 2019-10-31 07:28:31 | GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN | | | THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN | | | PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND PLANS | | | WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE | | | RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT | | | REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE PER | | | THE WPB AMENDMENTS TO FBC SEC. 107.2.1. |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
P |
Date |
2019-11-15 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2019-11-15 |
Time |
16:01 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2019-11-15 |
Time |
16:01 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2019-10-23 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2019-10-23 |
Time |
16:04 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2019-10-23 |
Time |
16:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-12-03 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-12-03 |
Time |
11:00 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-11-13 |
Time |
15:57 |
Sent To |
|
|
| Notes |
| 2019-11-14 15:58:01 | RESUB ROUTED TO ZONING INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-11-04 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2019-11-04 |
Time |
06:53 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2019-10-16 |
Time |
11:35 |
Sent To |
|
|
| Notes |
| 2019-10-17 11:35:28 | ROUTED TO ZONING INBOX |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2019-11-26 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2019-11-26 |
Time |
15:28 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2019-11-26 |
Time |
15:28 |
Sent To |
|
|
| Notes |
| 2019-11-26 15:28:50 | 11/26/19 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM | | | THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND | | | NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF | | | PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY | | | ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM | | | [email protected] | | | 561-701-6437 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2019-10-31 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2019-10-31 |
Time |
07:26 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2019-10-31 |
Time |
07:26 |
Sent To |
|
|
| Notes |
| 2019-10-31 07:26:25 | 10/31/2019 1ST PLUMBING/POOL REVIEW **DENIED** WITH | | | COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. HEATED SWIMMING POOLS AND INGROUND PERMANENTLY | | | INSTALLED SPAS SHALL BE EQUIPPED WITH A VAPOR-RETARDANT | | | COVER ON OR AT THE WATER SURFACE OR A LIQUID COVER OR | | | OTHER MEANS PROVEN TO REDUCE HEAT LOSS. 2017 FBC- | | | ENERGY- SEC. R 403.10.3. | | | 2. SIGNATURE (OR SEAL, OR TITLE BLOCK, OR ALL THREE) | | | ARE NOT IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE | | | 61G15-23.001, FLORIDA STATUTE 471.3. | | | 3. A SUB GAS PERMIT IS REQUIRED BY A LICENSED | | | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS | | | TO THE FBC SEC. 105.1. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM | | | [email protected] | | | 561-701-6437 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2019-11-15 |
|
|
Cont ID |
|
| Sent By |
rfalcone |
Date |
2019-11-15 |
Time |
14:58 |
Rev Time |
0.00 |
| Received By |
rfalcone |
Date |
2019-11-15 |
Time |
14:58 |
Sent To |
HIST |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2019-10-17 |
|
|
Cont ID |
|
| Sent By |
rfalcone |
Date |
2019-10-17 |
Time |
15:25 |
Rev Time |
0.00 |
| Received By |
rfalcone |
Date |
2019-10-17 |
Time |
15:25 |
Sent To |
HIST |
|
| Notes |
|
|