Plan Review Details - Permit 19100411
Plan Review Stops For Permit 19100411
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-10-25 Cont ID  
Sent By cthroop Date 2019-10-25 Time 14:56 Rev Time 0.00
Received By cthroop Date 2019-10-25 Time 13:10 Sent To  
Notes
2019-10-25 15:14:06PLAN REVIEW - BUILDING
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. VALUE -
 THE STATED VALUE APPEARS LOW FOR THE PROPOSED SCOPE OF
 WORK.
  
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 2. PROVIDE AN ENLARGED FLOOR PLAN.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 3. PROVIDE FRAMING PLAN FOR EACH ASSEMBLY TYPE THAT
 WORK WILL BE PERFORMED ON. I.E. WALL FRAMING,
 WINDOW/DOOR FRAMING, CEILING DIAPHRAM, ETC.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 4. PROVIDE SEPERATE MECH., ELCTRICAL & PLUMBING PLAN.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-10-21 Cont ID  
Sent By jpearson Date 2019-10-21 Time 15:50 Rev Time 0.00
Received By jpearson Date 2019-10-21 Time 12:38 Sent To  
Notes
2019-10-21 15:50:33CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED BY THE
 PERSON RESPONSIBLE FOR THE DESIGN. BUILDING PLANS SHALL
 BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL
 PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. THE BUILDING
 OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY,
 OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, IN ORDER
 TO PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE
 WITH THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES.WPB
 FBC 107.2.1, 107.3.5; FS 471, 481
 2. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902;
 FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2 AS APPLICABLE.
 3. IF ELECTRICAL PANEL WAS DAMAGED BY WATER OR FIRE,
 THEN THIS ITEM WILL NEED TO BE REPLACED. PROVIDE
 CLARIFICATION AND/OR CORRECTION. NEC 110.3; WPB FBC
 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-10-25 Cont ID  
Sent By cthroop Date 2019-10-25 Time 15:17 Rev Time 0.00
Received By cthroop Date 2019-10-08 Time 13:50 Sent To  
Notes
2019-10-09 13:50:41R12

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-10-25 Cont ID  
Sent By cthroop Date 2019-10-25 Time 15:14 Rev Time 0.00
Received By cthroop Date 2019-10-25 Time 13:10 Sent To  
Notes
2019-10-25 15:17:23PLAN REVIEW - MECHANICAL
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE A MECHANICAL PLAN.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-10-23 Cont ID  
Sent By gjohnson Date 2019-10-23 Time 10:25 Rev Time 0.00
Received By gjohnson Date 2019-10-22 Time 08:18 Sent To  
Notes
2019-10-23 11:51:131ST REVIEW: 19100411
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHOW LOCATION OF WATER HEATER AND PLUMBING FIXTURES
 ON FLOOR PLAN. PER WPB AMEND TO FBC 107.2.1
  
 2. WHAT PLUMBING WORK IS BEING DONE IN THE
 BATHROOMS.PER WPB AMEND TO FBC 107.2.1
  
 3. WHAT TYPE OF WATER HEATER IS BEING INSTALLED IS IT
 THE SAME AS EXISTING.PER WPB AMEND TO FBC 107.2.1
  
 4. PLEASE ENLARGE FLOOR PLAN . BUILDING PLANS SHALL BE
 DRAWN TO A MINIMUM 1/8
 INCH SCALE UPON SUBSTANTIAL PAPER, PER WPB AMEND TO FBC
 107.2.1.3
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]