Plan Review Details - Permit 19100676
Plan Review Stops For Permit 19100676
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2019-11-12 Cont ID  
Sent By thunt Date 2019-11-12 Time 07:13 Rev Time 0.00
Received By shill Date 2019-11-07 Time 07:59 Sent To  
Notes
2019-11-12 07:14:18REVIEWED REMOTELY BY TIM HUNT
 PROVISO: INSTALLATION MANUAL FOR THE L.P TANK FOR
 INSPECTION AND INSPECTOR TO VERIFY MIN MAKE UP AIR.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-10-21 Cont ID  
Sent By jesmith Date 2019-10-21 Time 08:57 Rev Time 0.00
Received By shill Date 2019-10-18 Time 16:47 Sent To  
Notes
2019-10-21 08:58:20GAS REVIEW REVISION #1**DENIED**
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-RES
 SEC. G2413.4.1, G2413.4.2. PROVIDE TOTAL DISTANCE OF
 COPPER TUBING. NO DISTANCE IS SHOWN ON PLAN OR ON
 SIZING CHART. FBC 107.3.5
  
  
 2. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE EXTERIOR BUILDING WALL AND ADJACENT
 PROPERTY LINES, THE DISTANCE OF THE TANK FROM ALL
 SOURCES OF IGNITION, OTHER CONTAINERS, BUILDINGS, AND
 THE LOCATION OF ANY BUILDING OPENINGS BELOW THE RELIEF
 VALVE OF THE TANK PER NFPA 58, TABLE 3-2.2.2.
  
 3. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL GAS
 SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.4
  
 4. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1, 2017 FBC-RES. SEC.
 G2421.1.
  
 5. YOUR TIE DOWN PLAN DOES NOT SHOW MEETING THE FBC FOR
 UP LIFT AS IT ONLY SHOWS THE CABLE WRAPPING AROUND THE
 TANK WITH NO EYE FOR THE CABLE TO GO THOUGH. FBC 107.2
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH (CGA SOLUTIONS
 [email protected]
 561-248-2703
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-11-12 Cont ID  
Sent By shill Date 2019-11-12 Time 07:15 Rev Time 0.00
Received By shill Date 2019-10-29 Time 15:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-10-21 Cont ID  
Sent By shill Date 2019-10-21 Time 09:03 Rev Time 0.00
Received By shill Date 2019-10-12 Time 09:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2019-11-12 Cont ID  
Sent By thunt Date 2019-11-12 Time 07:14 Rev Time 0.00
Received By shill Date 2019-11-07 Time 07:59 Sent To  
Notes
2019-11-12 07:14:46SEE GAS REVIEW
 REVIEWED REMOTELY BY TIM HUNT
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-10-21 Cont ID  
Sent By jesmith Date 2019-10-21 Time 08:58 Rev Time 0.00
Received By shill Date 2019-10-18 Time 16:48 Sent To  
Notes
2019-10-21 09:01:24SEE GAS REVIEW
 REVIEWED REMOTELY BY TIM HUNT
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-11-12 Cont ID  
Sent By shill Date 2019-11-12 Time 07:15 Rev Time 0.00
Received By shill Date 2019-11-12 Time 07:15 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2019-10-21 Cont ID  
Sent By shill Date 2019-10-21 Time 09:03 Rev Time 0.00
Received By shill Date 2019-10-21 Time 09:03 Sent To  
Notes
***NONE***