| 2019-11-14 11:43:52 | RESIDENTIAL (R3) BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE. |
| | |
| | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.001 FOR: |
| | A) ENTRY DOOR AS SHOWN ON PLANS. |
| | |
| | B) SINGLE HUNG WINDOW AS SHOWN ON PLANS. |
| | |
| | C) HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE |
| | IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE. SEE CITY SAMPLE. |
| | |
| | 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS |
| | |
| | 3- NEED TO PROVIDE COMPLETE FRAMING DETAILS ANS |
| | SPECIFICATIONS FOR THE NEW EXTERIOR DOOR AND WINDOW. |
| | SPECIFY ALL FRAMING MEMBERS AND CONNECTORS. SEC. |
| | R301.2.1 FBC-RESIDENTIAL. |
| | |
| | 4- NEED TO PROVIDE ATTACHMENT OF THE NEW WOOD FRAMED |
| | WALL TO EXISTING STEEL COLUMN. SEC. R301.2.1 |
| | FBC-RESIDENTIAL. |
| | |
| | 5- NEED TO PROVIDE ATTACHMENT OF THE NEW WOOD FRAMED |
| | WALL TO EXISTING CONCRETE BLOCK WALL. COLUMN. SEC. |
| | R301.2.1 FBC-RESIDENTIAL. |
| | |
| | 6- NEED TO PROVIDE ATTACHMENT OF THE NEW WOOD FRAMED |
| | WALL TO EXISTING BEAM SEC. R301.2.1 FBC-RESIDENTIAL. |
| | |
| | 7- THIS IS A CHANGE OF USE FROM CARPORT TO ENCLOSED |
| | SPACE. TYPICALLY, CARPORTS ARE BUILT WITHOUT A FLOOR |
| | VAPOR BARRIER. ENGINEER OF RECORD TO PROVIDE |
| | SPECIFICATIONS FOR THE CONCRETE SLAB VAPOR BARRIER AS |
| | REQUIRED BY SEC. R506.2.3 FBC-RESIDENTIAL OR PROVIDE |
| | PROOF THAT THERE IS AN EXISTING VAPOR BARRIER. |
| | |
| | 8- NEED TO PROVIDE ATTACHMENT OF THE NEW WALL |
| | SHEATHING. SEC. R301.2.1 FBC-RESIDENTIAL. |
| | |
| | 9- NEED TO SPECIFY 2 LAYERS OF WATER RESISTIVE BARRIERS |
| | AS REQUIRED BY SEC. R703.7.3 FBC-RESIDENTIAL ON THE |
| | WOOD FRAMED WALL. |
| | |
| | 10- NEED TO SPECIFY MIN. 7/8" STUCCO THICKNESS FOR |
| | EXTERIOR APPLICATIONS AS REQUIRED BY SEC. R702.2.2 AND |
| | TABLE R702.1(1) FBC-RESIDENTIAL. |
| | |
| | 11- A) ENGINEER TO REVISE THE BUILDING EXPOSURE. |
| | ACCORDING TO SEC. R301.2.1.4 FBC-RESIDENTIAL THIS |
| | BUILDING IS LOCATED IN EXPOSURE C NOT B. REVISE AS |
| | REQUIRED OR PROVIDE CALCULATIONS AND SPECIFY THE |
| | BUILDING EXPOSURE FOR EACH WIND DIRECTION. |
| | |
| | B) REVISE THE WINDOWS AND DOORS DESIGN PRESSURES. |
| | COORDINATE WITH REVISED BUILDING EXPOSURE. AND, |
| | ENGINEER TO CLARIFY IF THE DESIGN PRESSURES ARE GIVEN |
| | IN ULTIMATED DESIGN PRESSURES OR NOMINAL DESIGN |
| | PRESSRUES. SEC. R301.2.1.3 FBC-RESIDENTIAL. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| | COMMENTS, |