Plan Review Details - Permit 19100524
Plan Review Stops For Permit 19100524
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-07-17 Cont ID  
Sent By pvalenti Date 2023-07-17 Time 07:18 Rev Time 0.00
Received By pvalenti Date 2023-07-17 Time 07:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-01-31 Cont ID  
Sent By pvalenti Date 2023-01-31 Time 09:05 Rev Time 0.00
Received By pvalenti Date 2023-01-31 Time 09:05 Sent To  
Notes
2023-01-31 09:17:42PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1, WPB AMENDMENTS TO FBC B FIGURE
 1609.3(1): PLAN SHEETS A.0 AND A.1, THE WIND SPEED
 INDICATED ON THESE SHEETS NEEDS TO BE ADJUSTED TO 170
 MPH. THE ENGINEER WILL NEED TO PROVIDE 3RD PARTY
 VERIFIED DIGITAL SIGNATURES TO THE PLAN SHEETS.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-07-17 Cont ID  
Sent By pvalenti Date 2023-07-17 Time 07:19 Rev Time 0.00
Received By pvalenti Date 2023-06-30 Time 09:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-01-31 Cont ID  
Sent By medwards Date 2023-01-31 Time 09:23 Rev Time 0.00
Received By medwards Date 2023-01-30 Time 13:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-01-30 Cont ID  
Sent By lmarchan Date 2023-01-30 Time 07:47 Rev Time 0.00
Received By lmarchan Date 2023-01-06 Time 13:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2023-07-14 Cont ID  
Sent By cmontell Date 2023-07-14 Time 13:24 Rev Time 0.00
Received By cmontell Date 2023-07-14 Time 13:26 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2023-01-31 Cont ID  
Sent By medwards Date 2023-01-31 Time 09:23 Rev Time 0.00
Received By medwards Date 2023-01-31 Time 09:23 Sent To  
Notes
2023-01-31 09:23:45SEE BUILDING REVIEWER COMMENT BELOW.
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1, WPB AMENDMENTS TO FBC B FIGURE
 1609.3(1): PLAN SHEETS A.0 AND A.1, THE WIND SPEED
 INDICATED ON THESE SHEETS NEEDS TO BE ADJUSTED TO 170
 MPH. THE ENGINEER WILL NEED TO PROVIDE 3RD PARTY
 VERIFIED DIGITAL SIGNATURES TO THE PLAN SHEETS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-01-16 Cont ID  
Sent By medwards Date 2023-01-16 Time 10:10 Rev Time 0.00
Received By medwards Date 2023-01-16 Time 10:10 Sent To  
Notes
2023-01-16 10:11:031ST REVIEW FMC
 PERMIT: 19100524
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE NOA SUBMITTED IN THE DOCUMENTS FOR THE WALK-IN
 COOLER/FREEZER HAS AN EXPIRATION DATE OF 07/13/2022 AND
 IS NO LONGER VALID. PLEASE PROVIDE A CURRENT NOA FOR
 THIS PROJECT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-07-17 Cont ID  
Sent By pvalenti Date 2023-07-17 Time 07:19 Rev Time 0.00
Received By pvalenti Date 2023-07-17 Time 07:19 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-01-16 Cont ID  
Sent By medwards Date 2023-01-16 Time 10:11 Rev Time 0.00
Received By medwards Date 2023-01-16 Time 10:11 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2023-01-27 Cont ID  
Sent By CKimmerl Date 2023-01-27 Time 14:58 Rev Time 0.00
Received By ckimmerl Date 2023-01-27 Time 14:58 Sent To  
Notes
***NONE***