Plan Review Details - Permit 19100752
Plan Review Stops For Permit 19100752
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-11-25 Cont ID  
Sent By pvalenti Date 2019-11-25 Time 11:38 Rev Time 0.00
Received By pvalenti Date 2019-11-25 Time 11:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-10-22 Cont ID  
Sent By pvalenti Date 2019-10-22 Time 13:04 Rev Time 0.00
Received By pvalenti Date 2019-10-22 Time 13:04 Sent To  
Notes
2019-10-22 13:22:16***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 1. THERE IS NOT ENOUGH INFORMATION IN DESCRIPTION OF
 WORK APPLYING FOR.
 2. THE ADDRESS ON THE SUBMITTED PLANS IS DIFFERENT THAN
 ON THE APPLICATION.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-11-25 Cont ID  
Sent By pvalenti Date 2019-11-25 Time 11:39 Rev Time 0.00
Received By pvalenti Date 2019-11-13 Time 16:26 Sent To  
Notes
2019-11-14 16:26:18RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-10-22 Cont ID  
Sent By pvalenti Date 2019-10-22 Time 13:22 Rev Time 0.00
Received By pvalenti Date 2019-10-22 Time 13:22 Sent To  
Notes
2019-10-21 14:11:58REVISION ROUTED TO PVALENTI

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-11-25 Cont ID  
Sent By abelisle Date 2019-11-25 Time 07:41 Rev Time 0.00
Received By abelisle Date 2019-11-25 Time 06:13 Sent To B
Notes
2019-11-25 07:41:1711/25/19 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 A.BELISLE
 PLUMBING PLAN EXAMINER
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-10-24 Cont ID  
Sent By abelisle Date 2019-10-25 Time 06:35 Rev Time 0.00
Received By abelisle Date 2019-10-24 Time 06:34 Sent To I
Notes
2019-10-24 07:14:5810/24/2019 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1- PLEASE SUBMIT A SPERATE PLUMBING PERMIT APPLICATION
 FOR THE ROOF DRAINS, GREASE TRAP, ALL INTERIOR/
 EXTERIOR PLUMBING. PLUMBING SHALL BE DONE BY A LICENSED
 PLUMBING CONTRACTOR.
  
 2- SIGNATURE OF AN ARCHITECT-ENGINEER IS REQUIRED (OR
 SEAL, OR TITLE BLOCK, OR ALL THREE) ARE NOT IN
 ACCORDANCE WITH FLORIDA
 ADMINISTRATIVE CODE 61G15-23.001, FLORIDA STATUTE 471.
  
 3- PLEASE SHOW DIMENSIONS ON THE PLAN INDICATING THE
 BUILDINGS ACTUAL ROOF SIZE
  
 4- THE ADDRESS ON THE SUBMITTED PLANS IS DIFFERENT THAN
 THE ADDRESS LISTED ON THE PERMIT APPLICATION
  
 5- INDICATE ON THE PLAN ALL ROOF DRAINS TO BE
 INSTALLED, PLAN PAGE E 1.2 SHOWS SOME ADDITIONAL ROOF
 DRAINS NOT SHOWN ON C-1.
  
 6- PROVIDE 2-COPIES OF SPECIFICATIONS FOR THE TYPE OF
 ROOF DRAINS THAT ARE TO BE INSTALLED
  
 7- PROVIDE AN ISOMETRIC SHOWING THE ENTIRE ROOF
 DRAINAGE SYSTEM
  
 8- FLOOR DRAIN CONNECTED TO GREASE TRAP IN DUMPSTER
 AREA SHALL NOT RECIEVE ANY RAIN WATER, HOW WILL THE
 DUMPSTER PAD BE ELEVATED ABOVE THE SORROUNDING AREA
 OUTSIDE OF THE DUMPSTER ?
  
  
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLANS EXAMINER
 AVAILABLE BY APPOINTMENT ONLY
 [email protected]
 561-805-6695
  