| 2019-11-05 13:29:52 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 19100552 |
| | REVIEWED: NOVEMBER 5, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK |
| | BELOW) |
| | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ |
| | BUILDING-PERMIT-FORMS |
| | FBC[B] = FBC BUILDING |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | |
| | 1) 107.5.3 FBC[AMENDED]PLEASE ADD EXPOSURE CATEGORY TO |
| | SHEET S-101. |
| | |
| | 2) 107.5.3 FBC[AMENDED]SHEET A-3.01 AND A-3.02 STATE |
| | THAT THE ROOF DECK WILL BE 2X6 WOOD STRUCTURAL T&G |
| | DECKING. STRUCTURAL SHEETS CALL FOR PLYWOOD DECKING. |
| | PLEASE CO-ORDINATE ROOF DECKING TO MATCH SINCE THERE IS |
| | A DISCREPENCY WITH WEIGHT. |
| | |
| | 3) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR |
| | WINDOWS AT CUPOLA AND FIBERGLASS DOOR, OR INDICATE THAT |
| | THEY WILL BE A DEFERRED SUBMITTAL. |
| | |
| | 4) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR |
| | METAL ROOFING AND FLAT ROOF, OR INDICATE THAT ROOFING |
| | WILL BE A DEFERRED SUBMITTAL. |
| | |
| | 5) 1507.4.2 FBC[B] DECK SLOPE. MINIMUM SLOPES FOR METAL |
| | ROOF PANELS SHALL COMPLY WITH THE FOLLOWING: |
| | 1. THE MINIMUM SLOPE FOR LAPPED, NONSOLDERED SEAM METAL |
| | ROOF PANELS WITHOUT APPLIED LAP SEALANT SHALL BE THREE |
| | UNITS VERTICAL IN 12 UNITS HORIZONTAL (25-PERCENT |
| | SLOPE). |
| | 2. THE MINIMUM SLOPE FOR LAPPED, NONSOLDERED SEAM METAL |
| | ROOF PANELS WITH APPLIED LAP SEALANT SHALL BE ONE-HALF |
| | UNIT VERTICAL IN 12 UNITS HORIZONTAL (4-PERCENT SLOPE). |
| | LAP SEALANTS SHALL BE APPLIED IN ACCORDANCE WITH THE |
| | APPROVED MANUFACTURER?S INSTALLATION INSTRUCTIONS. |
| | 3. THE MINIMUM SLOPE FOR STANDING-SEAM METAL ROOF PANEL |
| | SYSTEMS SHALL BE ONE-QUARTER UNIT VERTICAL IN 12 UNITS |
| | HORIZONTAL (2-PERCENT SLOPE). |
| | -ADD NOTE 1-3 THAT APPLIES TO THE SLOPE BEING PROPOSED |
| | ON METAL ROOFING. |
| | -PROVIDE ENGINEERING FOR FLAT ROOFING ENHANCED NAILING |
| | IF APPLICABLE. |
| | |
| | NOTES: |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |