Plan Review Details - Permit 19100456
Plan Review Stops For Permit 19100456
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-02-07 Cont ID  
Sent By jgomez Date 2020-02-07 Time 09:48 Rev Time 0.00
Received By jgomez Date 2020-02-07 Time 09:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-01-09 Cont ID  
Sent By jgomez Date 2020-01-09 Time 10:06 Rev Time 0.00
Received By jgomez Date 2020-01-09 Time 09:56 Sent To  
Notes
2020-01-08 18:26:38RESIDENTIAL (R3), RE-ROOF THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1-OK
  
 ORIGINAL COMMENT:
 2- FLAT ROOF NOA 18-0919.07 SUBMITTED: SELECTED
 ASSEMBLY ON PAGE 21 OF 27 DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES. PROVIDE SIGNED AND SEALED
 RAS 117 CALCULATIONS FOR NAIL ENHANCING AT PERIMETER
 AND CORNER AREAS AS REQUIRED BY GENERAL LIMITATION #7
 ON LAST PAGE OF NOA. NEED THE CALCULATIONS TO MEET THE
 DESIGN PRESSURES REQUIRED BY SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. RAS 117 CALCULATIONS SUBMITTED ARE DONE
 FOR NOA 18-1127.18. THIS DOESN'T MATCH NOA 18-0919.07
 SUBMITTED BY THE ROOFING CONTRACTOR. THESE ARE TWO
 DIFFERENT MANUFACTURERS. REVISE AS REQUIRED TO MATCH
 AND PROVIDE TWO COPIES. ONLY ONE COPY WAS PROVIDED THIS
 TIME.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-11-22 Cont ID  
Sent By jgomez Date 2019-11-22 Time 14:27 Rev Time 0.00
Received By jgomez Date 2019-11-22 Time 13:08 Sent To  
Notes
2019-11-22 13:14:37RESIDENTIAL (R3), RE-ROOF SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 1- ACCORDING TO PALM BEACH COUNTY PROPERTY APPRAISER,
 THE VALUE OF THE STRUCTURE IS $350.151. THEREFORE, NEED
 TO COMPLY WITH THE ROOF TO WALL CONNECTIONS AS REQUIRED
 BY SEC. 706.8 FBC-EXISTING BUILDING. SHOW COMPLIANCE.
 NOTE: A SEPARATE SUB-PERMIT IS REQUIRED FOR ROOF TO
 WALL CONNECTIONS. THIS WORK CAN NOT BE DONE BY THE
 ROOFING CONTRACTOR UNLESS ROOFING CONTRACTOR POSSESSES
 THE PROPER LICENSE TO PERFORM THIS WORK.
  
 RESPONSE:
 A) THE ROOF TO WALL PROPOSAL SUBMITTED IS FOR $3,850
 AND IS FOR ENTIRE ROOF. ALSO, THE PROPOSAL WAS DONE BY
 BENTLEY ROOFING (ROOFING CONTRACTOR). ROOFING
 CONTRACTOR CAN NOT PERFORM THE WORK UNLESS HOLDING A
 LICENSE THAT ALLOWS THIS SCOPE OF WORK . A DETAILED
 PROPOSAL NEEDS TO BE DONE BY LICENSE CONTRACTOR WHO CAN
 PERFORM THE WORK. PROVIDE PROPOSAL WITH CONTRACTOR'S
 LETTERHEAD. THE PROPOSAL NEEDS TO HAVE A DETAILED
 BREAKDOWN THAT INCLUDES THE SPECIFIC HURRICANE STRAPS
 AND AREAS WHERE STRAPS WILL BE INSTALLED IN ORDER TO
 DETERMINE IF THE 15% EXCEPTION #2 OF SEC. 706.8.1
 FBC-EXISTING BUILDING APPLIES.
  
 SEE COPY OF EXCEPTION #2 OF SEC. 706.8.1 FBC-EXISTING
 BUILDING BELOW.
  
 SECTION 706.8.1 ROOF-TO-WALL CONNECTIONS FOR SITE-BUILT
 SINGLE FAMILY RESIDENTIAL STRUCTURES.
 EXCEPTIONS:
 #2) .ROOF-TO-WALL CONNECTIONS SHALL NOT BE REQUIRED
 UNLESS EVALUATION AND INSTALLATION OF CONNECTIONS AT
 GABLE ENDS OR ALL CORNERS CAN BE COMPLETED FOR 15
 PERCENT OF THE COST OF ROOF REPLACEMENT.
  
 B) FOR ADDITIONAL CLARIFICATION: SEC. 706.8 (B)
 FBC-EXISTING BUILDING SPECIES THAT MANDATED ROOF TO
 WALL CONNECTIONS ARE NOT REQUIRED BEYOND A 15 PERCENT
 INCREASE IN THE COST OF RE-ROOFING. THIS MEANS THAT THE
 FIRST 15 PERCENT IS REQUIRED.
 THE EXCEPTION #2 OF SEC. 706.8.1 ONLY APPLIES IF IT IS
 DETERMINED THAT THE INITIAL 15% WILL BE EXEMPT, THEN NO
 ROOF TO WALL CONNECTIONS WILL BE REQUIRED. THAT'S WHY
 THE LICENSE CONTRACTOR DETAILED BREAKDOWN IS REQUIRED.
  
 SECTION 706.8 (B) MANDATED RETROFITS OF THE
 ROOF-TO-WALL CONNECTION SHALL NOT BE REQUIRED BEYOND A
 15 PERCENT INCREASE IN THE COST OF REROOFING.
  
  
  
 C) IF IT IS DETERMINED THAT AT LEAST THE INITIAL 15%
 PERCENT OF THE ROOF TO WALL CONNECTIONS NEEDS TO BE
 DONE, THEN PROVIDE EITHER AN ENGINEERED DESIGN OR A
 PRESCRIPTIVE METHOD AS ALLOWED BY SEC. 706.8.1
 FBC-BUILDING SHOWING HOW THE WORK WILL BE DONE. CLEARLY
 SPECIFY HURRICANE STRAP AND PROPOSED LOCATIONS.
  
  
 ORIGINAL COMMENT:
 2- FLAT ROOF NOA 18-0919.07 SUBMITTED: SELECTED
 ASSEMBLY ON PAGE 21 OF 27 DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES. PROVIDE SIGNED AND SEALED
 RAS 117 CALCULATIONS FOR NAIL ENHANCING AT PERIMETER
 AND CORNER AREAS AS REQUIRED BY GENERAL LIMITATION #7
 ON LAST PAGE OF NOA. NEED THE CALCULATIONS TO MEET THE
 DESIGN PRESSURES REQUIRED BY SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 RESPONSE:
 RAS 117 CALCULATIONS SUBMITTED ARE DONE FOR NOA
 18-1127.18. THIS DOESN'T MATCH NOA 18-0919.07 SUBMITTED
 BY THE ROOFING CONTRACTOR. REVISE AS REQUIRED TO MATCH
 AND PROVIDE TWO COPIES. ONLY ONE COPY WAS PROVIDED THIS
 TIME.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-10-10 Cont ID  
Sent By jgomez Date 2019-10-10 Time 17:11 Rev Time 0.00
Received By jgomez Date 2019-10-10 Time 16:32 Sent To HIST
Notes
2019-10-10 17:11:54RESIDENTIAL (R3), RE-ROOF BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- ACCORDING TO PALM BEACH COUNTY PROPERTY APPRAISER,
 THE VALUE OF THE STRUCTURE IS $350.151. THEREFORE, NEED
 TO COMPLY WITH THE ROOF TO WALL CONNECTIONS AS REQUIRED
 BY SEC. 706.8 FBC-EXISTING BUILDING. SHOW COMPLIANCE.
 NOTE: A SEPARATE SUB-PERMIT IS REQUIRED FOR ROOF TO
 WALL CONNECTIONS. THIS WORK CAN NOT BE DONE BY THE
 ROOFING CONTRACTOR UNLESS ROOFING CONTRACTOR POSSESSES
 THE PROPER LICENSE TO PERFORM THIS WORK.
  
 2- FLAT ROOF NOA 18-0919.07 SUBMITTED: SELECTED
 ASSEMBLY ON PAGE 21 OF 27 DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES. PROVIDE SIGNED AND SEALED
 RAS 117 CALCULATIONS FOR NAIL ENHANCING AT PERIMETER
 AND CORNER AREAS AS REQUIRED BY GENERAL LIMITATION #7
 ON LAST PAGE OF NOA. NEED THE CALCULATIONS TO MEET THE
 DESIGN PRESSURES REQUIRED BY SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 3- ASPHALT SHINGLES ROOF PITCH OF 2:12 TO LESS THAN
 4:12 REQUIRES TWO LAYERS OF UNDERLAYMENT AS REQUIRED BY
 SEC. R905.2.2 FBC-RESIDENTIAL.
  
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2019-10-11 Cont ID  
Sent By fmittner Date 2019-10-11 Time 11:03 Rev Time 0.00
Received By fmittner Date 2019-10-11 Time 11:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-02-07 Cont ID  
Sent By jgomez Date 2020-02-07 Time 10:02 Rev Time 0.00
Received By jgomez Date 2020-02-05 Time 16:27 Sent To I
Notes
2020-02-06 16:27:47RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-01-09 Cont ID  
Sent By jgomez Date 2020-01-09 Time 10:13 Rev Time 0.00
Received By jgomez Date 2020-01-08 Time 18:19 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-11-22 Cont ID  
Sent By jgomez Date 2019-11-22 Time 14:33 Rev Time 0.00
Received By jgomez Date 2019-11-22 Time 13:07 Sent To I
Notes
2019-11-22 13:08:28RESUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-10-11 Cont ID  
Sent By cpuell Date 2019-10-11 Time 12:45 Rev Time 0.00
Received By cpuell Date 2019-10-09 Time 11:16 Sent To  
Notes
***NONE***