| 2019-10-15 15:22:34 | PROVISO: |
| | 1. PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| | PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE |
| | OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS. |
| | 2. TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM |
| | BUILDING STRUCTURES. |
| | 3. TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE, |
| | OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS |
| | ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET. |
| | 4. POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS |
| | LOCATIONS. |
| | 5. PROVIDE NONCOMBUSTIBLE FLAME CERTIFICATE FOR THE |
| | CANOPY MATERIAL. |
| | 6. GENERATORS AND OTHER INTERNAL COMBUSTION POWER |
| | SOURCES SHALL BE SEPARATED FROM TENTS BY A MINIMUM OF 5 |
| | FEET AND SHALL BE PROTECTED FROM CONTACT BY FENCING OR |
| | ENCLOSURE. |
| | 7. OPEN-AIR MERCANTILE OPERATIONS: PER NFPA 101 SECTION |
| | 36.4.3.3, MERCANTILE OPERATIONS THAT ARE CONDUCTED IN |
| | ROOFED-OVER AREAS SHALL BE TREATED AS MERCANTILE |
| | BUILDINGS, PROVIDED THAT CANOPIES OVER INDIVIDUAL SMALL |
| | STANDS TO PROTECT MERCHANDISE FROM THE WEATHER ARE NOT |
| | CONSTRUED AS CONSTITUTING BUILDINGS FOR THE PURPOSE OF |
| | THIS CODE. THE INTENT OF 36/37.4.3.3 IS TO EXEMPT SMALL |
| | MERCHANDISE STANDS WITH CANOPIES FROM CLASSIFICATION AS |
| | MERCANTILE BUILDINGS. ALL OTHER ROOFED-OVER AREAS |
| | SHOULD BE TREATED AS BUILDINGS CLASSIFIED BY AREA AND |
| | HEIGHT AS CLASS A, CLASS B, OR CLASS C MERCANTILE |
| | OCCUPANCIES AND ARE SUBJECT TO THE APPROPRIATE |
| | PROVISIONS OF CHAPTERS 36 AND 37 OF THE LIFE SAFETY |
| | CODE. |
| | |