Plan Review Details - Permit 19100651
| Plan Review Stops For Permit 19100651 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2020-03-19 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-03-19 |
Time |
09:55 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-03-03 |
Time |
06:46 |
Sent To |
|
|
| Notes |
| 2020-03-19 09:56:44 | PLAN REVIEW - BUILDING | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 2ND REVIEW | | | | | | RESULTS: DENIED | | | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | COMMENTS FROM 1ST REVIEW HAVE NOT BEEN ADDRESSED. | | | | | | 1. NOTICE ONLY - VALUE HAS BEE ADJUSTED FROM $200,000 | | | TO $532,250 BASED ON THE ICC BUILDING EVALUATION | | | TABLES. | | | | | | 2. PROVIDE PRODUCT APPROVALS FOR WINDOWS AND EXTERIOR | | | DOORS. YOU MAY ELOECT TO DEFER REVIEW OF THESE DOC'S. | | | SEE BELOW. | | | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS. | | | | | | 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS | | | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE | | | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE | | | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO | | | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. | | | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR | | | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED | | | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST | | | THE DEFERRED SUBMITTALS ON | | | THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING | | | OFFICIAL. | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | | OFFICIAL. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED. | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-11-18 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-11-18 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-11-08 |
Time |
08:09 |
Sent To |
|
|
| Notes |
| 2019-11-18 15:37:13 | PLAN REVIEW - BUILDING | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. NOTICE ONLY - VALUE HAS BEE ADJUSTED FROM $200,000 | | | TO $532,250 BASED ON THE ICC BUILDING EVALUATION | | | TABLES. | | | | | | 2. PROVIDE PRODUCT APPROVALS FOR WINDOWS AND EXTERIOR | | | DOORS. YOU MAY ELOECT TO DEFER REVIEW OF THESE DOC'S. | | | SEE BELOW. | | | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS. | | | | | | 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS | | | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE | | | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE | | | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO | | | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. | | | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR | | | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED | | | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST | | | THE DEFERRED SUBMITTALS ON | | | THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING | | | OFFICIAL. | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | | OFFICIAL. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED. | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2020-03-16 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2020-03-16 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2020-03-16 |
Time |
11:06 |
Sent To |
|
|
| Notes |
| 2020-03-16 09:25:31 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. SHEET 024_EL, THE 24 26 16 PANEL SCHEDULE LOCATED | | | NEXT TO THE LOAD CALCULATION STATES THAT THERE WILL BE | | | 100 AMP BREAKERS FEEDING THE THREE SUB-PANELS. THE | | | PANEL SCHEDULE FOR THIS PANEL LOCATED AT THE TOP OF THE | | | PAGE STATES THAT THEY ARE FED WITH 20 AMP CIRCUITS. | | | CORRECT DISCREPANCY. WPB FBC 107.2.1 | | | 2. SHEET 024_EL, THE 24 26 16 PANEL SCHEDULE LOCATED | | | NEXT TO THE LOAD CALCULATION STATES THAT THE WIRE SIZE | | | FEEDING THE THREE SUB-PANELS WILL BE # 4. THIS WIRE | | | SIZE IS NOT RATED FOR 100 AMPS. PROVIDE CORRECTION. | | | WIRE SIZES FROM NEC 310.15(B)(7), OR FBC RE E3603.1, | | | CAN ONLY BE USED WHEN THE SERVICE CONDUCTOR SUPPLIES | | | 100% OF THE LOAD. SINCE THIS IS NOT THE CASE, PROVIDE | | | CORRECTED WIRE SIZE FROM METER CAN TO PANELS. NEC | | | 310.15(B)(7) AND (B)(16); FBC RE E3603.1, E3705.1 | | | 3. SHEET 024_EL, THE 24 26 16 PANEL SCHEDULE LOCATED | | | NEXT TO THE LOAD CALCULATION SHOWS A GROUNDING | | | ELECTRODE CONDUCTOR TO EACH SUB-PANEL. THE GROUNDING | | | ELECTRODE CONDUCTOR IS ONLY CONNECTED AT THE MAIN. AN | | | EQUIPMENT GROUNDING CONDUCTOR, SIZED TO CODE, IS | | | REQUIRED TO BE INSTALLED WITH ALL FEEDERS TO | | | SUB-PANELS. PROVIDE CORRECTION. NEC 250.122; FBC RE | | | E3704.6, 3607.3.1 | | | 4. PLAN IS NOT CLEAR AS TO THE OVER-CURRENT PROTECTION | | | OF FEEDERS TO THE SUB-PANELS. THESE CIRCUITS NEED TO BE | | | PROTECTED AT THE SOURCE, THE MAIN DISTRIBUTION PANEL. | | | IF THE INTENT IS TO TAP OFF THE MAIN 300 WITH THESE | | | FEEDERS, THESE TAPS WOULD NEED T COMPLY WITH THE TAP | | | RULES PER NEC 240.21. THE PANEL SCHEDULES STATES THEY | | | ARE MAIN LUG ONLY, BUT ALSO STATE THERE IS A 100 AMP | | | MAIN. WHICH IS IT? PROVIDE CLARIFICATION AND/OR | | | CORRECTIONS. WPB FBC 107.2.1; NEC 240.4, 240.21 | | | 5. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR | | | SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY | | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | | SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC | | | RE E3606.3 | | | 6. PROVIDE LOAD CALCULATION FOR EACH SUB-PANEL (P.1, | | | P.2, P.3). BASED ON THE CONNECTED LOAD SHOWN, EACH OF | | | THESE PANELS IS OVERLOADED. PROVIDE CORRECTION. NEC | | | 215.2, 220, 408.30; FBC RE E3602.2 | | | 7. CIRCUIT #24 FROM P.1 IS SHOWN FEEDING LIGHTS AND | | | RECEPTACLES IN MORE THAN ONE BATHROOM. THIS IS NOT | | | PERMITTED PER CODE. AN INDIVIDUAL 20 AMP CIRCUIT IS | | | ALLOWED TO FEED LIGNTS AND RECEPTACLES IN ONE BATHROOM | | | IF IT DOES NOT EXTEND TO OTHER BATHROOMS. OR, A | | | SEPARATE CIRCUIT CAN BE USED FOR LIGHTING, AND THE | | | RECEPTACLE CIRCUIT CAN FEED OTHER BATHROOMS. AS SHOWN | | | ON PLAN, THE CIRCUITRY IS NOT CODE COMPLIANT. PROVIDE | | | CORRECTION. NEC 210.11(C)(3); FBC RE E3703.4 | | | 8. CIRCUIT #17 FROM P.2 IS SHOWN FEEDING LIGHTS AND | | | RECEPTACLES IN MORE THAN ONE BATHROOM. THIS IS NOT | | | PERMITTED PER CODE. AN INDIVIDUAL 20 AMP CIRCUIT IS | | | ALLOWED TO FEED LIGNTS AND RECEPTACLES IN ONE BATHROOM | | | IF IT DOES NOT EXTEND TO OTHER BATHROOMS. OR, A | | | SEPARATE CIRCUIT CAN BE USED FOR LIGHTING, AND THE | | | RECEPTACLE CIRCUIT CAN FEED OTHER BATHROOMS. AS SHOWN | | | ON PLAN, THE CIRCUITRY IS NOT CODE COMPLIANT. PROVIDE | | | CORRECTION. NEC 210.11(C)(3); FBC RE E3703.4 | | | 9. CIRCUIT #17 FROM P.3 IS SHOWN FEEDING LIGHTS AND | | | RECEPTACLES IN MORE THAN ONE BATHROOM. THIS IS NOT | | | PERMITTED PER CODE. AN INDIVIDUAL 20 AMP CIRCUIT IS | | | ALLOWED TO FEED LIGNTS AND RECEPTACLES IN ONE BATHROOM | | | IF IT DOES NOT EXTEND TO OTHER BATHROOMS. OR, A | | | SEPARATE CIRCUIT CAN BE USED FOR LIGHTING, AND THE | | | RECEPTACLE CIRCUIT CAN FEED OTHER BATHROOMS. AS SHOWN | | | ON PLAN, THE CIRCUITRY IS NOT CODE COMPLIANT. PROVIDE | | | CORRECTION. NEC 210.11(C)(3); FBC RE E3703.4 | | | 10. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR | | | SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE | | | EQUIPMENT PER CODE. SHOW LOCATION OF UNITS ON PLAN. WPB | | | FBC 107.2.1; NEC 210.63; FBC RE E3901.12 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH | | | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. | | | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL | | | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. | | | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD | | | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-11-09 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2019-11-09 |
Time |
21:53 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2019-11-08 |
Time |
06:14 |
Sent To |
|
|
| Notes |
| 2019-11-09 21:53:35 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PLAN IS BLURRED AND UNREADABLE. | | | | | | THE SUBMITTED FLOOR PLAN IS UNACCEPTABLE. PLEASE REVIEW | | | THE FOLLOWING SECTIONS FROM THE WEST PALM BEACH | | | AMENDMENTS TO THE FBC: | | | | | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN | | | UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS | | | SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING | | | OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT | | | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF | | | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL | | | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT | | | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED | | | BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND | | | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM | | | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, | | | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE | | | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, | | | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE | | | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS | | | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | | INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO | | | SECTION 107.3.5). | | | | | | 107.2.1.3 QUALITY OF BUILDING PLANS. BUILDING PLANS | | | SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON | | | SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. | | | THE BUILDING OFFICIAL MAY ESTABLISH THROUGH | | | DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND | | | SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS | | | RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH | | | THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR | | | OTHER ITEMS RELATED TO RECORDS MANAGEMENT. ELECTRONIC | | | MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE REQUIREMENTS | | | OF FLORIDA STATUTES. | | | | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-657-1653 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-03-21 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-03-21 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-03-02 |
Time |
11:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-12-09 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2019-12-09 |
Time |
17:02 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2019-11-04 |
Time |
08:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2020-10-16 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2020-10-16 |
Time |
13:09 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-03-03 |
Time |
06:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2019-11-20 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-11-20 |
Time |
08:57 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-11-08 |
Time |
08:09 |
Sent To |
|
|
| Notes |
| 2019-11-20 09:01:06 | ****ADVISORY**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | THE MUNICIPAL QUESTIONNAIRE WAS RECEIVED (WAS UPLOADED | | | TO SUPPORTING DOCS NAMED "6081 SD PBC IMPACT FEE"). | | | AFTER THIS PROJECT HAS PASSED BOTH BUILDING AND ZONING, | | | PLEASE ADVISE VIA EMAIL AND REFER TO THIS PLAN REVIEW: | | | | | | [email protected] | | | | | | PALM BEACH COUNTY WILL THEN BE INVITED TO REVIEW YOUR | | | APPLICATION FOR IMPACT FEES. | | | | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2020-03-11 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-03-11 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-03-03 |
Time |
06:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2019-11-18 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-11-18 |
Time |
14:10 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-11-15 |
Time |
07:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2020-03-19 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-03-19 |
Time |
08:54 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-03-03 |
Time |
06:46 |
Sent To |
|
|
| Notes |
| 2020-03-19 09:15:58 | PLAN REVIEW - PLUMBING | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. DRAIN SIZE NOT SHOWN FOR 3RD FLOOR TO 2ND FLOOR | | | BATHROOM GROUP. | | | P3005.4DRAIN PIPE SIZING. | | | DRAIN PIPES SHALL BE SIZED ACCORDING TO DRAINAGE | | | FIXTURE UNIT (D.F.U.) LOADS. THE SIZE OF THE DRAINAGE | | | PIPING SHALL NOT BE REDUCED IN SIZE IN THE DIRECTION OF | | | FLOW. THE FOLLOWING GENERAL PROCEDURE IS PERMITTED TO | | | BE USED: | | | | | | 2. VENT SIZE FROM 2ND TO 3RD FLOOR NOT SHOWN ON ISO. | | | P3102.3SIZE. | | | THE REQUIRED VENT SHALL BE SIZED IN ACCORDANCE WITH | | | SECTION P3113.1 BASED ON THE REQUIRED SIZE OF THE | | | BUILDING DRAIN. | | | | | | 3. 3RD FLOOR VTR NOT SIZED ON ISO. | | | P3102.3SIZE. | | | THE REQUIRED VENT SHALL BE SIZED IN ACCORDANCE WITH | | | SECTION P3113.1 BASED ON THE REQUIRED SIZE OF THE | | | BUILDING DRAIN. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2019-11-18 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-11-18 |
Time |
15:47 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-11-15 |
Time |
07:37 |
Sent To |
|
|
| Notes |
| 2019-11-18 15:49:54 | PLAN REVIEW - PLUMBING | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PLUMBING RISER DIAGRAHMS HAVE EXCESSIVE DESIGN | | | ISSUES. | | | 2. PROVIDE A CODE COMPLIANT RISER DIAGRAHM DESIGNED BY | | | YOUR PLUMBING CONTRACTOR. | | | | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2020-03-19 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-03-19 |
Time |
09:51 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-03-03 |
Time |
06:46 |
Sent To |
|
|
| Notes |
| 2020-03-19 09:53:56 | PLAN REVIEW - ROOFING | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 2ND REVIEW | | | | | | RESULTS: DENIED | | | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | COMMENTS FROM 1ST REVIEW HAVE NOT BEEN ADDRESSED. | | | | | | 1. ROOFING PERMIT REQUIRED. | | | | | | 2. PROVIDE PRODUCT APPROVALS FOR PROPOSED ROOFING | | | SYSTEM COMPONENTS. DOCUMENTS MAY BE DEFERRED. SEE | | | BELOW. | | | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE ROOFING, WINDOW AND DOOR | | | SUBMITTALS. | | | | | | 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS | | | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE | | | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE | | | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO | | | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. | | | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR | | | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED | | | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST | | | THE DEFERRED SUBMITTALS ON | | | THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING | | | OFFICIAL. | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | | OFFICIAL. | | | | | | | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2019-11-18 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-11-18 |
Time |
15:44 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-11-08 |
Time |
08:09 |
Sent To |
|
|
| Notes |
| 2019-11-18 15:46:49 | PLAN REVIEW - ROOFING | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. ROOFING PERMIT REQUIRED. | | | | | | 2. PROVIDE PRODUCT APPROVALS FOR PROPOSED ROOFING | | | SYSTEM COMPONENTS. DOCUMENTS MAY BE DEFERRED. SEE | | | BELOW. | | | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE ROOFING, WINDOW AND DOOR | | | SUBMITTALS. | | | | | | 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS | | | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE | | | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE | | | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO | | | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. | | | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR | | | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED | | | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST | | | THE DEFERRED SUBMITTALS ON | | | THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING | | | OFFICIAL. | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | | OFFICIAL. | | | | | | | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2020-03-19 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-03-19 |
Time |
09:16 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-03-03 |
Time |
06:46 |
Sent To |
|
|
| Notes |
| 2020-03-19 09:19:08 | PLAN REVIEW - DIGITAL SIGNATURE | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. MULTIPLE PLAN PAGES TO BE RE-SUBMITTED. SIGNATURE | | | REVIEW WILL BE REQUIRED. | | | | | | 2. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL | | | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE | | | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT. | | | | | | | | | | | 2020-03-16 09:09:56 | ELECTRICAL SHEETS OK. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2019-11-18 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-11-18 |
Time |
15:37 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-11-08 |
Time |
08:09 |
Sent To |
|
|
| Notes |
| 2019-11-18 15:43:55 | PLAN REVIEW - SIGNATURE AND SEAL | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PLAN PAGES 004-ST AND 006-ST MISSING DESIGNER | | | SIGNTURE AND SEAL. | | | | | | 1. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH | | | FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE | | | NEXT REVIEW CYCLE REQUIRE REVIEW. | | | | | | 2. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL | | | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE | | | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT. | | | | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2020-03-19 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2020-03-19 |
Time |
15:49 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2020-03-19 |
Time |
15:49 |
Sent To |
|
|
| Notes |
| 2020-03-19 15:50:14 | REPEAT COMMENTS3/19/20- FAILED | | | 1. STAFF WAS NOT SURE HOW THE LAYOUT OF THE FLOORS | | | WORKS. EACH ROOM MUST BE ASSESSABLE TO THE ENTIRE | | | FLOOR. | | | 2. HOW WIDE IS THE DRIVEWAY AT THE PROPERTY LINE? | | | 3. SEPARATE PERMITS ARE REQUIRED FOR LANDSCAPING, | | | DRIVEWAY AND TRASH ENCLOSURE. | | | | | | ANGELLA VANN | | | 561-822-1441 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2019-12-09 |
|
|
Cont ID |
|
| Sent By |
avann |
Date |
2019-12-09 |
Time |
16:46 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2019-12-09 |
Time |
16:46 |
Sent To |
|
|
| Notes |
| 2019-12-09 16:59:53 | 12/9/19- FAILED | | | 1. STAFF WAS NOT SURE HOW THE LAYOUT OF THE FLOORS | | | WORKS. EACH ROOM MUST BE ASSESSABLE TO THE ENTIRE | | | FLOOR. | | | 2. HOW WIDE IS THE DRIVEWAY AT THE PROPERTY LINE? | | | 3. SEPARATE PERMITS ARE REQUIRED FOR LANDSCAPING, | | | DRIVEWAY AND TRASH ENCLOSURE. | | | | | | ANGELLA VANN | | | 561-822-1441 | | | [email protected] | | | |
|
|
|