Plan Review Details - Permit 19100626
Plan Review Stops For Permit 19100626
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-10-29 Cont ID  
Sent By jpearson Date 2019-10-29 Time 09:07 Rev Time 0.00
Received By jpearson Date 2019-10-29 Time 09:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-10-15 Cont ID  
Sent By jpearson Date 2019-10-15 Time 16:02 Rev Time 0.00
Received By jpearson Date 2019-10-15 Time 16:02 Sent To M
Notes
2019-10-15 16:02:32CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM IS NOT CODE COMPLIANT. THE SERVICE
 CONDUCTORS MUST HAVE OVERCURRENT PROTECTION AND THE
 PANEL IS SHOWN AS MAIN LUG ONLY. SERVICE CONDUCTORS ARE
 NOT PERMITTED TO EXTEND FURTHER THAN 8 FEET INTO A
 STRUCTURE WITHOUT OVERCURRENT PROTECTION. IF THIS
 OVERCURRENT PROTECTION IS LOCATED ON THE EXTERIOR OF
 THE DWELLING, THAN THE CONDUIT TO THE INTERIOR PANEL
 MUST INCLUDE AN EQUIPMENT GROUNDING CONDUCTOR. IF THE
 CONDUCTORS ARE RUN UNDERGROUND FROM THE METER TO THE
 INTERIOR PANEL, AND THAT PANEL HAS A MAIN BREAKER, THE
 CONDUCTORS MUST NOT EXCEED 8 FEET IN LENGTH BEFORE
 TERMINATION TO THE MAIN BREAKER. PROVIDE CORRECTION.
 NEC 230.70, 250.122; FBC RE E3601.6, E3704.6, 3607.3.1
 2. PROVIDE ACCURATE RISER DIAGRAM. THE REVISED RISER
 DOES NOT SHOW THE POOL PANEL, BUT THE PANEL SCHEDULE
 FOR THE POOL PANEL IS STILL ON PLAN. WHICH IS ACCURATE?
 IS THERE A POOL PANEL OR NOT? PROVIDE CLARIFICATION AND
 CORRECTIONS AS NEEDED. NEC 215.5; WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-10-18 Cont ID  
Sent By cmontell Date 2019-10-18 Time 14:08 Rev Time 0.00
Received By cmontell Date 2019-10-18 Time 14:07 Sent To  
Notes
2019-10-15 14:22:04REVISION ROUTED TO JPEARSON

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-10-18 Cont ID  
Sent By cmontell Date 2019-10-18 Time 14:07 Rev Time 0.00
Received By cmontell Date 2019-10-18 Time 14:06 Sent To I
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved