| Plan Review Stops For Permit 19100815 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2019-11-20 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-11-20 |
Time |
08:03 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-11-20 |
Time |
08:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-10-28 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-10-28 |
Time |
13:59 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-10-28 |
Time |
11:07 |
Sent To |
|
|
| Notes |
| 2019-10-28 14:00:06 | BUILDING REVIEW COMMENTS: | | | | | | W.P.B. PERMIT: 19100813 | | | REVIEWED: OCTOBER 28, 2019 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER PX4191 | | | [email protected] | | | 561-805-6718 | | | | | | FLORIDA BUILDING CODE,6TH EDITION (2017) | | | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK | | | BELOW) | | | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ | | | BUILDING-PERMIT-FORMS | | | FBC[B] = FBC BUILDING | | | | | | 107.5.3 FBC[AMENDED]PLEASE SPECIFY WHAT TYPE, SIZE AND | | | EMBEDMENT OF ANCHORS THAT WILL BE USED FOR THE | | | CONNECTIONS AT TANK TO PAD, OR INDICATE WHERE THAT | | | INFORMATION IS PROVIDED. | | | | | | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F | | | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2019-11-01 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-11-01 |
Time |
12:28 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-11-01 |
Time |
12:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2019-11-20 |
|
|
Cont ID |
|
| Sent By |
sathomas |
Date |
2019-11-20 |
Time |
00:00 |
Rev Time |
0.00 |
| Received By |
sathomas |
Date |
2019-11-20 |
Time |
00:00 |
Sent To |
I |
|
| Notes |
| 2019-11-20 13:51:50 | PROVISO: | | | PROVIDE A COPY OF THE LOAD CALCULATIONS ONSITE DURING | | | INSPECTION. | | | SUBJECT TO FIELD INSPECTION. | | | | | | S.THOMAS | | | 561-804-4728 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2019-10-23 |
|
|
Cont ID |
|
| Sent By |
sathomas |
Date |
2019-10-23 |
Time |
00:00 |
Rev Time |
0.00 |
| Received By |
sathomas |
Date |
2019-10-23 |
Time |
00:00 |
Sent To |
E |
|
| Notes |
| 2019-10-23 11:33:05 | 1. UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY REVIEW | | | COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE (2015 | | | EDITION WITH FLORIDA AMENDMENTS.) | | | | | | 2. ALL WORK SHOULD ALSO REFERENCE COMPLIANCE TO NFPA | | | 110 ( STANDARD FOR EMERGENCY AND STANDBY POWER SYSTEMS | | | ) AND 37 (STANDARD FOR THE INSTALLATION AND USE OF | | | STATIONARY COMBUSTION ENGINES AND GAS TURBINES) | | | | | | 3. PER NFPA 110:7.9.1.1 ALL FUEL TANKS AND SYSTEMS | | | SHALL BE INSTALLED AND MAINTAINED IN ACCORDANCE WITH | | | NFPA 30, FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE; NFPA | | | 37, STANDARD FOR THE INSTALLATION AND USE OF STATIONARY | | | COMBUSTION ENGINES AND GAS TURBINES; NFPA 54, NATIONAL | | | FUEL GAS CODE; AND NFPA 58, LIQUEFIED PETROLEUM GAS | | | CODE. | | | | | | 4.PER NFPA 110:4 THE GENERATOR SHALL BE OF A CERTAIN | | | CLASS/TYPE/LEVEL. PLEASE PROVIDE CLARIFICATION AS TO | | | THE CLASS/TYPE/LEVEL. | | | | | | 5. PAGE E2.1.19 SHOWS FUEL CALCULATIONS, HOWEVER THERE | | | IS NO PLAN INDICATION THE MEANS AND QUANTITY OF FUEL | | | STORAGE. | | | | | | 6. ALL WORK SHALL BE SUBJECT TO FIELD INSPECTION. | | | | | | | | | S.THOMAS | | | 561-804-4728 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2019-11-20 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-11-20 |
Time |
13:15 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-11-20 |
Time |
13:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2019-11-05 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-11-05 |
Time |
15:26 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-11-05 |
Time |
15:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-11-21 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-11-21 |
Time |
08:43 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-11-21 |
Time |
08:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-11-06 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2019-11-06 |
Time |
07:37 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-10-17 |
Time |
13:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2019-11-20 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-11-20 |
Time |
08:04 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-11-20 |
Time |
08:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2019-10-28 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-10-28 |
Time |
14:02 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-10-28 |
Time |
14:02 |
Sent To |
|
|
| Notes |
| 2019-10-28 14:03:41 | OK-ALL SHEETS FOR INITIAL REVIEW | | | ANY ADDITIONAL SHEETS SUBMITTED WILLNEED TO BE SIGNED | | | DIGITALLY. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2019-11-25 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2019-11-25 |
Time |
13:46 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2019-11-25 |
Time |
13:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2019-11-20 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2019-11-20 |
Time |
10:09 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2019-11-20 |
Time |
10:09 |
Sent To |
|
|
| Notes |
| 2019-11-20 10:11:28 | 11/20/19- REPEAT COMMENT. A FIVE FOOT WIDE HEDGE IS | | | REQUIRED AROUND THE DUMPSTER AND GENERATOR ENCOLUSER. | | | | | | ANGELLA VANN | | | 561-822-1441 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2019-11-05 |
|
|
Cont ID |
|
| Sent By |
avann |
Date |
2019-11-05 |
Time |
16:19 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2019-11-05 |
Time |
16:19 |
Sent To |
|
|
| Notes |
| 2019-11-05 16:19:30 | 11/5/19- FAILED. 1. IS PARKING BEING REMOVED REQUIRED | | | PARKING? 2. A FIVE (5) FOOT LANDSCAPE BUFFER IS | | | REQUIRED AROUND THE DUMPSTER AND GENERATOR ENCLOSURES. | | | | | | ANGELLA VANN, AICP | | | 561-822-1441 | | | [email protected] |
|
|