Plan Review Details - Permit 19100610
Plan Review Stops For Permit 19100610
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2019-12-04 Cont ID  
Sent By jpearson Date 2019-12-04 Time 13:04 Rev Time 0.00
Received By jpearson Date 2019-12-04 Time 13:04 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-11-27 Cont ID  
Sent By jpearson Date 2019-11-27 Time 14:26 Rev Time 0.00
Received By jpearson Date 2019-11-27 Time 14:26 Sent To I
Notes
2019-11-27 14:26:09CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PROVIDE TWO
 COPIES OF PLAN FOR REVIEW. WPB FBC 107.1 (NOT
 CORRECTED. ONLY ONE SET OF PLANS AND SOME OLD SHEETS IN
 THE SET.)
 2. CORRECTED.
 3. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-11-13 Cont ID  
Sent By jpearson Date 2019-11-13 Time 09:09 Rev Time 0.00
Received By jpearson Date 2019-11-13 Time 09:09 Sent To I
Notes
2019-11-13 08:06:23CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PROVIDE TWO
 COPIES OF PLAN FOR REVIEW. WPB FBC 107.1
 2. AFTER THE PLAN HAS BEEN SIGNED AND SEALED BY THE
 ENGINEER OF RECORD(EOR), WRITTEN NOTES ARE NOT
 PERMITTED ON PLAN. PROVIDE TWO FULL SETS WITH ALL
 CHANGES FROM EOR. WPB FBC 107.1
 3. PLAN SHOWS #4 WIRE BEING FED FROM A 100 AMP BREAKER.
 THIS WIRE IS NOT RATED FOR 100 AMPS. PROVIDE
 CORRECTION. NEC 310.15(B)(16), 240.4(B)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-11-13 Cont ID  
Sent By jpearson Date 2019-10-14 Time 11:09 Rev Time 0.00
Received By jpearson Date 2019-10-14 Time 11:09 Sent To  
Notes
2019-11-13 07:47:56CHANGE STATUS TO FAIL, SEE RESULTS FOR SECOND REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2019-12-04 Time   Rev Time 0.00
Received By lmarchan Date 2019-12-02 Time 15:13 Sent To  
Notes
2019-12-03 15:14:01RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-11-27 Time   Rev Time 0.00
Received By lmarchan Date 2019-11-25 Time 13:30 Sent To  
Notes
2019-11-26 13:31:07RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-11-13 Time   Rev Time 0.00
Received By lmarchan Date 2019-11-08 Time 16:01 Sent To  
Notes
2019-11-12 16:01:45RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-10-14 Time   Rev Time 0.00
Received By lmarchan Date 2019-10-10 Time 16:34 Sent To  
Notes
2019-10-10 16:34:41REVISION ROUTED TO JPEARSON


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved