Plan Review Details - Permit 19100815
Plan Review Stops For Permit 19100815
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-11-20 Cont ID  
Sent By dbattles Date 2019-11-20 Time 08:03 Rev Time 0.00
Received By dbattles Date 2019-11-20 Time 08:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-10-28 Cont ID  
Sent By dbattles Date 2019-10-28 Time 13:59 Rev Time 0.00
Received By dbattles Date 2019-10-28 Time 11:07 Sent To  
Notes
2019-10-28 14:00:06BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19100813
 REVIEWED: OCTOBER 28, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
  
 107.5.3 FBC[AMENDED]PLEASE SPECIFY WHAT TYPE, SIZE AND
 EMBEDMENT OF ANCHORS THAT WILL BE USED FOR THE
 CONNECTIONS AT TANK TO PAD, OR INDICATE WHERE THAT
 INFORMATION IS PROVIDED.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-11-01 Cont ID  
Sent By jpearson Date 2019-11-01 Time 12:28 Rev Time 0.00
Received By jpearson Date 2019-11-01 Time 12:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-11-20 Cont ID  
Sent By sathomas Date 2019-11-20 Time 00:00 Rev Time 0.00
Received By sathomas Date 2019-11-20 Time 00:00 Sent To I
Notes
2019-11-20 13:51:50PROVISO:
 PROVIDE A COPY OF THE LOAD CALCULATIONS ONSITE DURING
 INSPECTION.
 SUBJECT TO FIELD INSPECTION.
  
 S.THOMAS
 561-804-4728

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-10-23 Cont ID  
Sent By sathomas Date 2019-10-23 Time 00:00 Rev Time 0.00
Received By sathomas Date 2019-10-23 Time 00:00 Sent To E
Notes
2019-10-23 11:33:051. UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY REVIEW
 COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE (2015
 EDITION WITH FLORIDA AMENDMENTS.)
  
 2. ALL WORK SHOULD ALSO REFERENCE COMPLIANCE TO NFPA
 110 ( STANDARD FOR EMERGENCY AND STANDBY POWER SYSTEMS
 ) AND 37 (STANDARD FOR THE INSTALLATION AND USE OF
 STATIONARY COMBUSTION ENGINES AND GAS TURBINES)
  
 3. PER NFPA 110:7.9.1.1 ALL FUEL TANKS AND SYSTEMS
 SHALL BE INSTALLED AND MAINTAINED IN ACCORDANCE WITH
 NFPA 30, FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE; NFPA
 37, STANDARD FOR THE INSTALLATION AND USE OF STATIONARY
 COMBUSTION ENGINES AND GAS TURBINES; NFPA 54, NATIONAL
 FUEL GAS CODE; AND NFPA 58, LIQUEFIED PETROLEUM GAS
 CODE.
  
 4.PER NFPA 110:4 THE GENERATOR SHALL BE OF A CERTAIN
 CLASS/TYPE/LEVEL. PLEASE PROVIDE CLARIFICATION AS TO
 THE CLASS/TYPE/LEVEL.
  
 5. PAGE E2.1.19 SHOWS FUEL CALCULATIONS, HOWEVER THERE
 IS NO PLAN INDICATION THE MEANS AND QUANTITY OF FUEL
 STORAGE.
  
 6. ALL WORK SHALL BE SUBJECT TO FIELD INSPECTION.
  
  
 S.THOMAS
 561-804-4728

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2019-11-20 Cont ID  
Sent By gjohnson Date 2019-11-20 Time 13:15 Rev Time 0.00
Received By gjohnson Date 2019-11-20 Time 13:15 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2019-11-05 Cont ID  
Sent By gjohnson Date 2019-11-05 Time 15:26 Rev Time 0.00
Received By gjohnson Date 2019-11-05 Time 15:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-11-21 Cont ID  
Sent By dbattles Date 2019-11-21 Time 08:43 Rev Time 0.00
Received By dbattles Date 2019-11-21 Time 08:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-11-06 Cont ID  
Sent By lmarchan Date 2019-11-06 Time 07:37 Rev Time 0.00
Received By lmarchan Date 2019-10-17 Time 13:48 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-11-20 Cont ID  
Sent By dbattles Date 2019-11-20 Time 08:04 Rev Time 0.00
Received By dbattles Date 2019-11-20 Time 08:03 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-10-28 Cont ID  
Sent By dbattles Date 2019-10-28 Time 14:02 Rev Time 0.00
Received By dbattles Date 2019-10-28 Time 14:02 Sent To  
Notes
2019-10-28 14:03:41OK-ALL SHEETS FOR INITIAL REVIEW
 ANY ADDITIONAL SHEETS SUBMITTED WILLNEED TO BE SIGNED
 DIGITALLY.

Review Stop Z ZONING
Rev No 3 Status P Date 2019-11-25 Cont ID  
Sent By ajones Date 2019-11-25 Time 13:46 Rev Time 0.00
Received By ajones Date 2019-11-25 Time 13:46 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2019-11-20 Cont ID  
Sent By ajones Date 2019-11-20 Time 10:09 Rev Time 0.00
Received By ajones Date 2019-11-20 Time 10:09 Sent To  
Notes
2019-11-20 10:11:2811/20/19- REPEAT COMMENT. A FIVE FOOT WIDE HEDGE IS
 REQUIRED AROUND THE DUMPSTER AND GENERATOR ENCOLUSER.
  
 ANGELLA VANN
 561-822-1441
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2019-11-05 Cont ID  
Sent By avann Date 2019-11-05 Time 16:19 Rev Time 0.00
Received By ajones Date 2019-11-05 Time 16:19 Sent To  
Notes
2019-11-05 16:19:3011/5/19- FAILED. 1. IS PARKING BEING REMOVED REQUIRED
 PARKING? 2. A FIVE (5) FOOT LANDSCAPE BUFFER IS
 REQUIRED AROUND THE DUMPSTER AND GENERATOR ENCLOSURES.
  
 ANGELLA VANN, AICP
 561-822-1441
 [email protected]


Account Summary | Usage Policy | Privacy Policy